Download Print this page

Interface Description - Huawei R4815N1 User Manual

Rectifier

Advertisement

R4815N1 Rectifier User Manual V1.2

Interface Description

The rear panel of the rectifier provides an golden finger
connection which is used as AC input, DC output and
signal connection.For the location of the pins, see
Figure 3. For the definitions of the pins, see Table 1.
Figure 4 Pins on the rear panel
Table 1 Definitions of the pins on the rear panel
Pin
Definition
1, 9
L
2, 10
N
3, 11
PE
4
CANL
13
ACD1
5
ACD2
12
CANH
6, 14
OUTPUT+
8
OUTPUT-
7
Pre-charge
CAUTION
Only trained and qualified personnel can be allowed to
install or service the rectifier.
Each rectifier input is protected by two fuses, one for the
live wire and the other for the neutral wire.
Function
Live line
Neutral line
Protect earth
CANL
Slot detection signal 1
Slot detection signal 2
CANH
Output:48V+
Output:48V-
Pre-charge
CAUTION
This product should be used in the environment that meets
specifications described in the user manual.
If the product is used with abnormal power grid input or
exposed to salt mist, dust, or mist, the product may become
faulty, and the resulting product exceptions or component
damage are beyond the warranty scope.
Removing the Rectifier
Figure 5 Removing a PSU
Step 1: Push the locking latch left.
Step 2: Remove the PSU out of the PDU by
externally drawing the handle, as shown
in Figure 5.
Installing the Rectifier
Figure 6 Installing a PSU
Step 1: Push the locking latch left and pull out the
handle.
Step 2: Push the PSU slowly into the subrack
along the guide rail and push the locking
latch right to fix the handle, as shown in
Figure 6.
Transport
The product must be packed with firmly packing
box when transport. Out of the box the mark
"prevent moisture", "lay down carefully" and other
required mark must have. Any transport tools are
permitted if the product in the packing box. When
transport must avoid rain and snow attack directly
and mechanical shock.
Storage
Product should be packaged in the packing box
before use. The store room should be meet:
-40º C to +70º C ambient temperature, related
humidity less than 80%, dry, ventilation and hasn't
any corrosive gas.
3