BECS BECSys5 Operation And Maintenance Manual

BECS BECSys5 Operation And Maintenance Manual

Water chemistry controller
Table of Contents

Advertisement

Operation and Maintenance Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BECSys5 and is the answer not in the manual?

Questions and answers

Phillip Touchette
April 6, 2025

how do I add free chlorine to a Becsys5 controller

1 comments:
Mr. Anderson
April 6, 2025

To add free chlorine control to a BECSys5 controller:

1. Install the free chlorine (free Cl) probe at the bottom as indicated.
2. Set the Control Source to the right side of the screen and select "free Cl."
3. Ensure the free Cl input is enabled in the controller settings.
4. You can choose to control using ORP, free Cl, or both if the free Cl probe is used.
5. The controller may override other settings to maintain free Cl control and prevent ORP from dropping out of range.
6. For super chlorination or chlorine booster pump control, additional configuration options become available when free Cl input is enabled.

Reset the failsafe using the "Reset Fail/Safe" button if needed to re-enable normal chlorine control.

This answer is automatically generated

Summary of Contents for BECS BECSys5

  • Page 1 Operation and Maintenance Manual...
  • Page 3: Table Of Contents

    A – 5.12: UV Turndown ........15   A – 5.13: Polymer ..........16   A – 5.14: Recirculation Pump......16   A – 5.9.1: VFD Control: ........16   9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 5: Warnings

    Rev: L13 Warnings Pay particular attention to the following warnings encountered while utilizing your BECSys5 Water Chemistry Controller: Warning: Various other warning boxes may be found throughout the manual text. Caution: Various caution boxes may be found throughout the manual text.
  • Page 6: General Guidelines

    Environmental Conditions The BECSys5 is housed in a NEMA 4X (IP65) enclosure. It should not be used in explosive environments. The BECSys5 should be mounted so that adequate ventilation is provided around the enclosure, preventing general environmental specifications from being exceeded (see table below).
  • Page 7: Nsf Suggested Operation Ranges

    Pressure Swichgage 0 – 50 PSI Differential Swichgage 0 – 50 PSI Conductivity Sensor 0 – 20,000 micromho Turbidimeter 0 – 20.0 NTU Flowmeter 0 – 655.35 Kgpm Page 3 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 8: Section A: Programming The Controller

    Pressing and holding the +/- button disables the access code, while pressing enter will enable and set the access code to the value on the screen. Page 4 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 9: A - 3.2: The Menu Screens

    For some values, certain keys may take on special functions that are explained in the lower lines of the screen. The Down/up message in the example above is one of them. Page 5 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 10: A - 3.3: The Lock Screen Key

     Alarm Hysteresis (Mgr): This value sets the amount that the ORP reading has to rise above the high alarm or fall below the low alarm before the alarm will shut off. Page 6 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 11: A - 4.3: Cl Inputs Setup

    The value entered must be 0.5 ppm or greater.  Reset Calibration (Op): Resets the calibration to the original factory setting. Page 7 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 12: A - 4.5: Conductivity/Tds Setup

     Low Alarm (Op): The low alarm will activate off. when the pressure reaches or falls below this setting. You may disable this alarm by holding down the +/- key for 1 second. Page 8 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 13: A - 4.10.3: Filter Differential Pressure

    +/- key for 1 second. If the recirc pump is assigned a relay, the high strainer vacuum alarm will trigger an emergency off of the system. Page 9 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 14: A - 5: Control Outputs

    During this time, the feeder will turn on for a percentage of the Time Base and turn off for the remainder. Page 10 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 15: A - 5.2: Chlorine Control

    The closer to set point, the less time the feeder is ON. Page 11 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 16 The first week is fixed to be the week of free Cl control so that the ORP will not drop out Sunday, January 2 , 2000 and every four of a programmed range. weeks afterwards. Page 12 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 17: A - 5.3: Chlorine Booster Control

    Reset Fail/Safe LED on the face one has been completed. panel and display a message to alert the operator. If in TBP Pause mode, the controller will reset the timer. Page 13 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 18: A - 5.5: Dechlorination

