Sinamics Perfect Harmony Gh180 6Sr41 Manufactured In Nma Nuernberg, Germany - Siemens GH180 Operating Instructions Manual

Medium-voltage drive sinamics perfect harmony
Hide thumbs Also See for GH180:
Table of Contents

Advertisement

Display Name
Mtr Tem Over-Load Fault
Motor Over Volt Alarm
Motor Over Volt Fault
IOC
Under Load Alarm
Under Load Alarm
Output Phase Imbal
Output Phase Open
In Torque Limit
In Torq Limit Rollback
Minimum Speed Trip
Loss of Field Current

SINAMICS PERFECT HARMONY GH180 6SR41 manufactured in NMA Nuernberg, Germany

Operating Instructions Rev.201706301306
Actual Name
Type
Motor Tempera‐
F
ture (or Motor
Current) Over-
Load Fault
Motor Over Volt‐
A
age Alarm
Motor Over Volt‐
F
age
Fault
Instantanteous
F
Over Current
same
A
same
F
Output Phase
A
Imbalance
same
A
same
A
In Torque Limit
F/A
Rollback
same
F/A
same
F/A
Enable
Potential Cause
Fixed
Motor temperature or motor current, depending on
choice of over-load method, has exceeded the over-
load setting for the time specified by the over-load
timeout parameter.
SOP
If motor voltage exceeds 90% of the motor over‐
voltage limit in the motor limit menu.
SOP
The measured motor voltage exceeds the threshold
set by the motor trip volts (1160) parameter in the
limits menu (1120). An improperly set-up or tuned
drive usually causes this fault. This could include
the secondary tap setting. A high line condition can
also cause this.
Fixed
Drive instantaneous over-current (IOC) faults usu‐
ally result when the signal from test point IOC on
the system interface board exceeds the level set by
the drive IOC setpoint (7110) parameter in the input
protect menu (7000).
SOP
The torque producing current of the drive has drop‐
ped below a preset value set by the user.
Menu
This fault usually indicates a loss of load condition
when the torque producing current of the drive has
dropped below a preset value set by the user for
the specified amount of time.
Fixed
The software has detected an imbalance in the mo‐
tor currents.
SOP
The software has detected an open phase condition
at the drive output to the motor. Generally, if this
occurs, the problem is with the feedback. A true
open output phase will result in an IOC trip.
SOP
This alarm is issued when the drive is in speed roll‐
back, due to a torque limit condition, for more than
one minute.
SOP
This fault or alarm, depending on the SOP program,
is issued when the drive is in speed rollback, due
to a torque limit condition, for more than 30 minutes.
SOP
Motor speed is below the zero speed setting (2200).
This is either due to a motor stall condition, if speed
demand is higher than the zero speed setting, or a
low speed demand condition, where speed demand
is lower than the zero speed setting.
SOP
This occurs only with synchronous motor control
due to field exciter failure or loss of power to the
exciter.
8.2 Major Drive Faults and Alarms
Operation
129

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GH180 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

6sr41

Table of Contents

Save PDF