G u id e Form S pecifi cations
General
The individually mounted low voltage power circuit
breaker shall consist of an electrically and mechanically
trip-free circuit breaker element.
The circuit breaker shall be of the draw-out type capable
of being racked to the disconnect position with the door
closed .
The circuit breaker shall meet ANSI C37. 1 3 , C37 . 1 6 and
C37 .50 and be UL listed.
I nterlocks will be provided to prevent connecting or dis
connecting the circuit breaker u nless the breaker is open.
The breaker shall be prevented from being closed during
any racking operation. A test position shall be provided to
permit operating the breaker while it is disconnected from
the power circuit.
MicroVersaTrip R MS-9 trip devices sha l l
•
True rms current sensing for long time character
istics.
•·
Time current characteristic adjustments of the fixed
point type, gold plated for maximum reliability and
setting accuracy.
•
All internal solid-state circuitry of epoxy conformal
coated to resist environmental contamination.
•
Rating plugs for application flexibility.
•
Adjustable current setting of 0.5 to 1 . 1 of sensor
tap.
•
Adjustable long-time delay with four bands.
•
Integral long-time timing light.
•
Adjustable instantaneous.
•
I ntegral test provisions.
Optional c haracteristics
•
True rms sensing for short time characteristics
•
Short-time pick up and delay with Ft in or out
•
High range instantaneous
•
Ground fault pick up and delay with Ft in or out
•
Self-powered overload, short circuit, and ground
fault target indicators that continue to give indication
even when control power has been lost
•
Zone selective i nterlocking
AKR
Other
Circuit Breaker Publ ications
General Installation and Maintenance
AKR-30S, AKRU-30S
G E �)-5019
AKR-30/50/T50
G EK-64459
AKR-75/100 and AKS-50
G EK-64460
AK-25
G E I-50299
AK-50, AKT-50, AK-75, -100
G EK-7303
ECS/SST Supplement
G E I-86135
AKR-3/3A-50
G E K-7310
Installation and Operating I nstallations
AK-25/50, AKT-50, AK-75/1 00
G E K-7302
AKR-30/50, AKRT-50
G EI-86150
AKR-75/1 00
GEI-86151
AKS-50, AKST-50
G EI-86160
G E I-86157
ECS, 1 8, 2A Trip Devices
60
Detailed
•
This specification covers General Electric Company low
voltage power circuit breakers, types AKA, AKRT, or
AKRU.
•
The continuous current frame
2000, 3200, 4000.
•
Circuit breakers shall be manually or electrically operated.
•
Control voltage for electrically operated breakers shall be :
•
Volts:
•
Circuit breakers rms symmetrical interrupting ratings:
240VAC kA
i ncl ude:
480VAC kA
600VAC kA
250VDC kA
•
Overcurrent trip devices shall be solid-state type
MicroVersaTrip® RMS-9.
•
Each solid-state trip unit shall be equipped with the follow
ing field adjustable time current characteristics.
-Adjustable current, and long-time delay
-Integral long-time timing light
-Instantaneous, standard or high range
-Short-time pick up and delay with l2t in or out
-Ground fault pick up and delay with
-Target indicators, overload, short-circuit, and ground
•
Each circuit breaker shall be equipped with the following
accessories:
-Shunt trip-Voltage
-Undervoltage release-
-Undervoltage release with time delay-
-Overload bell alarm switch
-Lockout device
-Auxiliary Switch:
-Operation counter
•
Portable MicroVersaTrip RMS-9 test kit
Testing Instructions
G EK-64464
G EK-73300
G EK-64454
G EK-7309
G E K-7301
Renewal Parts
G EF-4527
G E F-4552
G E F-41 49
G E F-4150
G EF-4395
G E F-4396
ratings shall be
fault
Number of contacts:
Normally open "a" type
Normally closed "b" type
MicroVersaT rip T est Set TVTS1
ECS/SST T est Set T AK-TS2
ECS/SST T est Set T AK-TS1
Power Sensor High Current T esting
Power Sensor T est Set
AKR-30/50/T50
AKR-75/100
AK-25
AK-50
AK-75
AK-100
800, 1 600,
l2t
in or out