360 passive infrared low voltage occupancy sensor with light level, isolated relay and manual on feature (17 pages)
Summary of Contents for Watt Stopper UT-300-1
Page 1
Walk-Through Mode ...3 minutes if no activity after 30 sec. Test Mode .5 sec. upon intial power-up or DIP switch reset Ultrasonic Coverage Model UT-300-1 ..........up to 500 ft Model UT-300-2 ..........up to 1000 ft Model UT-300-3 ..........up to 2000 ft Sensitivity Adjustment ..
UNIT DESCRIPTION The Watt Stopper UT-300 sensors turn lighting systems on and off based on occupancy. The UT-300 can be confi gured to turn lighting on, and hold it on as long as it detects cccupancy. After no movement is detected for a user specifi ed or SmartSet time (5 to 30 minutes) the lights are switched off.
PLACEMENT GUIDELINES Depending upon obstacles such as furniture or partitions, the area of coverage may be less or more than the sensing distances shown in the coverage pattern. This must be considered when planning the number of sensors and their placement. It is also recommended to place the sensor 4 to 6 feet away from air supply ducts.
WIRING DIRECTIONS CAUTION TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING POWER PACKS OR SENSORS. Each Watt Stopper BZ series power pack can supply power for 4 UT-300 sensors. When using more sensors than this, multiple power packs are required.
Page 5
Standard wiring with local off switch Line Voltage Wire Color Legend Line Feed Through Neutral Black White Load #1 Power Pack Low Voltage Load #2 Class 2 (Optional) Line Black Voltage Common Blue Control Out +24V Ceiling Depluggable Terminal Spring Clips (2) Rear Housing Line Voltage Switches...
Manual-On wiring with low voltage momentary switch Line Voltage Line Wire Color Legend Feed Through Neutral Black White Load Power Pack Low Voltage Line Voltage Class 2 Blue +24V Control Out Black Common Man.Switch Common Jumper Man. Switch Back LVS-1 Ceiling Depluggable Terminal...
MOUNTING THE SENSOR Directly to Ceiling 1. Attach the plastic spring clips to Ceiling the edge of the sensor in the slots provided. 2. Cut a 3.5” to 4” round hole in Depluggable terminal the acoustic ceiling tile at the mounting location.
SENSOR ADJUSTMENT The sensors are factory preset to allow for quick installation in most applications. Verifi cation of proper wiring, coverage, and customizing the sensor’s settings can be done using the following procedures. To make adjustments, open the Front Cover with a small screwdriver.
On Mode: Switch 1 Override The Manual ON function is facilitated by installing Normal a momentary switch such as a Watt Stopper LVS-1 Override Momentary Toggle Switch, or RS2-3 Low Voltage Momentary Switch. This switch connects to the Time Delay 3 4 5 sensor’s Manual (Man.) Switch and Common terminals...
Override: Switch 2 To override all sensor functions, set DIP switch 2 to the ON position. The green LED comes on and stays on for the duration of the override. This bypasses the occupancy detection control functions of the sensor, but still allows the lights to be manually controlled with a light switch, if one is installed.
TROUBLESHOOTING CAUTION TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE WORKING WITH OR NEAR HIGH VOLTAGE. For any unexpected operation 1. Check DIP switch settings. 2. Make sure the switches are set according to the defi ned settings in the DIP Switch Setting chart.
Adjustment”). 2. Relocate the sensor. ORDERING INFORMATION Catalog # Description UT-300-1 Ultrasonic Occupancy Sensor, up to 500 sq ft coverage, Low Voltage w/Isolated Relay and Manual On feature UT-300-2 Ultrasonic Occupancy Sensor, up to 1000 sq ft coverage, Low Voltage w/Isolated Relay and Manual On feature...
fi ve years. There are no obligations or liabilities on the part of The Watt Stopper, Inc. for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property, revenue, or profi...
Need help?
Do you have a question about the UT-300-1 and is the answer not in the manual?
Questions and answers