Azure
Set-Up
(Numbers below correspond to connections in diagram on reverse side)
Set motor voltage: 230V w/RED jumper open, 115V w/RED jumper connected (closed)
¡
Set motor rotation: CCWLE w/WHITE jumper open, CWLE w/WHITE jumper connected (closed)
¬
Set motor mode of operation: X-13 w/BLUE jumper open, PSC w/BLUE jumper connected (closed)

For PSC Motor Operation:

First remove power from the HVAC system and set thermostat to OFF.
Connect WHITE NEUTRAL lead to system Neutral.
¡
Connect GREEN/YELLOW GROUND lead to system Ground.
¬
Connect BROWN & WHITE harness to system 24V and Common.
(This is a temporary connection for auto sizing the motor)
Connect RED speed tap 5 to system L1.
(This is a temporary connection for auto sizing the motor)
Apply power to the HVAC system. Make certain to close the blower
housing, and open all supplies and returns. Also make certain the air
filter is clean. Motor will run for approximately 2 minutes and stop to
indicate the auto sizing process is complete.
When motor comes to a complete stop, remove power. NOTE: MOTOR
MUST COME TO A COMPLETE STOP BEFORE POWER IS
REMOVED OR THE MOTOR MAY NOT ACCEPT THE PROGRAM.
BECAUSE THE SYSTEM HAS POWER, DO NOT BE ALARMED IF
THE BLOWER RESTARTS APPROXIMATELY 30 SECONDS AFTER
THE AUTO SIZE IS COMPLETE.
Disconnect the BROWN & WHITE harness and the RED speed tap 5.
ƒ
Connect the 115V speed taps as desired to the HVAC system control
board for Heat/Cool.
Apply power to the HVAC system and test full operation including airflow
test.
Note: For low speed constant fan operation, see Azure
98888
2014 MOTORS & ARMATURES, Inc.
©
All rights reserved. MARS is a registered
trademark of Motors & Armatures, Inc.
Digi-Motor
Quick Reference Guide
MARS Motor No. 10860/10861

WARNING!

installation manual.
www.marsdelivers contractors.com
®

For X-13 Motor Operation:

First remove power from the HVAC system and set
thermostat to OFF.
Remove the GREEN/YELLOW and WHITE lead power
wire harness from the Azure motor.
¡
Plug the factory power harness into Azure
¬
Connect BROWN & WHITE auto sizing harness to
system 24V and Common.
(This is a temporary connection for auto sizing the
motor).
Apply power to the HVAC system. Make certain to
close the blower housing, and open all supplies and
returns. Also make certain the air filter is clean. Motor
will run for approximately 2 minutes and stop to
indicate the auto sizing process is complete.
When motor comes to a complete stop, remove power.
NOTE: MOTOR MUST COME TO A COMPLETE
STOP BEFORE POWER IS REMOVED OR THE
MOTOR MAY NOT ACCEPT THE PROGRAM.
Disconnect and remove the BROWN & WHITE auto
sizing harness.
ƒ
Connect the 24V speed taps as desired to the
thermostat board for heat/cool.
Apply power to the HVAC system and test full
operation including airflow.
.
®
Delivering Confidence

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Azure Digi-Motor 10860 and is the answer not in the manual?

Questions and answers

Summary of Contents for Mars Azure Digi-Motor 10860

  • Page 1 Note: For low speed constant fan operation, see Azure installation manual. operation including airflow. ™ 98888 ® 2014 MOTORS & ARMATURES, Inc. www.marsdelivers contractors.com © All rights reserved. MARS is a registered trademark of Motors & Armatures, Inc. Delivering Confidence...

This manual is also suitable for:

Azure digi-motor 10861

Table of Contents