Indicates the drive is not in the trip state. If Pr 10.36 is On(1) and an auto-reset is being used, this bit is not cleared until all auto-resets have been
attempted and the next trip occurs.
10.02
Drive active
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
Indicates that the inverter output is active.
10.03
Zero speed
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
This bit is set to On(1) when the absolute value of the ramp output is at or below the threshold programmed into Pr 3.05.
10.04
Running at or below minimum speed
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
In bipolar mode (Pr 1.10 = On) this parameter is the same as zero speed (Pr 10.03).
In unipolar mode, this parameter is set if the absolute value of the ramp output is at or below minimum speed + 0.5Hz. Minimum speed is defined by
Pr 1.07.
The parameter is only set if the drive is running.
10.05
Below set speed
10.06
At speed
10.07
Above set speed
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
These flags are set by the speed detector in menu 3. These flags are only set if the drive is running.
See Pr 3.06 on page 58.
10.08
Load reached
Bit
SP
Coding
1
Range
OFF(0) or On(1)
Update rate
Background
Indicates that the modulus of the active current is greater or equal to the rated active current as defined in menu 4.