    ORP, or both to use to control the Ozone feed.  ORP Set Point (Op): This option is only shown if the Control Input is ORP or Both. This value sets the Page 14 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 19: A - 5.8: Autofill

    UV turndown relay turns on. a message to alert the operator. An operator must reset the failsafe through the Reset Fail/safe button to re-enable normal control. Page 15 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 20: A - 5.13: Polymer

     Ozone Fireman Switch (Op): This option is only shown if a relay is assigned to the Ozone control. This value sets the minimum amount of time to leave Page 16 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 21: A - 6: Control Options

    GOING TO SLEEP again once all Warning: Disabling the pH lockout will allow feeds have been satisfied again. for chemical overfeeds which may damage equipment or harm patrons. Page 17 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 22: A - 7: Calculations

    IP address information must be set manually via the remaining items listed here.  IP Address (Mgr): This option is only shown if DHCP is disabled. Sets the controllers IP address. Page 18 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 23: A - 8.2.4: Installed Options

    (the part after the @) into the second screen. Page 19 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 24: A - 8.4: Date, Time & Units

    If you have a 4-20 mA board installed in your system you may choose 4-20mA outputs from the main menu. By selecting one of the 4-20mA output channels you will be able to select the following: Page 20 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 25: A - 11: Access Menu

    If at anytime you wish to logon as another access level, you may do so by pressing the Menu key and selecting Logon from the main menu. Page 21 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 26: Section B: The Normal Display

    Super chlorination, dechlorination, sensor wash, and power saver all display status information in this area Page 22 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 27: Section C: Using The Face Panel Quick Keys

    Relay Modules connected to the controller, showing what is assigned to those relays and their Manual Flow Rate changes the VFD output to current state. maintain a specified flow rate. Page 23 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 28: C - 3: The Cal Key (Calibration)

    All the other relays will remain off until the emergency off button is pressed again. Page 24 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 29: Section D: Maintenance

    After removing the sensor from inside. Tighten slowly to the stop. from the flow cell, clean it as in routine Page 25 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 30: D - 3: Total Chlorine Sensor

    O-Ring retainer. membrane cap. Warning: Never touch the electrode finger. Fill the membrane cap to the edge with the electrolyte. Make sure there are no bubbles. Page 26 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 31: D - 4: Conductivity Sensor

    Chlorine Sensor polarizes the surface of the gold cathode. The polarization period (one hour) must elapse before calibration is performed based on the results acquired through the use of a DPD test kit. Page 27 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 32: Section E: Feed Charts

    1.25 ts 0.100 ts 0.167 ts 0.250 ts 0.50 ts 0.75 ts 1.00 ts ts = teaspoon tb = tablespoon cp = one cup (8 fl oz) Page 28 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132...
  • Page 33: E - 2: Pool Feed Charts

    = one cup (8 fl oz) pt = one pt (16 fl oz) qt = one quart (32 fl oz) gl = one gallon (128 fl oz) lb =pounds of dry chemical Page 29 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 34: Section F: Replacement Parts

    9660003 Temperature Sensor (10’ cable) [range: 32°F to 212°F (0°C to 100°C)] Documentation Flow Switches 8620007 BECSys5 Operation and Maintenance Manual 9660006 Reed flow switch [Switch Point (On): 2.0 gpm] 8620013 BECSys5 Installation and Technical Manual 9660007 Rotary flow switch [Switch Point (On): 1.5 gpm]...
  • Page 35 Nipple, ½” Close 8060621 Sample Valve, ¼” Ball Cock 8060546 Ball Valve ½” PVC 9060549 S80 Bushing, PVC ¾ x ½ 9060544 Pressure Gauge 8060673 Pressure Regulator Page 31 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com...
  • Page 36: Section G: Warranty

    BECS will repair, or if repair is not possible, replace the defective part or parts of the BECSys controller. BECS will have the sole right to determine whether to repair or replace a product. BECS will not be responsible for any expense associated with installation of repaired or replacement parts.
  • Page 37 Louis, Missouri is home to an exceptional design team, and all manufacturing is performed onsite at this facility where we can personally assure the quality of our products. The BECS commitment to excellence drives the most innovative new products and unparalleled customer service.

Table of Contents

Save PDF