Samsung AC***MXSCCC Installation Manual

Samsung AC***MXSCCC Installation Manual

Outdoor/indoor units

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Samsung AC***MXSCCC

  • Page 2: Air Conditioner

    MXSCCC Air Conditioner installation manual imagine the possibilities Thank you for purchasing this Samsung product. ES FR DB68-07241A-00...
  • Page 3: Table Of Contents

    Contents PREPARATION Safety precautions ......................3 Preparation for outdoor unit installation.
  • Page 4: Safety Precautions

    In order to prevent electric shocks, fires or injuries, always stop the unit, disable the protection switch and contact SAMSUNG’s technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy.
  • Page 5 Safety precautions Installing the unit IMPORTANT: When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines. Always disassemble the electric lines before the refrigerant tubes. Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the authorized technician has collected the material from the retailer.) After completing the installation, always carry out a functional test and provide the instructions on how to operate the air...
  • Page 6: Preparation For Outdoor Unit Installation

    Preparation for outdoor unit installation The air conditioner uses R-410A refrigerant. A Type: AC018MXSCCC Cooling Only (Unit : inch) 25.98 0.91 0.47 12.20 2.13 34.65 B Type: AC024MXSCCC Cooling Only (Unit : inch) 25.98 0.47 0.71 12.20 2.09 34.65 Moving the Outdoor Unit by Wire Rope Fasten the outdoor unit by two 26.2 ft or longer wire ropes as shown at the figure.
  • Page 7: Deciding On Where To Install The Outdoor Unit

    Air Guide Duct (This product is not Stereo provided by Samsung) 8 inch If the outdoor unit is installed at a height, ensure that its base is firmly fixed in position. Make sure that the water dripping from the drain hose runs away correctly and safely.
  • Page 8 - Install the outdoor unit in a place (such as near buildings etc.) where it can be prevented from sea breeze which can damage the outdoor unit. Outdoor unit Outdoor unit Sea breeze Sea breeze - If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around to block the sea breeze.
  • Page 9 Deciding on where to install the outdoor unit Space Requirements for Outdoor Unit When installing 1 outdoor unit (Unit : inch) ❋ When the air outlet is opposite the wall ❋ When the air outlet is towards the wall 78.74 or more 5.91 or more 23.62 or more ❋...
  • Page 10 When installing 1 outdoor unit (with wind baffle) (Unit : inch) ❋ When the air outlet is opposite the wall ❋ When the air outlet is towards the wall 78.74 or more 5.91 or more 23.62 or more ❋ When 3 sides of the outdoor unit are blocked by the wall ❋ The upper part of the outdoor unit and the air outlet is towards the wall 11.81 or more ❋...
  • Page 11 Deciding on where to install the outdoor unit 11.81 or more 23.62 or more 23.62 or more 23.62 or more 11.81 or more ❋ When 3 sides of the outdoor unit are blocked by the wall 11.81 or more 23.62 or more 23.62 or more ❋...
  • Page 12 11.81 or more 23.62 or more 23.62 or more 23.62 or more 11.81 or more ❋ When 3 sides of the outdoor unit are blocked by the wall 11.81 or more 23.62 or more 23.62 or more ❋ When front and rear side of the outdoor unit is towards the wall ❋...
  • Page 13: Outdoor Unit Installation

    Outdoor unit installation The outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration, particularly if the outdoor unit is to be installed in a location exposed to strong winds or at a height, the unit must be fixed to an appropriate support(wall or ground).
  • Page 14: Connecting The Cable

    Connecting the cable Two electronic cables must be connected to the outdoor unit. The connection cord between indoor unit and outdoor unit. The power cable between outdoor unit and auxiliary circuit breaker. Be sure to run the power supply cable and the communication cable through electrical conduit as seen in the picture.
  • Page 15 Connecting the cable 1. RLA is based on AHRI 210/240 colling standard condition [Indoor temp. : 26.7 °C / 80 °F(DB) / 19.46 °C / 67 °F(WB), Outdoor temp. : 35 °C / 95 °F(DB)] NOTE 2. Voltage tolerance is ± 10 %. 3.
  • Page 16 Wiring Diagram of Power Cable When using ELB for 1 phase Power Supply 1(L) 2(N) Electrical component box MCCB Cable tie MCCB Indoor Cable clamp Power Main power cable Communication cable Indoor Unit ❋ The appearance of the unit may be different from the picture depending on the model. You should connect the power cable into the power cable terminal and fasten it with a clamp.
  • Page 17 Connecting the cable Wiring Diagram of Connection Cord 1 phase Indoor Unit L1 L2 L1 L2 1(L) 2(N) Cable Indoor Power Main power cable Communication cable Cable clamp outdoor unit Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely.
  • Page 18: Connecting The Power Terminal

    Connecting the Power Terminal Connect the cables to the terminal board using the compressed ring terminal. Cover a solderless ring terminal and a connector part of the power cable and then connect it. Silver solder Nominal Nominal dimensions dimensions Standard Standard Standard Min.
  • Page 19: Connecting The Refrigerant Pipe

