Table 2 - Modbus address list

(frequently needed measured values)
C
The addresses contained in the description
can be adjusted directly on the device in
the range from 0 to 800.
The address range 800-999 is available for
programming comparators on the device.
The addresses above 1000 can only be
processed via modbus!
Modbus
address
Address
via Display
19000
808
19002
810
19004
812
19006
814
19008
816
19010
818
19012
860
19014
862
19016
864
19018
866
19020
868
19022
870
19024
872
19026
874
19028
884
19030
886
110
Format
RD/WR
Unit
float
RD
V
float
RD
V
float
RD
V
float
RD
V
float
RD
V
float
RD
V
float
RD
A
float
RD
A
float
RD
A
float
RD
A
float
RD
W
float
RD
W
float
RD
W
float
RD
W
float
RD
VA
float
RD
VA
C
A complete overview of the parameters and
measured values as well as explanations
regarding the selected measured values
is filed in the document "Modbus Address
List" on the CD or Internet.
Note
Voltage L1-N
Voltage L2-N
Voltage L3-N
Voltage L1-L2
Voltage L2-L3
Voltage L3-L1
Current, L1
Current, L2
Current, L3
Vector sum; IN=I1+I2+I3
Real power L1
Real power L2
Real power L3
Sum; Psum3=P1+P2+P3
Apparent power S L1
Apparent power S L2