ELREHA TAR 1260 Technical Manual

ELREHA TAR 1260 Technical Manual

Tar x260 dual-setpoint and pi-controller for temperature-, pressure or humidity

Advertisement

TAR
1260
TAR
3260
TAR
5260
TAR 19260
Please note Safety
Instructions !
l Usable as: Temperature-, Humidity-,
Pressure- or Cold Storage Controller
with relay outputs
l Operation Modes: Double Single
Setpoint, Dual Setpoint, Proportional-/
PI-Controller, Step Controller,
Setpoint shift by 2
Cold Storage Control with Cyclic
Defrost
l Output 0-10VDC delivers control
deviation or an actual value image
Dual-Setpoint and PI-Controller for
Temperature-, Pressure or Humidity
nd
sensor,
ELEKTRONISCHE REGELUNGEN GMBH
6)4N $
Software Version from 040603
Nr. 5311032-03/07 E
l Limit value alarm, Alarm relay
l Inputs for PTC/Pt1000 and 4...20 mA
for any 2-wire-transmitters
l 2. setpoint by Digital Input
l Minimum Stop-time
l RS-485-Interface
l 4 different housings
Technical Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TAR 1260 and is the answer not in the manual?

Questions and answers

Summary of Contents for ELREHA TAR 1260

  • Page 1 Technical Manual Dual-Setpoint and PI-Controller for Temperature-, Pressure or Humidity 6)4N $ Software Version from 040603 Nr. 5311032-03/07 E 1260 3260 5260 TAR 19260 Please note Safety Instructions ! l Usable as: Temperature-, Humidity-, l Limit value alarm, Alarm relay l Inputs for PTC/Pt1000 and 4...20 mA Pressure- or Cold Storage Controller with relay outputs...
  • Page 2 • All used temperature sensors must be identical. Never Housing, Protection use PTC (TF 201) and PT1000 (TF 501) mixed. This will TAR 1260 ....77 x 35 mm, IP 54 from front not work. TAR (2)3260 .... for 35mm DIN-rail, IP 30 TAR (2)5260 ....
  • Page 3 Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260 Page 3 Operating Parameters (setpoints, times, etc.) Operating Elements If ON in op-mode 3: All selectable parameters hold a parameter number (e.g. P03), you Setpoint just shifted will find a listing on the next page. If ON in op-mode 4: Stage 1 ON/OFF Defrost runs...
  • Page 4 Page 4 Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260 Parameter Listing Param.-No Code Description Default val. Limits Your value x x x x - Actual value of sensor/transmitter 1 x x - Actual value of sensor 2 x x x x - Control setpoint 1 ( Absolute value ) Within the limits set by P10/P11...
  • Page 5 Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260 Page 5 Parameter Listing (contin.) Parameter- Code Description Default val. Limits Your value number x x x x -- Remaining idle time relay 1 Display only ! x x x x -- Remaining idle time relay 2 Display only ! x x x x -- Remaining time Digital Input delay (OK 1)
  • Page 6 Page 6 Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260 Functional Description Sensor connection Example: Switching hysteresis For the setpoints P03 / P04 you can fix a The controller operates either with temperature - Control Setpoint 1 P03 = 10°C switching hysteresis with parameters P12 and sensors of the types TF201 (PTCs) and TF 501 - Limit value P19 = 20°C,...
  • Page 7 Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260 Page 7 2 = Freezing (DF) Alarm relay characteristic Defrost Function Used for temperature applications below 0°C. The load would be switched by the Parameter P09 defines if the alarm relay is In operation mode 4 (P14=4) a simple defrost NC-contact, this enables that the load will affected from the actual value P01 or P02 and function can be used.
  • Page 8 2 /night-setpoint. Setpoints will be increased / decreased by the value of P06. The type TAR 1260 has no optocoupler input, the P34 = 2 No voltage (1260: contact open) at Digital Input 1 starts function will be activated by opening an external, an external alarm.
  • Page 9 Unfortunately, supply voltage and control input are not isolated in actuators, this may destroy the TAR 1260. Because of this: If a TAR 1260 must control a servo drive, the TAR must be supplied by an own, separate transformer !
  • Page 10 Page 10 Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260 Dimensions TAR 1260 56 (2.2) 3 (.12) (.47) 0-10V + 1 2 V N D O ELREHA O K 1 76 (3.0) 4 . . 2 0 m A At controllers which are produced before 3/2002,...
  • Page 11 Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260 Page 11 Dimensions TAR 3260 Temperature Sensor Connection TAR 3260 105 (4.13) 2 0 2 1 2 5 2 6 3 5 3 6 3 7 3 8 2 2 2 3 2 9 3 0 3 5 3 6 T A R 4 8 5...
  • Page 12 Page 12 Technical Manual Temperature-, Humidity-, Pressure-Controller TAR x260 Dimensions TAR 5260 Temperature Sensor Connection TAR 5260 E L R E H A 1 7 1 8 2 3 2 4 119 (4.69) sensor 1 mains sensor 2 relay K1 4-20 mA IN 0 - 1 0 V = O U T G N D...
  • Page 13 E L R E H A 162,5 - Wiring diagram shows a connector equal to DIN 41612, type 'F', rear view. - The 'terminal' numbers are used in ELREHA's pre- wired subracks. Humidity Transmitter Connection TAR 19260 terminal terminal O K 1 relay 1...
  • Page 14 IEC 1000-4-1, IEC 1000-4-2, IEC 1000-4-3*, IEC 1000-4-4, IEC 1000-4-5, EN 55011 B, EN 50081, part 1 and 2; EN 50082, part 1 and 2, EN 61010 part 1, EN 61010-1/A2 part 1/A1 This statement is made from the manufacturer / importer ELREHA Elektronische Regelungen GmbH Klaus Birkner, Developement and 68766 Hockenheim, Germany...

This manual is also suitable for:

Tar 3260Tar 5260Tar 19260

Table of Contents

Save PDF