    Connecting the refrigerant pipe Refrigerant piping system Pipe length or height Refrigerant piping system table AC018MXSCCC AC024MXSCCC Max. allowable length Actual pipe length L0 + H + L1 98.4 ft (30 m) or less 164.0 ft (50 m) or less Allowable height length Actual pipe length 65.6 ft (20 m) or less...
  • Page 20: Adding Refrigerant (R-410A)

    Adding refrigerant (R-410A) The outdoor unit is loaded with sufficient refrigerant for the standard piping. Thus, refrigerant must be added if the piping is lengthened. This operation can only be performed by a qualified refrigeration specialist. For quantity of adding refrigerant, refer to page 19.
  • Page 21: Connecting Up And Removing Air In The Circuit

    Connecting up and removing air in the circuit When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor CAUTION works with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high.
  • Page 22 5. Purge the air from the system using vacuum pump for about 10 minutes. Close the valve of the low pressure side of manifold gauge clockwise. Make sure that pressure gauge shows -0.1 MPa(-76cmHg) after about 10 minutes. This procedure is very important to avoid a gas leak. Turn off the vacuum pump.
  • Page 23: Cutting/Flaring The Pipes

    Cutting/Flaring the pipes 1. Make sure that you have the required tools available. (pipe cutter, reamer, flaring tool and pipe holder) 2. If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle with the side of the pipe.
  • Page 24: Performing Leak Tests

    Performing leak tests LEAK TEST WITH NITROGEN (before opening valves) In order to detect basic refrigerant leaks, before recreating the vacuum and A(Gas) recirculating the R-410A, it’s responsible of installer to pressurize the whole system with nitrogen (using a cylinder with pressure reducer) at a pressure above 40 bar (gauge).
  • Page 25: Insulation

    Insulation Once you have checked that there are no leaks in the system, you can insulate the piping and hose. 1. To avoid condensation problems, place an insulator around each refrigerant pipe. When insulate the pipe, be sure to overlap the insulation. The insulation has to be produced in full compliance of European NOTE regulation reg.
  • Page 26: Using Stop Valve

    Using stop valve To Open the Stop Valve 1. Open the cap and turn the stop valve counterclockwise by using a hexagonal wrench. 2. Turn it until the axis is stopped. Do not apply excessive force to the stop valve and always use special instruments. Otherwise, the stopping box can be damaged and the back sheet can leaks.
  • Page 27: Interface Module Installation (Optional)

    Interface module Installation (Optional) Accessories (Interface module : MIM-B14) Interface module Interface module Interface module Installation Manual Case Cable-tie power cable communication cable 1. Fix the case at with bolts on the side of the control box in the outdoor unit. (See the picture) 2.
  • Page 28: Checking Correct Grounding

    Checking correct grounding If the power distribution circuit does not have a grounding or the grounding does not comply with specifications, an grounding electrode must be installed. The corresponding accessories are not supplied with the air conditioner. 1. Select an grounding electrode that complies with the specifications given in the illustration.
  • Page 29: Testing Operations

    Testing operations 1. Check the power supply between the outdoor unit and the auxiliary circuit breaker. 1 phase power supply : L1, L2 2. Check the indoor unit. 1) Check that you have connected the power and communication cables correctly. (If the power cable and communication cables one mixed up or connected incorrectly, the PCB will be damaged.) 2) Check the thermistor sensor, drain pump/hose, and display are connected correctly.
  • Page 30 Short Display contents SEG1 SEG2 SEG3 SEG4 Unit push Protective control Frequency status 0: Normal 0: No Protective control 1: Hold 1: Freezing 0: Cooling 2: Down Protective control 2: Non-stop defrosting 1: Heating 3: Up_limit 3: Over-load 4: Down_limit 4: Discharge 5: Total electric current The temperature of heat radiating...
  • Page 31: Installing The Wind Baffle

    Installing the wind baffle If you operate the cooling operation of air conditioner in the condition where ambient temperature is lower than 23 °F DB(Dry bulb), or the outdoor unit might be faced with strong wind directly, the wind baffle should be installed to prevent the outdoor unit fan from operating in reverse way.
  • Page 32: Troubleshooting

    Troubleshooting The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorized Service Center. Outdoor unit If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB. Priority Error number Explanation...
  • Page 33 Troubleshooting Priority Error number Explanation E500 IPM over heat error on inverter 1 E484 PFC Overload (Over current) Error E466 DC-Link voltage under/over error E403 Compressor down due to freeze protection control E440 Heating operation restricted at outdoor temperature over Theat_high value (default: 30 °C) E441 Cooling operation restricted at outdoor temperature below Tcool_low value (default: 0 °C) E556...
  • Page 34: Extending The Power Cable

    Extending the power cable 1. Prepare the following tools. Tools Crimping pliers Connection sleeve Insulation tape Contraction tube 20xØ0.26 inch(6.5 mm) 70xØ0.31 inch(8.0 mm) Spec MH-14 Width 0.75 inch(19 mm) (HxOD) (LxOD) Shape 2. As shown in the figure, peel off the shields from the rubber and wire of the Power cable power cable.
  • Page 35 Extending the power cable 5. Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape. Three or more layers of insulation are required. Method 1 Method 2 Insulation tape Insulation tape 1.57 inch 1.38 inch...
  • Page 36 Memo English-35...

Table of Contents