6-4. STANDARD OPERATION DATA
Heat pump type(1)
Service Ref.
Mode
Capacity
Input
Indoor unit Service Ref.
Phase , Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase , Hz
Volts
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
SHF
BF
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is :
PLA-RP1.6AA.UK
Cooling
3,600
W
1.07
kW
PLA-RP1.6AA.UK
1 , 50
V
A
0.79
PUHZ-RP1.6VHA
1 , 50
V
4.01
A
2.70
MPa
1.01
MPa
°C
70
°C
46
°C
15
5
m
°C
D.B.
27
°C
W.B.
19
°C
D.B.
15.6
°C
D.B.
35
°C
W.B.
24
0.89
0.11
f )
1(MPa)=10.2(kgf/f
PLA-RP2AA.UK
Heating
Cooling
4,100
5,000
1.12
1.55
PLA-RP2AA.UK
1 , 50
230
PUHZ-RP2VHA
1 , 50
230
4.23
6.16
2.69
2.91
0.74
0.99
71
73
41
49
2
11
5
5
20
27
15
19
35.5
15.4
7
35
6
24
—
0.86
—
0.14
52
PLA-RP2.5AA.UK
Heating
Cooling
6,000
6,000
1.62
1.65
PLA-RP2.5AA.UK
1 , 50
230
0.79
PUHZ-RP2.5VHA
PUHZ-RP2.5VHA
1 , 50
230
6.61
6.47
2.60
2.76
0.67
0.99
65
77
44
44
12
-1
5
5
20
27
19
15
37.8
14.3
35
7
24
6
—
0.78
0.14
—
Heating
7,000
1.85
230
0.79
1
230
7.50
2.63
0.70
81
44
8
5
20
15
40.9
7
6
—
—