Temperature Sensor Calibration (General)
Temperature Sensor Calibration: List the installed IntelliCenter™ Control System
sensors (ambient air, pool and solar (if installed). The current sensor temperature
is displayed. Tap sensor name bar to access Sensor Calibration screen.
Sensor Calibration: Adjust the sensor temperature value. Use Up/Down arrow to
Increase or decrease temperature value compared to actual reading. Tap Check
mark to save setting. Tap X to exit without saving setting.
Temperature Sensor Calibration Procedure:
all weather thermometer. Calibrate the air sensor in the shade. The Home
screen displays the Pool, Spa Water Temp and Air Temp setting. Calibrate the
Spa and Pool temperatures the same way as described below for Water and Air
temperature sensor. Be sure the air temperature sensor is located in the shade for
accurate readings. To calibrate the air, pool and spa sensors:
1. First, tap the Pool or Spa button on the Temperature Sensor Calibration screen
to switch on the spa or pool filter pump.
2. Tap Pool Sensor to start the pool calibration.
3. Place the thermometer in the spa or pool. Take an accurate temperature
reading. When calibrating the air sensor, place the thermometer next to the
air sensor. The sensor is normally located near or under the Load Center
or Power Center enclosure, not inside the enclosure. Take an accurate
temperature reading in the shade.
4. On the Calibrate Sensors screen, use the Up or Down buttons to raise or lower
the Air, Pool and Spa temperature to match the corresponding thermometer
temperature reading.
5. Press the OK Calibration button when done.
Water Sensor
Solar Sensor
Air Sensor
75 F °
89 F °
72 F °
Before you start, you need an accurate
IntelliCenter Control System User's Guide
| 43