FDS300 Flame Detector FDS300 Safety and Technical Manual Ref: 2401.6000 Rev: 2.3 ECN: 4436 Safety Instructions For the correct and effective use of this equipment, to maintain safety and avoid hazards it is essential that you read and understand these instructions fully, act accordingly BEFORE installing, operating or maintaining the equipment.
Page 7
The FS301 flame simulator can be used to verify correct detector positioning and coverage. • The FDS300 has one sensitivity setting, this is factory set, and no changes can be made to set-up except by fully trained Micropack engineers. •...
FDS300 Flame Detector FDS300 Safety and Technical Manual Ref: 2401.6000 Rev: 2.3 ECN: 4436 Mounting & Orientation The mounting bracket allows the detector’s vertical orientation to be adjusted from 0 to 45°, and allows a horizontal rotation of +/-45°. Figure 1: Detector Mounting Bracket & Orientation...
FDS300 Flame Detector FDS300 Safety and Technical Manual Ref: 2401.6000 Rev: 2.3 ECN: 4436 Wiring Procedure The wiring terminals are located in the rear section of the detector enclosure and are accessible by removal of the end cap. The front section of the enclosure should only be accessed by trained personnel.
FDS300 Flame Detector FDS300 Safety and Technical Manual Ref: 2401.6000 Rev: 2.3 ECN: 4436 3.32 Relay Output The following wiring connection diagrams shows wiring the detector when a relay output is required. Figure 6: 2 Pair Termination NOTE: EOL and Alarm resistors values are defined by the client and the control system/fire panel which the detectors are being integrated into micropack.co.uk...
The supporting structure must allow for horizontal adjustment of the detector orientation. The support structure should be in place prior to detector installation. Information on mounting is available from Micropack (Engineering) Limited. The threaded flame path of the enclosure cover and body must be protected from damage during installation.
FDS300 Flame Detector FDS300 Safety and Technical Manual Ref: 2401.6000 Rev: 2.3 ECN: 4436 Application Guidelines In considering the application of the detector it is important to know of any conditions that may prevent the detector from responding. The detector provides reliable response to visible flames within its field of view, and insensitivity to common false alarm sources.
The detector sensitivity to different fuel sources is dependent on the apparent size of the flame, the detectors typical response is shown below (see table 4). Table 4: Typical FDS300 Response Characteristics Fuel Fire Size...
Page 21
FDS300 Flame Detector FDS300 Safety and Technical Manual Ref: 2401.6000 Rev: 2.3 ECN: 4436 Step Periodic Inspection and Maintenance Suggested Interval General Inspection and maintenance of the detector and faceplate 6 monthly 6-14 Specific inspection and maintenance of the detector enclosure...
If any fault is suspected within the electronics module the module is to be returned to Micropack for investigation and repair if required. Any faults should be reported to Micropack as per the instruction in section 6.2.
FDS300 Flame Detector FDS300 Safety and Technical Manual Ref: 2401.6000 Rev: 2.3 ECN: 4436 Power Fault If the detector LED indicator is OFF then there may be a power supply fault, as shown below: Figure 10: Power Supply Diagnostic Chart...
FDS300 Flame Detector FDS300 Safety and Technical Manual Ref: 2401.6000 Rev: 2.3 ECN: 4436 Appendix B - Help us to help you From: QA Department Micropack (Engineering) Limited Fire Training Centre Schoolhill, Portlethen AB12 4RR Tel: +44 (0) 1224 784055...