Download Print this page
Advantech ADAM-4541 User Manual

Advantech ADAM-4541 User Manual

Fiber optic to rs-232/422/485 converter. single-mode fiber optic to rs-232/422/485 converter

Advertisement

Quick Links

S E R I A L
C O M M U N I C A T I O N
ADAM-4541
Fiber Optic to RS-232/422/485 Converter
ADAM-4542
Single-mode Fiber Optic to RS-232/422/485
Converter
Introduction
Fiber optic transmission offers the benefits of
wide bandwidth, immunity to EMI/RFI interference,
and secure data transmission. The ADAM-4541/
ADAM-4542 can be used as an RS-232/422/485
point-to-point or point-to-multipoint connection for
transmitting and converting full/half-duplex signals and
their equivalents within a fiber optic environment.
Fiber optics are the perfect solution for applications
where the transmission medium must be protected
from electrical exposure, lightning, atmospheric
conditions or chemical corrosion.
The ADAM-4541/4542 is specifically designed to link
various machinery equipped with RS-232/422/
485 communication ports (such as computer
systems or manufacturing machines). Using
standard ST connectors, the module's fiber optic
ports can accommodate a wide range of fiber
optic cable sizes, including 62.5/125 (9/125) m.
F eatures
* Compact size economizes space
* Direct plug-and-play
* Easily mounted on a DIN-rail, panel or
piggyback
* Transmission speeds of up to 115.2 kbps
* Optical fibers enable transmission of 2.5 km for
ADAM-4541 and 15 km for ADAM-4542.
* Half/Full-duplex, bidirectional transmission
mode
* Avoids lightning strikes and EMI/RFI
interference
* Prevents damage from electrostatic discharge
* Stable and error-free data transmission
* Automatic internal RS-485 bus supervision
* No external flow control signals required for
RS-485
* Transient suppression and over-current
protection on RS-422/485 data lines
* Reserved space for termination resistors
* LED for power and data flow indication
* Power requirement: +10 ~ +30 V
ADAM and the ADAM logo are trademarks of Advantech.
I N T E R F A C E
F O R
I N D U S T R I A L
User's Manual
Specifications
Fiber Optics
Wavelength
Transmission
Distance
Optical Power
Budget (attenuation)
Power Consumption
* Casing: ABS with captive mounting hardware
* Communication mode: Asynchronous
* Connector: Plug-in screw terminal
* Fiber port: ST
* Transmission mode: Full/Half-duplex,
bidirectional
* Transmission rate: Up to 115.2 kbps
* Operating temperature: -10 ~ 70° C
(14 ~ 158° F)
* Operating humidity: 5 ~ 95% (non-condensing)
* Accessories (included): Nylon DIN-rail
mounting adapter, SECC panel mounting
bracket
Note:
Fiber optics are designed for industrial
applications.
50/125 m, 62.5/125 m, and 100/140 m
are commonly used for multi-mode;
9/125 m are commonly for single-mode.
Unpacking
The ADAM-4541/4542 package includes the
following:
• 1 ADAM-4541 or ADAM-4542 module
• 1 mounting bracket
• 1 User's Manual
• 1 3P to DB 9 cable
DC
(Red:RX, white:TX, Black:GND)
Part No. 2000000330 1st Edition Printed in Taiwan May 1999
A U T O M A T I O N
ADAM-4541
ADAM-4542
multi-mode
single-mode
820 nm
1310 nm
2.5 km
15 km
12.5 dB
9 dB
1 W (typical);
1.6 W (typical);
1.5 W (max.)
2.1W (max.)
Installation

Advertisement

loading
Need help?

Need help?

Do you have a question about the ADAM-4541 and is the answer not in the manual?

Questions and answers

Summary of Contents for Advantech ADAM-4541

  • Page 1 • 1 User's Manual • 1 3P to DB 9 cable * Power requirement: +10 ~ +30 V (Red:RX, white:TX, Black:GND) ADAM and the ADAM logo are trademarks of Advantech. Part No. 2000000330 1st Edition Printed in Taiwan May 1999...
  • Page 2: Block Diagram

    The following tables illustrate the switch settings for the ADAM-454114542: Switch 1 controls the data format. Data can be ADAM-4541/4542 data format settings (SW1) 9, 10, 11 or 12 bits. The factory default is 10 bits: one start bit, eight data bits, one stop bit Data Format and no parity bit.
  • Page 3 #define TIME_OUT 4000 static int base0=0x3f8; static int base1=0x2f8; static char rec[160]; RS-232/422 ADAM-4541 static char cmd[160]; void main () int i,timeout; char rflag,tflag; bioscom(0,0xE3,0); /* Set COM1 as follows: Baud Rate = 9600, Data Bits = 8, */ printf("\nInput string : ");...
  • Page 4: Troubleshooting

    Troubleshooting Possible reasons for malfunction 汗 The TX and RX connection5 are rever5ed. Solution: Make 5ure the fiber connection i5 made 5o that the TX of one end i5 connected to the RX of the other. 汗 Poor connection between the ADAM-454114542 Power supply and the communication port.

This manual is also suitable for:

Adam-4542