For the measurement of C
side and IN A to the HV side (see Figure 5-4 blow).
HV
C
HL
C
H
Figure 5-4: CP TD1 connected to a two-winding transformer for the measurement of
With this setup 3 configurations are available as well (see Table 5-2 below). As C
before, usually only C
L
Table 5-2: Modes available with a measurement setup as seen in Figure 5-4
Mode
UST-A
GSTg-A or GSTg-(A+B) Guarded
GSTg-B
OMICRON
the setup has to be changed. The HV output has to be connected to the LV
L
LV
C
L
is measured in this second measurement.
IN A
Measured
Measured
CP TD 1
Ground
Guarded
Measured
Measured
Power transformers
HV output
IN B
IN A
C
and C
HL
L
has been measured
HL
Result
C
HL
C
L
C
+ C
HL
L
43