1.0 Introduction
The WH1 wall mounted range of units is designed to provide
mechanical supply and extract ventilation with heat recovery.
The unit is fitted with two independent fans. Each fan has full speed
control for background and boost ventilation rates.
To recover heat from the extract air the heat exchanger block is
utilised. The heat exchanger can recover up to 95% of the normally
wasted heat.
If the unit has integral automatic HX bypass (AB models only)
The bypass damper shall open automatically via a wax actuator
allowing the air to bypass the heat exchanger to deliver fresh
filtered air during the warmer months.
Figure 1. Airflow through unit (Standard unit).
Exhaust air
from house
to outside
Figure 2. Airflow through OH unit (Opposite hand unit).
Supply air
to house
2.0 Installation
Installation must be carried out by competent personnel in
accordance with the appropriate authority and conforming
to all statutory governing regulations. All mains wiring must be in
accordance with the current I.E.E. Regulations, or the appropriate
standards. Ensure that the mains supply (Voltage, Frequency and
Phase) complies with the rating label.
Please note a clear working space is required around the installed
unit to allow the cover to be removed and provide sufficient access
for maintenance such as filter change.
Please allow a minimum of 430mm in front of the MRXBOX95-WH1
unit and 360m in front of the MRXBOX95AB-WH1.
Nuaire: A Trading Division of Polypipe Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA
T: 029 2088 5911 F: 029 2088 7033 E: info@nuaire.co.uk W: www.nuaire.co.uk
Installation and Maintenance
MRXBOX95-WH1 (Standard Unit)
MRXBOX95-WH1-OH (Opposite hand Unit)
MRXBOX95AB-WH1 (Standard Unit)
MRXBOX95AB-WH1-OH (Opposite hand Unit)
Mechanical Ventilation Units with Heat Recovery for Wall Mounting
Intake air
from outside
Supply air
to house
Extract air
from house
Extract air
from house
Exhaust air
from house
to outside
Intake air
from outside
The unit must remain switched on at all times to maintain
ventilation within the dwelling. Turning the unit off will cause
long term damage to the unit and building fabric.
This appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental capabilities,
or lack of experience and knowledge, unless they have been
given supervision or instruction concerning the use of the
appliance by a person for their safety. Children should be
supervised so that they do not play with the appliance.
The fan must be installed indoors, on a suitable wall away from
direct sources of frost, heat, water spray or moisture generation.
For a vibration-free result the unit must be mounted to a solid wall.
2.1 Wall Mounting the MVHR Unit
The unit is designed for wall mounting, only on a solid wall.
A gypsum block or stud/plasterboard wall will not suffice.
1. One part of the mounting bracket (supplied) should be offered up
to the wall, ensuring it's located horizontally. Mark the fixing points
through the pre drilled holes in the bracket and install with screws
(by others), ensuring the interlock side is at the top, (fig. 3).
Figure 3. Fixing the mounting bracket to the wall.
2. Install the unit on the wall by ensuring the bracket fixed to the
rear of the unit interlocks over the wall mounted bracket (fig. 4).
Figure 4. Mounting the unit on the wall mounted bracket.
Note: Care must be taken to ensure the unit is installed true in
all 3 dimensions. Failure to do so may result in overflow from the
internal condensation drip tray.
(See overleaf for mounting option details, on walls or
in the loft space).
1
The EMC Directive
2014/30/EU
The Low Voltage
Directive
2014/35/EU
27. 11. 17. Leaflet Number 671686

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MRXBOX95-WH1 and is the answer not in the manual?

Questions and answers

Summary of Contents for NuAire MRXBOX95-WH1

  • Page 1 Please allow a minimum of 430mm in front of the MRXBOX95-WH1 unit and 360m in front of the MRXBOX95AB-WH1. Nuaire: A Trading Division of Polypipe Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA T: 029 2088 5911 F: 029 2088 7033 E: info@nuaire.co.uk W: www.nuaire.co.uk...
  • Page 2 Installation and Maintenance The WH1 Wall Mounted Range of Units Ducting in the Valve in ceiling. ceiling void. Side view of unit mounted on the block wall in a cupboard. MVHR-DRAIN Condensate drain, uninsulated drain pipe with min 5 fall running to SVP. Ducting in the Valve in ceiling.
  • Page 3: Condensate Drain

    Ideally 150mm diameter or 204 x 60mm rectangular ducting should Nuaire recommend MVHR-DRAIN be used as the primary be used. (Refer to dwelling design drawing, figure 10a and 10b on condensate take-off. (see figure 8b and 8C.
  • Page 4 Installation and Maintenance The WH1 Wall Mounted Range of Units Step 3: The required airflow rates are as follows: 2.7 ADF 2010 Ventilation Calculations the maximum whole dwelling extract ventilation rate (e.g. boost) Design of MVHR Systems should be at least the greater of step 1 and step 2. The MVHR system has been sized for the winter period.
  • Page 5 Nuaire wall mounted unit. MVHR-DRAIN Condensate drain, uninsulated drain pipe with min 5 fall running to SVP. ALSO FROM NUAIRE - range of thermal ducting, an all-in-one insulated ducting system. (see installation document 671620). 27. 11. 17. Leaflet Number 671686...
  • Page 6: Optional Controls

    3 Pole contact separation Grey Light isolator of 3mm. switches Optional speed 3 switch (Double Pole) Kitchen switch 5.1 Optional Controls For further information contact Nuaire on 029 2085 8400. 27. 11. 17. Leaflet Number 671686...
  • Page 7: Status Indication

    The label covering the control has an adhesive Isolation - Before commencing work make sure that the unit, switched live and Nuaire control are electrically panel which should be removed post commissioning to prevent isolated from the mains supply and switched live supply.
  • Page 8 The product warranty applies to the UK mainland and in accordance with Clause 14 of our Conditions of Sale. Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details. 12.0 After Sales...

This manual is also suitable for:

Mrxbox95-wh1-ohMrxbox95ab-wh1-ohMrxbox95ab-wh1

Table of Contents

Save PDF