Micropack FDS301 Safety & Technical Manual

Micropack FDS301 Safety & Technical Manual

Visual flame detector

Advertisement

 
FDS301
VISUAL FLAME
DETECTOR
SAFETY & TECHNICAL
MANUAL
Ref: 2200.5009
micropack.co.uk

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FDS301 and is the answer not in the manual?

Questions and answers

Summary of Contents for Micropack FDS301

  • Page 1   FDS301 VISUAL FLAME DETECTOR SAFETY & TECHNICAL MANUAL Ref: 2200.5009 micropack.co.uk...
  • Page 2: Table Of Contents

    System Design Guidelines Earthing & Screening Requirements Power Supply RS485 Communications HART Protocol Cable Selection 4.5.1 DC Power 4.5.2 Video 4.5.3 RS485 Communication This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2016...
  • Page 3 FDS301 Flame Detector FDS301 Safety and Technical Manual Ref: 2200.5009 Rev: 2.3 ECN 4434 Application Guidelines Positioning Requirements Detection Coverage Exposure to Flare Radiation Optical Contamination Enclosed Areas Detector Sensitivity Maintenance and Commissioning Procedure Functional Testing Fault Finding Removal of the Electronics...
  • Page 4: Introduction

    This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 5: Safety Instructions

    FDS301 Flame Detector FDS301 Safety and Technical Manual Ref: 2200.5009 Rev: 2.3 ECN 4434 Safety Instructions For the correct and effective use of this equipment, to maintain safety and avoid hazards it is essential that you read and understand these instructions fully, act accordingly BEFORE installing, operating or maintaining the equipment.
  • Page 6: Vds En54 Part 10 Limitations Of Use

    As the FDS301 responds to visible flame the FDS301 cannot be used in locations where flare stacks are within its field of view without triggering alarms. The FDS301 is unable to detect fires that are invisible to the naked eye, such as those using pure hydrogen, methanol and sulphur as fuel.
  • Page 7 The FS301 flame simulator can be used to verify correct detector positioning and coverage (see section 6.2 of this document). • The FDS301 has one sensitivity setting, this is factory set, and no changes can be made to set-up except by fully trained Micropack engineers. •...
  • Page 8: Installation

    The enclosure comprises the front enclosure cover (including the faceplate window), the rear enclosure cover, the enclosure body (with certification label), and the mounting bracket. This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 9: Mounting & Orientation

    FDS301 Flame Detector FDS301 Safety and Technical Manual Ref: 2200.5009 Rev: 2.3 ECN 4434 Mounting & Orientation The mounting bracket allows the detector’s vertical orientation to be adjusted from 0 to 45°, and allows a horizontal rotation of +/-45°. Figure 1: Detector Mounting Bracket & Orientation Status led must be below the lens.
  • Page 10 When mounting on a wall in this orientation allow for the cable gland and cable as this may restrict the downward rotation of the detector. This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 11: Wiring Procedure

    FDS301 Flame Detector FDS301 Safety and Technical Manual Ref: 2200.5009 Rev: 2.3 ECN 4434 Wiring Procedure The wiring terminals are located in the rear section of the detector enclosure and are accessible by removal of the end cap. The front section of the enclosure should only be accessed by trained personnel.
  • Page 12: 4-20Ma Output

    Video + Video ‐‐‐ 10 11 12 13 RS485A 14 RS485B *Tied to spare terminal at control panel to allow RS485 communication with detector. This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 13 Information for wiring in the 4-20mA mode listed in figures 5 to 8 on previous page: 3 Pair Termination: Fully functional detector with continuous video and 4-20mA alarm output. Reversal of polarity across terminals 1 & 2 will enable Micropack RS485 communication. 2 Pair Termination: 4-20mA output only with reversal of polarity across terminals 1 &...
  • Page 14: Relay Output

    Figure 12: 4 Pair Termination FDS301 Terminal 24Vdc 0Vdc Sense Return Signal Video Output Video + Video ‐‐‐ 10 11 12 ALRM 13 RS485A 14 RS485B This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 15: Installation Checklist

    Fully functional detector with continuous video, alarm and fault relays as well as permanent Micropack RS485 communication connections. Micropack RS485 communication should only be accessed by trained personnel. EOL and Alarm resistor values defined by the client and the control system which the detectors are being integrated into.
  • Page 16: Electrical

    All cable screens (shield) should be connected to the local clean earth at the control panel. The screens and twisted pairs should be maintained to within 1” (25.4mm) of the terminations. This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 17: System Design Guidelines

    A&B (3&4) whilst the power supply polarity is reversed. Using Micropack Simple Apps software, the RS485 channel can be used to view and/or modify detector firmware, version, configuration or download recorded alarm video from SD card. Contact Micropack for Simple Apps software.
  • Page 18: Hart Protocol

    This section specifies suitable cable characteristics to ensure correct operation of the flame detector. There are several different wiring methods available, as detailed in 3.3.1 and 3.3.2 of this manual. This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 19: Dc Power

    FDS301 Flame Detector FDS301 Safety and Technical Manual Ref: 2200.5009 Rev: 2.3 ECN 4434 4.5.1 DC Power NOTE: Table 2 shows absolute maximums for cable lengths; try not to approach these values. Table 2: Maximum Cable Lengths (24V supply) Installation based...
  • Page 20: Video

