TCS-NET General Purpose Interface
8

Input/Output Specifications

Digital Inputs and Outputs
1. Functions
The following signals can be set and their states can read through the Modbus (TCB-IFMB640TLE) interface.
However, RO1, RO2 (*1), DI3, and DI6 can be accessed from a central controller such as the 64-way central
control remote controller (TCB-SC642TLE2).
DI6, DI5, DI4, DI1, DI2 and DI3 are photocoupler input signals. Transmit these input signals through contacts, a
switch, or a sink device.
For details of these signals, see the "Connection to External Devices".
Signal classification
Digital output
Relay contact
output
Digital input
Type 1
Connector
RO1+
RO1-
RO2;+
RO2-
RO3+
RO3-
(TCB-IFCG1TLE only)
RO4+
RO4-
(TCB-IFCG1TLE only)
15-EN
Port
Data item
name
DO1
Output type
DO2
DO3
Output point
DO4
Maximum contact current 1 A
Maximum contact voltage 250 VAC
DI1
Input type
DI2
Number of input points
DI3
Input resistance
DI4
DI5
Minimum input ON
DI6
current
Maximum allowable input
ON current
Maximum input OFF
current
SW5
Signal name
-2
Relay 1 ch output for
general purpose
interface
OFF
OFF
ON
Relay 2 ch output for
general purpose
interface
OFF
OFF
OFF
ON
Relay 3 ch output for
general purpose
*
interface
Relay 4 ch output for
general purpose
*
interface
TCB-IFCG1TLE
"a" or "b" contact
selectable
4
30 VDC
Photocoupler insulation
6
100 Ω
2 mA
30 mA
0.05 mA
SW5
SW5
-3
-4
Relay contact output
Normally open. Closed for 250 ms when Relay 1 setup
OFF
*
request is turned ON. (*1)
Normally open. Closed for 250 ms each time Relay 1 setup
ON
*
request is turned ON or OFF. HA output type (*1)
Normally open. Continuously closed when Relay 1 setup
*
*
request is ON, and opened when Relay 1 setup request is
OFF. (*2)
Relay contact output
Normally closed. Opened for 250 ms when Relay 1 setup
OFF
ON
request is turned OFF. (*1)
Normally open. Closed for 250 ms when Relay 1 setup
OFF
OFF
request is turned OFF. (*1)
Normally open. Closed when Relay 2 setup request is ON,
ON
*
and opened when Relay 2 setup request is OFF.
Normally open. Closed when Relay 2 setup request is ON,
*
*
and opened when Relay 2 setup request is OFF.
Relay contact output. Normally open.
*
*
Closed when Relay 3 setup request is ON, and opened
when Relay 3 setup request is OFF.
Relay contact output. Normally open.
Closed when Relay 4 setup request is ON, and opened
*
*
when Relay 4 setup request is OFF.
– 16 –
Installation Manual
TCB-IFCG2TLE
"a" or "b" contact
selectable
2
1 A
250 VAC
30 VDC
Photocoupler insulation
1
100 Ω
2 mA
30 mA
0.05 mA
Operation
In/
Out
Out
Out
Out
Out