The following function types are supported:
1. Flow compensation, linear. Used for density compensation of volume flow.
2. Flow compensation, square root. Usually, IN_1 is pressure, IN_2 temperature and IN_3 is the
compressibility factor Z.
3. Flow compensation, approximate. Both IN_2 and IN_3 would be connected to the same
temperature.
= √ (_1)×(_2)×(_3)×(_3) × []
4. BTU flow, where IN_1 is inlet temperature, and IN_2 the outlet temperature.
5. Traditional Multiply Divide
6. Average
f = number of inputs used in computation (unusable inputs are not used).
7. Traditional Summer
8. Fourth order polynomial. All inputs except IN_LO (not used) are linked together.