    The characteristic impedance of a transmission line is the same as for the video above. micropack.co.uk This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 21: Application Guidelines

    All these issues are of crucial importance to a successful installation and they should be afforded great attention during the detailed design, construction and commissioning phases of the work. This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 22: Detection Coverage

    Figure 14: FDS301 Coverage & Field of View Software analysis of the actual detector coverage may be required to ensure adequate coverage of the hazards. This analysis can also be used to optimise the number of detectors.
  • Page 23: Enclosed Areas

    Gasoline pan Fire 0.3m x 0.3m pan 44m (144 feet) 0.6m x 0.6m pan 61m (200 feet) Silane 0.6m plume 13m(42 feet) This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 24: Maintenance And Commissioning

    FDS301 Flame Detector FDS301 Safety and Technical Manual Ref: 2200.5009 Rev: 2.3 ECN 4434 Maintenance and Commissioning Procedure This maintenance schedule / commissioning procedure is intended for guidance only. The actual level of maintenance required will depend on the severity of the operating environment and the likelihood of damage or the rate of contamination from oil, sea spray, deluge system etc.
  • Page 25 Check the mA output is indicating 0mA. De-isolate the detector and ensure the status LED indicates green. Reinstate the detector back into service. This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 26: Functional Testing

    Refer to the FS301 Flame Simulator user manual (ref. 2301.6042) for instructions on its use. Failure of the detector to respond to the FS301 flame simulator should be reported to Micropack (Engineering) Limited (info@micropack.co.uk). It should be ensured that the flame detector and flame simulator are being used correctly in the first instance by referring to their manuals.
  • Page 27: Fault Finding

    Check the most obvious possible causes first. • Work systematically through the problem. • Keep good notes on the original problem, each step taken and the results observed. This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 28: Led Indication

    Ref: 2200.5009 Rev: 2.3 ECN 4434 LED Indication The detector LED indicator is used to reveal the detector’s current state, as shown below: Figure 15: FDS301 Fascia - Status LED STATUS LED Table 7: LED Status Diagnostic Chart LED Colour...
  • Page 29: Power Fault

    If there is video directly from the FDS301 then the control system must be examined for failures. This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 30: Technical Specification

    FDS301 Flame Detector FDS301 Safety and Technical Manual Ref: 2200.5009 Rev: 2.3 ECN 4434 Technical Specification Electrical Specification Parameter Units Comment Power Supply Supply Voltage outside Canada Inc. ripple Supply Voltage inside Canada Inc. ripple Supply Ripple Vpk-pk Detector Power Consumption (no heater) Detector Power Consumption (inc.
  • Page 31: Mechanical Specification

    Comment Operating Ambient Temperature °C - 60 + 85 Storage Ambient Temperature °C - 60 + 85 Relative Humidity % RH Condensing This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 32: Certification And Approvals

    FDS301 Flame Detector FDS301 Safety and Technical Manual Ref: 2200.5009 Rev: 2.3 ECN 4434 Certification and Approvals Parameter Authority/Standard Approval Certificate Hazardous Area Certification ATEX Ex II 2 G Ex db IIC T4 IP66 FM07ATEX0033 Hazardous Area Certification NEC 505...
  • Page 33: Appendix A Acronyms, Terms & Abbreviations

    Nano Farad, Pico Farad – Capacitance Personal Computer (IBM PC Compatible) R or Ω Ohms (electrical resistance) Voltage Versus Watts (Wattage) This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 34: Appendix B Help Us To Help You

    FDS301 Flame Detector FDS301 Safety and Technical Manual Ref: 2200.5009 Rev: 2.3 ECN 4434 Appendix B - Help us to help you From: QA Department Micropack (Engineering) Limited Fire Training Centre Schoolhill, Portlethen AB12 4RR Tel: +44 (0) 1224 784055...
  • Page 35: Appendix Ciec 61508 Failure Rate Data

    Clean window of detector using a soft cloth and detergent. Perform a test of the FDS301 using the FS301. Remove the by-pass/inhibit and restore normal operation. This document is strictly private and confidential, reproduction without Micropack approval is prohibited. © Micropack Engineering Ltd, 2015...
  • Page 36: Appendix Dfds301 Field Of View

    FDS301 Flame Detector FDS301 Safety and Technical Manual Ref: 2200.5009 Rev: 2.3 ECN 4434 Appendix D - FDS301 Field of View Horizontal field of view to a 0.1 metre2 N-heptane pan fire with an alarm response time of less than 10 seconds 100%=44 metres Horizontal field of view to a 0.1 metre2 N-heptane pan fire with an alarm response time of less...
  • Page 37 Portlethen, Aberdeen AB12 4RR Colorado, 80526 Tel: +44 (0)1224 784055 Tel: +1 970 377 2230 Fax: +44 (0)1224 784056 Fax: +1 970 377 2273 Email: sales@micropack.co.uk Email: info@micropackamericas.com ISO9001:2008 micropack.co.uk micropackamericas.com Certified Subject to modifications. © 2015 Micropack (Engineering) Ltd.