2. Press the Enter button from the Main Menu to view the Parameters screen for the
mode that is currently active.

6.2.3: Using Reset Mode

Reset Mode has two options:
• Reset: Demand (rStd): resets the Max and Min values
• Reset: Energy (rStE): resets the energy accumulator fields
1. Press the Enter button while
either rStd or rStE is in the A win-
dow. The Reset Demand No or
Reset Energy No screen appears.
• If you press the Enter button
again, the Main Menu appears,
with the next mode in the A
window. (The Down button
does not affect this screen.)
• If you press the Right button,
the Reset Demand YES or
Reset Energy YES screen
appears. Press Enter to per-
form a reset.
NOTE: If Password protection is enabled for reset, you must enter the four digit
password before you can reset the meter. (See Chapter 5: Communication Installation
on page 5-1, for information on Password protection.) To enter a password, follow the
instructions in 6.2.4: Entering a Password on page 6-6.
CAUTION! Reset Demand YES resets all Max and Min values.
2. Once you have performed a reset, the screen displays either "rSt dMd donE" or
"rSt EnEr donE"and then resumes auto-scrolling parameters.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
6: Using the Shark® 200 Meter
MENU
ENTER
-
A
-
B
-
C
MENU
ENTER
-
A
-
B
-
C
#
Doc
E149701
MENU
ENTER
-
A
-
B
-
C
MENU
ENTER
-
A
-
B
-
C
6-5

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Shark 200 and is the answer not in the manual?

Questions and answers

William Hubert
March 24, 2025

how to setup 4-20 ma I/O card for 360 KW

1 comments:
Mr. Anderson
March 24, 2025

To set up the 4-20 mA I/O card for the Electro Industries Shark 200 meter for 360 kW:

1. Connect to the Meter: Ensure you are connected to the meter using the Communicator EXT™ software.
2. Access the I/O Card Configuration: Navigate to the profile section where the I/O card slots are displayed.
3. Select the 4-20 mA Output Card: Identify the slot where the 4-20 mA card is installed and select it.
4. Set Output Scaling:
- Define the source register that corresponds to real power (kW).
- Set the low-end value (e.g., 0 kW) to output 4 mA.
- Set the high-end value (e.g., 360 kW) to output 20 mA.
5. Apply and Save Settings: Confirm changes and save them in the meter configuration.

This setup ensures that the output current will linearly scale from 4 mA at 0 kW to 20 mA at 360 kW.