8.6 - Alarm codes
The alarm codes are displayed in the Reset Alarms menu,
while in the Current Alarm menu and alarm histories textual
information regarding the event is provided.
8.6.1 - General alarm codes
Alarm No. Alarm code
Alarm description
THERMISTOR FAILURE
1
15001
Evaporator entering water thermistor fault
2
15002
Evaporator leaving water thermistor fault
3
15003
Defrost thermistor fault, circuit A
4
15004
Defrost thermistor fault, circuit B
5
15006
Condenser entering water thermistor fault
6
15007
Condenser leaving water thermistor fault
7
15008
Reclaim condenser entering
thermistor fault, circuit A
8
15009
Reclaim condenser leaving
thermistor fault, circuit B
9
15010
OAT thermistor fault
10
15011
Master/slave common water thermistor fault
11
15012
Suction gas thermistor fault, circuit A
12
15013
Suction gas thermistor fault, circuit B
13
15014
Suction gas thermistor fault, circuit C
14
15015
Discharge gas thermistor fault, circuit A
15
15016
Discharge gas thermistor fault, circuit B
16
15017
Discharge gas thermistor fault, circuit C
17
15036
Dry Cooler Leaving thermistor failure
18
15018
Condenser subcooling liquid thermistor fault, circuit A
19
15019
Condenser subcooling liquid thermistor fault, circuit B
20
15021
Space temperature thermistor fault
21
15023
Evaporator heater feedback thermistor fault
22
15024
Economizer gas thermistor fault, circuit A
23
15025
Economizer gas thermistor fault, circuit B
24
15026
Economizer gas thermistor fault, circuit C
25
15030
Free cooling liquid thermistor fault, circuit A
26
15031
Free cooling liquid thermistor fault, circuit B
TRANSDUCER FAILURE
27
12001
Discharge transducer fault, circuit A
28
12002
Discharge transducer fault, circuit B
29
12003
Discharge transducer fault, circuit C
30
12004
Suction transducer fault, circuit A
31
12005
Suction transducer fault, circuit B
32
12006
Suction transducer fault, circuit C
33
12007
Heat reclaim pump-down pressure transducer fault,
circuit A
34
12008
Heat reclaim pump-down pressure transducer fault, circuit B As above
35
12010
Oil pressure transducer fault, circuit A
36
12011
Oil pressure transducer fault, circuit B
37
12012
Oil pressure transducer fault, circuit C
38
12013
Economizer pressure transducer fault, circuit A
39
12014
Economizer pressure transducer fault, circuit B
40
12015
Economizer pressure transducer fault, circuit C
41
12016
Free cooling pump inlet pressure transducer fault,
circuit A
42
12017
Free cooling pump outlet pressure transducer fault, circuit A
43
12018
Free cooling pump inlet pressure transducer fault, circuit B As above
44
12019
Free cooling pump outlet pressure transducer fault, circuit B
47
12024
Water pressure 1 transducer failure (before the evaporator) As above
48
12025
Water pressure 2 transducer failure (after the evaporator)
49
12026
Water pressure 3 transducer failure (before the filter)
50
12027
Water pressure 4 transducer failure (after the filter)
52
12029
Low water pressure
34
Action taken
Reset type
Automatic, if thermistor
Unit shuts down
reading returns to normal
As above
Unit shuts down
As above
Cooling mode: Alert is displayed
Heating mode: Circuit A shuts down
As above
Cooling mode: Alert is displayed
Heating mode: Circuit B shuts down
As above
Heating mode: Unit shuts down
As above
As above
As above
Unit returns to the air-cooled
mode
As above
As above
As above
Unit shuts down
As above
Master/slave operation is disabled
and the unit returns to the
stand-alone mode
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit C shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit C shuts down
As above
None
As above
Unit returns to the air-cooled mode As above
As above
As above
As above
None
As above
None
As above
Economizer function disabled
As above
As above
As above
As above
As above
Free cooling disabled
As above
As above
Automatic, if sensor
Circuit A shuts down
voltage reading
returns to normal
As above
Circuit B shuts down
As above
Circuit C shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit C shuts down
As above
Reclaim session stopped and the
unit returns to the air-cooled
mode
As above
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit C shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit C shuts down
As above
Free cooling stopped and the unit
returns to mechanical cooling
As above
As above
As above
As above
As above
Alert - the values read by the
hydronic kit function are not
reliable
As above
As above
As above
As above
As above
As above
As above
Alert – the unit continues to
operate
Possible cause
Defective thermistor
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
Defective transducer
or installation fault
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
As above
Water loop pressure
too low, risk of pump
cavitation