2.4 SPECIFICATIONS
BREAKER FLASHOVER
Operating quantity:
Pickup level voltage:
Dropout level voltage:
Pickup level current:
Dropout level current:
2
Level accuracy:
Pickup delay:
Timer accuracy:
Operate time:
BREAKER RESTRIKE
Principle:
Availability:
Pickup level:
Reset delay:
INCIPIENT CABLE FAULT DETECTION
Principle:
Availability:
Pickup level:
Reset delay:
Operating mode:
SYNCHROCHECK
Max voltage difference: 0 to 400000 V in steps of 1
Max angle difference:
Max freq. difference:
Hysteresis for max. freq. diff.: 0.00 to 0.10 Hz in steps of 0.01
Dead source function:
FLEXLOGIC
Programming language: Reverse Polish Notation with graphical
Lines of code:
Internal variables:
Supported operations:
Inputs:
Number of timers:
Pickup delay:
Dropout delay:
2-22
phase current, voltage and voltage differ-
ence
0 to 1.500 pu in steps of 0.001
97 to 98% of pickup
0 to 1.500 pu in steps of 0.001
97 to 98% of pickup
±0.5% or ±0.1% of rated, whichever is
greater
0 to 65.535 s in steps of 0.001
±3% of operate time or ±42 ms, which-
ever is greater
<42 ms at 1.10 × pickup at 60 Hz
detection of high-frequency overcurrent
condition ¼ cycle after breaker opens
one per CT/VT module (not including 8Z
modules)
0.1 to 2.00 pu in steps of 0.01
0.000 to 65.535 s in steps of 0.001
detection of ½ cycle or less overcurrent
condition during normal load
two per CT/VT module (not including 8Z
modules)
0.1 to 10.00 pu in steps of 0.01
0.000 to 65.535 s in steps of 0.001
number of counts, counts per time win-
dow
°
0 to 100
in steps of 1
0.00 to 2.00 Hz in steps of 0.01
None, LV1 & DV2, DV1 & LV2, DV1 or
DV2, DV1 xor DV2, DV1 & DV2
(L = Live, D = Dead)
visualization (keypad programmable)
512
64
NOT, XOR, OR (2 to 16 inputs), AND (2
to 16 inputs), NOR (2 to 16 inputs),
NAND (2 to 16 inputs), latch (reset-domi-
nant), edge detectors, timers
any logical variable, contact, or virtual
input
32
0 to 60000 (ms, sec., min.) in steps of 1
0 to 60000 (ms, sec., min.) in steps of 1
F60 Feeder Protection System
2 PRODUCT DESCRIPTION
AUTORECLOSURE
Single breaker applications, 3-pole tripping schemes
Up to 4 reclose attempts before lockout
Independent dead time setting before each shot
Possibility of changing protection settings after each shot with
FlexLogic
LOAD ENCROACHMENT
Responds to:
Positive-sequence quantities
Minimum voltage:
0.000 to 3.000 pu in steps of 0.001
Reach (sec. Ω):
0.02 to 250.00 Ω in steps of 0.01
Impedance accuracy:
±5%
Angle:
5 to 50° in steps of 1
Angle accuracy:
±2°
Pickup delay:
0 to 65.535 s in steps of 0.001
Reset delay:
0 to 65.535 s in steps of 0.001
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Operate time:
<30 ms at 60 Hz
THERMAL OVERLOAD PROTECTION
Thermal overload curves: IEC 255-8 curve
Base current:
0.20 to 3.00 pu in steps of 0.01
Overload (k) factor:
1.00 to 1.20 pu in steps of 0.05
Trip time constant:
0 to 1000 min. in steps of 1
Reset time constant:
0 to 1000 min. in steps of 1
Minimum reset time:
0 to 1000 min. in steps of 1
Timer accuracy (cold curve): ±100 ms or 2%, whichever is greater
Timer accuracy (hot curve): ±500 ms or 2%, whichever is greater
for I
< 0.9 × k × I
p
TRIP BUS (TRIP WITHOUT FLEXLOGIC)
Number of elements:
6
Number of inputs:
16
Operate time:
<2 ms at 60 Hz
Timer accuracy:
±3% or 10 ms, whichever is greater

2.4.2 USER-PROGRAMMABLE ELEMENTS

FLEXCURVES™
Number:
4 (A through D)
Reset points:
40 (0 through 1 of pickup)
Operate points:
80 (1 through 20 of pickup)
Time delay:
0 to 65535 ms in steps of 1
FLEX STATES
Number:
up to 256 logical variables grouped
under 16 Modbus addresses
Programmability:
any logical variable, contact, or virtual
input
and I / (k × I
) > 1.1
b
b
GE Multilin