Product operation and reliability depend upon proper installation. DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex product supplier.
4007ES operator instructions are described in the 4007ES Operator’s Manual 579-1165. 4007ES programming instructions are described in the 4007ES Programmer’s manual 579-1167. 2.1 4007ES product list Table 1: Product list Part number Base panels 4007-9101 4007ES Hybrid, red 4007-9201 4007ES, red 4007-9102 4007ES Hybrid, platinum...
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 2.2 Glossary Table 3: Glossary Term Definition Abbreviation for Auxiliary; typically used to describe Auxiliary Power. End-of-Line, typically in reference to and end-of-line resistor or EOL resistor. FACP Fire Alarm Control Panel. In this document, “Hybrid”...
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 3 Installation Introduction This chapter describes how to install the 4007ES panel. It can be semi-flush or surface mount. 3.1 Mounting the 4007ES panels • Due to the danger of metal fragments falling into electronics when drilling the holes for the conduits, remove the electronics in the system: - To remove the electronics, unscrew the ten screws.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Fig 3: Back Box Installation dimensions and Semi-Flush Mounting (Right) 3.2 Trim Kit 3.2.1 Trim kit application Trim kits are used to cosmetically cover wall openings when boxes are mounted semi-flush into the wall. The kit includes: •...
3.3 Wiring Wiring guidelines Follow these guidelines when connecting power-limited (PL) systems. For more information about these guidelines, contact your authorized Simplex product supplier. • Non-power limited (NPL) field wiring (AC power, batteries, City connection, DACT) must be installed and routed in the shaded areas shown in Figure 6: Field wiring guidelines (NAC power supply shown as reference) on page 8 •...
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Fig 7: EOL relay diagram • In areas of high lightning activity, or in areas that have large power surges, use the 2081- 9027 or the 2081-9044 Transient Suppressor on monitor points.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 3.3.3 Battery guidelines A fused harness is required to connect the backup batteries. Use harness 734-304 for a NAC power supply, and harness 734-303 for an IDNAC power supply. The harness is shipped with the panel. The mating spade lug on the battery should be 0.250 in. X 0.032 in. (6.35 mm X 0.81 mm). If another size is needed, you need to replace the battery terminal connectors on the supplied battery harness.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 4 NAC power supply A conventional reverse polarity NAC power supply is used in a 4007ES hybrid panel. It provides 6A and can support the following: • Non-addressable notification devices. • Addressable initiating devices. See Figure 10: NAC power supply on page 11 and Table on page 11 for the main components of the NAC power supply.
The NAC power supply allows connection to up to four Class A NAC circuits. Notification appliances within the 4007ES system are synchronized including any attached 4009 series NAC extenders. Do not mix Wheelock and Simplex branded devices in the same system, they will not be synchronized.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 4.3 Specifications Table 6: Specifications Maximum appliances 70 per circuit.* * Each 49CMT series appliance counts as 5 regular appliances for the maximum 70 appliances that can be supported per NAC. As the earth fault sensitivity with thirteen MT appliances drops from 10 K to 9.6K ohms, no more than thirteen 49CMT series appliances may be placed on one circuit.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 4.3.2 Wiring distances Table on page 14 lists the maximum distances from the NAC terminal block to the last appliance in a Class A configuration, depending on wire gauge and current. Use Table on page 14 to calculate the wire distances for your application if you are using Class A wiring. Table on page 14 gives the values for a Class B configuration.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Fig 12: Class A NAC wiring 3. Route the wire from the last appliance to the A+ and A- inputs on the same NAC circuit of the power supply. 4. Repeat steps 1 through 3 for each NAC output you want to use. 5.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 4.4 Troubleshooting Figure 14: LEDs on the 4007ES hybrid power supply on page 16 and Table on page 16 show the LED definition for the NAC power. Fig 14: LEDs on the 4007ES hybrid power supply Table 11: LEDs on the 4007ES hybrid power supply LED10 Green.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5 IDNAC power supply An IDNAC power supply is used in the 4007ES panel, the non-hybrid panel. It provides 4 A and can support the following: • Addressable notification devices. • Addressable initiating devices. See Figure 15: IDNAC power supply on page 17 and Table on page 17 for the main components of the IDNAC power supply.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.1 Power supply specifications The IDNAC Power Supply can supply 4A of 24V power in addition to the base draw of the CPU/power supply cards. The current draw taken from optional cards, IDNet Devices, Aux Power, and NACs must be subtracted from 4A. Table 13: 4007ES system current draw 2 A at 120 VAC, 50/60 Hz Maximum AC input...
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.3 Specifications Table 14: IDNAC specifications • Up to 12 4905-9929 remote TrueAlert Addressable Isolators per IDNAC Circuit. • Up to 30 devices connected directly to any isolator terminal pair*. Supports •...
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.5 IDNAC Class B wiring tables Use the following tables to calculate the wiring distance to farthest appliance. The maximum wiring distance is the shorter of the distance limits as calculated by alarm current voltage drop or by reaching the communications distance limit. Wiring Limit Based on Alarm Current Wiring Limit Based on Communication Distance to the Last Appliance...
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.6 IDNAC Class B wiring To connect the power supply to appliances using Class B wiring: 1. Route the wire from the + and the - outputs on the IDNAC terminal block (TB2) to the appropriate inputs on a peripheral notification appliance. 2.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.7 Compatible devices and appliances The devices and appliances listed in Table on page 22 are compatible with the IDNAC power supply. Notification devices are synchronized within the 4007ES system, including any attached 4009 series NAC extenders. Table 16: Compatible devices and appliances Addressable device description Model numbers...
