Installation and maintenance 4342 en - 2010.03 / d R 450 M & T A.V.R. This manual concerns the alternator AVR which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. By following certain important points during installation, use and servicing of your AVR, you can look forward to many years of trouble-free operation.
LEROY-SOMER Installation and maintenance 4342 en - 2012.03 / d R 450 M & T A.V.R. CONTENTS 1 - GENERAL INFORMATION ....................4 1.1 - Description ........................4 1.2 - Identification ......................... 4 1.3 - Tools ..........................4 2 - POWER SUPPLY ....................... 5 2.1 - AREP excitation system ....................5...
LEROY-SOMER Installation and maintenance 4342 en - 2010.03 / d R 450 M & T A.V.R. 1 - GENERAL INFORMATION - R 450M: single-phase sensing, 1.1 - Description - R 450T: three-phase sensing, The R450 AVR is supplied in a casing...
LEROY-SOMER Installation and maintenance 4342 en - 2012.03 / d R 450 M & T A.V.R. 2 - POWER SUPPLY to the alternator main voltage (Shunt characteristic), the second one has a Both the AREP & PMG excitation systems voltage proportional to the stator current are controlled by the AVR.
LEROY-SOMER Installation and maintenance 4342 en - 2010.03 / d R 450 M & T A.V.R. 2.2 - PMG excitation system The AVR monitors the alternator output voltage by adjusting the excitation current. With PMG excitation, a permanent magnet The rotating switch should be in the PMG generator (PMG) added to the alternator position (see 3.2.3).
LEROY-SOMER Installation and maintenance 4342 en - 2012.03 / d R 450 M & T A.V.R. 2.3 - SHUNT or separate excitation system With SHUNT excitation, the AVR is powered by the main winding (100V to 140V - 50/60 Hz ) by using X1, X2 on the AVR.
LEROY-SOMER Installation and maintenance 4342 en - 2010.03 / d R 450 M & T A.V.R. 3 - TECHNICAL CHARACTERISTICS 3.2.1.2 - Quadrature droop: Quadrature droop adjustment 3.1 - Electrical characteristics potentiometer P4 within a range : - maximum power supply: 150V - 50/60 Hz - from 0 to 8% with a PF=0.8 for 400V...
Page 9
LEROY-SOMER Installation and maintenance 4342 en - 2012.03 / d R 450 M & T A.V.R. current. In all operating conditions the WARNING maximum excitation current is clamped to 9.5 A ± 0.5 A. Overrun indications: limitation threshold must adjustable between 1 and 5.5 A. The...
Page 10
LEROY-SOMER Installation and maintenance 4342 en - 2010.03 / d R 450 M & T A.V.R. I exc(A) Diagram 2 2.9x I (Maximum current I exc) threshold (max. 9.5 A) threshold (1...5.5A) t(s) Shutdown Activation of 90 s. tempo elapsed : application 0.5 ~ 0.7...
Page 11
LEROY-SOMER Installation and maintenance 4342 en - 2012.03 / d R 450 M & T A.V.R. 3.2.2 - Rotating switch selection: LAM 3.2.3 Rotating switch: excitation type and U/F and time response 50Hz EXT.FREQ. SHUNT/AREP SET. MODE 1 RAPIDE NORMAL...
LEROY-SOMER Installation and maintenance 4342 en - 2010.03 / d R 450 M & T A.V.R. 3.3 - U/F and LAM function 3.3.2.2 - Soft voltage recovery function During load impacts, the function helps the 3.3.1 - Frequency variation compared...
LEROY-SOMER Installation and maintenance 4342 en - 2012.03 / d R 450 M & T A.V.R. 3.4.3 - Power - R729 module: same as R726 with additional functions. • Detection of a diode fault. • 4-20 mA input. • Possibility of kVAR regulation.
LEROY-SOMER Installation and maintenance 4342 en - 2010.03 / d R 450 M & T A.V.R. 4 - INSTALLATION - COMMISSIONING Action Factory setting Pot. 4.1 - Electrical checks on the AVR Voltage minimum fully 400 V - 50 Hz...
Page 15
LEROY-SOMER Installation and maintenance 4342 en - 2012.03 / d R 450 M & T A.V.R. i) Vary the frequency (speed) around 48 or However, for applications requiring an 58 Hz according to the operating frequency, overload protection (see 3.2.1.4), the...
Page 16
LEROY-SOMER Installation and maintenance 4342 en - 2010.03 / d R 450 M & T A.V.R. The exciter is switched off by disconnecting the AVR power supply (1 wire on each auxiliary winding) - contact rating 16 A - 250 V A.C.
LEROY-SOMER Installation and maintenance 4342 en - 2012.03 / d R 450 M & T A.V.R. 4.3 - Electrical faults Fault Action Measurements Check/Cause The alternator builds up and its - Lack of residual magnetism voltage is still correct when the...
LEROY-SOMER Installation and maintenance 4342 en - 2010.03 / d R 450 M & T A.V.R. 5 - SPARE PARTS 5.1 - Designation Description Type Code Voltage regulator R 450 M AEM 110 RE 032 (AVR) Voltage regulator R 450 T...