G u id e Form S pecifi cations
General
The individually mounted low voltage power circuit
breaker shall consist of an electrically and mechanically
trip-free circuit breaker element.
The circuit breaker shall be of the draw-out type capable
of being racked to the disconnect position with the door
closed .
The circuit breaker shall meet ANSI C37. 1 3 , C37 . 1 6 and
C37 .50 and be UL listed.
I nterlocks will be provided to prevent connecting or dis­
connecting the circuit breaker u nless the breaker is open.
The breaker shall be prevented from being closed during
any racking operation. A test position shall be provided to
permit operating the breaker while it is disconnected from
the power circuit.
MicroVersaTrip R MS-9 trip devices sha l l
True rms current sensing for long time character­
istics.
•·
Time current characteristic adjustments of the fixed­
point type, gold plated for maximum reliability and
setting accuracy.
All internal solid-state circuitry of epoxy conformal
coated to resist environmental contamination.
Rating plugs for application flexibility.
Adjustable current setting of 0.5 to 1 . 1 of sensor
tap.
Adjustable long-time delay with four bands.
Integral long-time timing light.
Adjustable instantaneous.
I ntegral test provisions.
Optional c haracteristics
True rms sensing for short time characteristics
Short-time pick up and delay with Ft in or out
High range instantaneous
Ground fault pick up and delay with Ft in or out
Self-powered overload, short circuit, and ground
fault target indicators that continue to give indication
even when control power has been lost
Zone selective i nterlocking
AKR
Other
Circuit Breaker Publ ications
General Installation and Maintenance
AKR-30S, AKRU-30S
G E �)-5019
AKR-30/50/T50
G EK-64459
AKR-75/100 and AKS-50
G EK-64460
AK-25
G E I-50299
AK-50, AKT-50, AK-75, -100
G EK-7303
ECS/SST Supplement
G E I-86135
AKR-3/3A-50
G E K-7310
Installation and Operating I nstallations
AK-25/50, AKT-50, AK-75/1 00
G E K-7302
AKR-30/50, AKRT-50
G EI-86150
AKR-75/1 00
GEI-86151
AKS-50, AKST-50
G EI-86160
G E I-86157
ECS, 1 8, 2A Trip Devices
60
Detailed
This specification covers General Electric Company low
voltage power circuit breakers, types AKA, AKRT, or
AKRU.
The continuous current frame
2000, 3200, 4000.
Circuit breakers shall be manually or electrically operated.
Control voltage for electrically operated breakers shall be :
Volts:
Circuit breakers rms symmetrical interrupting ratings:
240VAC kA
i ncl ude:
480VAC kA
600VAC kA
250VDC kA
Overcurrent trip devices shall be solid-state type
MicroVersaTrip® RMS-9.
Each solid-state trip unit shall be equipped with the follow­
ing field adjustable time current characteristics.
-Adjustable current, and long-time delay
-Integral long-time timing light
-Instantaneous, standard or high range
-Short-time pick up and delay with l2t in or out
-Ground fault pick up and delay with
-Target indicators, overload, short-circuit, and ground
Each circuit breaker shall be equipped with the following
accessories:
-Shunt trip-Voltage
-Undervoltage release-
-Undervoltage release with time delay-
-Overload bell alarm switch
-Lockout device
-Auxiliary Switch:
-Operation counter
Portable MicroVersaTrip RMS-9 test kit
Testing Instructions
G EK-64464
G EK-73300
G EK-64454
G EK-7309
G E K-7301
Renewal Parts
G EF-4527
G E F-4552
G E F-41 49
G E F-4150
G EF-4395
G E F-4396
ratings shall be
fault
Number of contacts:
Normally open "a" type
Normally closed "b" type
MicroVersaT rip T est Set TVTS1
ECS/SST T est Set T AK-TS2
ECS/SST T est Set T AK-TS1
Power Sensor High Current T esting
Power Sensor T est Set
AKR-30/50/T50
AKR-75/100
AK-25
AK-50
AK-75
AK-100
800, 1 600,
l2t
in or out