Page 25
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Table 17: Compatible devices and appliances Addressable device appliance TrueAlert appliance model TrueAlert ES appliance model numbers description numbers 49VO-WRF 49VO-WWF 49VO-WWS-BA 49VO-WRA-A 49VO-WWF-BA 49VO-WRA-A-BA 49VO-WWA-BA 49VO-WWA-A 49VO-WWA-A-BA 49VO-WRA-BA 49VO-WWS-A-BA 49VO-WRF-BA 49VO-WRS 4906-9201 49VO-WRQ-BA...
Page 26
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Table 17: Compatible devices and appliances Addressable device appliance TrueAlert appliance model TrueAlert ES appliance model numbers description numbers 59AV-WRF 59AV-WRF-BA 59AV-WWFAB 59AV-WWF 59AV-WWFAB-BA LED audible/visible (A/V) wall mount 59AV-WWF-BA 59AV-APPLWR 59AV-WRFAB 59AV-APPLWW 59AV-WRFAB-BA...
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.8 Auxiliary relays section overview Table 18: Electrical specifications for Auxiliary relays Electrical specifications: Relay circuit rated to switch: 2 A at 30 VAC or 30 VDC, resistive load. Relay contacts are Form C dry contacts. Transorbs provide suppression to earth. Do not switch voltages Contacts: greater than rating, or damage may result.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.9 Troubleshooting The code produced by the illuminated yellow indicator LEDs corresponds to a trouble that is either occurring on the system, or on the SLC channels. See Table on page 26 for the 4007ES LED definitions, and see Figure 21: SLC channel trouble LED codes on page 27 for the 4007ES LEDs and their codes.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.9.1 SLC channel trouble LED codes SLC channel troubles are indicated by LEDs A to D, as well as IDNAC. See Figure 21: SLC channel trouble LED codes on page 27 for the description of the LEDs.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 5.9.2 System trouble LED codes System troubles are indicated by LEDs A to D. Fig 22: System trouble LED codes Page 28 579-1102 Rev H...
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 6 4007ES power supplies This chapter describes the common sections of both the 4007ES Hybrid NAC power supply and the 4007ES IDNAC power supply. 6.1 Power supplies specifications Table 21: Operating conditions Operating conditions: Operating temperature range 32 °F - 120 °F (0 °C - 49 °C).
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 6.3 IDNet Section overview The power supply provides an isolated IDNet channel. This section is compatible with IDNet communicating initiating devices and enables the system CPU to communicate with up to 250 peripheral devices, such as smoke detectors and pull stations. Fig 23: IDNET on the power supply Specifications...
6.5 Wiring parameters Table on page 31 identifies the IDNet wiring parameters that you must consider when installing this card. For additional wiring information, see Simplex Addressable Fire Alarm Panels Field Wiring Specifications (900-408). Table 23: IDNet wiring parameters IDNet wiring capacitance parameters...
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 6.6 Class A Wiring To wire an IDNet section as a Class A circuit: 1. Make sure the jumpers on P2 are set to positions 3-5 and 4-6. 2. Route the wiring from the IDNet circuit primary terminals (B+, B-) on TB1 of the IDNet to the corresponding inputs on the first device. 3.
2. The conductors must test free of all grounds and stray voltages before connection to appliances and panel. 3. Terminate Class B NACs, as shown, using a 733- 894 EOL. For Canadian applications, mount end-of-line resistor to a Simplex-US Model 431537 EOL plate in accordance with ULC-S527.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Table 25: Simple NAC wiring limits Alarm current 20 AWG 18 AWG 16AWG 14 AWG 12 AWG Line resistance (Ohms) 2.00 77 ft 123 ft 195 ft 310 ft 493 ft 1.75 Note: This chart indicates the maximum distance for 1/4 -2A loads.
Page 37
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual Fig 30: RUI wiring to the host panel Page 35 579-1102 Rev H...
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 6.10Troubleshooting The code produced by the illuminated indicator LEDs corresponds to a trouble occurring on the system. See Table on page 36 for the IDNet LED definitions, and see Table on page 36 for the 4007ES trouble messages. Table 28: LEDs on the 4007ES power supplies Normally off.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 7 Optional modules and cards The 4007ES can be ordered with a variety of optional cards and modules, depending on the system requirements. 8 Point Zone/ Relay Card The 8-point Zone/relay Card (4007-9801) mounts in the 4007ES panel. Up to four cards can be added. Each card monitors up to eight Class B or four Class A zones, or eight relay contacts.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 2. Use the provided hardware to secure the RS-232 bracket to the 4007ES box. 3. Connect the free end of harness 734-308 to connector J17 (Zone/Relay) on the IDNAC PSU. See the Dual RS-232 Interface Module installation instructions (579-910) for more information about installing the module. 7.1 Example of combinations Figure 32: Example 1 on page 38 , Figure 33: Example 2 on page 38, and Figure 34: Example 3 on page 38 are examples of some of the combinations that can be made in a 4007ES using the available optional cards and modules.
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual 8 Appendix A ULC programming requirements 8.1 Common earth fault ground and common trouble indicator This application monitors a system pseudo that counts the number of ground faults or troubles that occur on the system. Each time this counter increments, such as when a ground fault or trouble occurs, a yellow LED on the operator interface panel illuminates.
Page 42
Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.