Negative Pressure; Draft; Chimney And Exhaust Connection - Quadra-Fire MT VERNON E2-C Installation Manual

Mt. vernon e2 pellet appliance
Table of Contents

Advertisement

C. Negative Pressure
WARNING
Risk of Asphyxiation!
Negative pressure can cause spillage of combustion
fumes and soot.
Negative pressure results from the imbalance of air avail-
able for the appliance to operate properly. It can be strongest
in lower levels of the house.
Causes include:
Exhaust fans (kitchen, bath, etc.)
Range hoods
Combustion air requirements for furnaces, water
appliances and other combustion appliances
Clothes dryers
Location of return-air vents to furnace or air conditioning
Imbalances of the HVAC air handling system
Upper level air leaks such as:
- Recessed lighting
- Attic hatch
- Duct leaks
To minimize the effects of negative air pressure:
Install the outside air kit with the intake facing prevailing
winds during the heating season
Ensure adequate outdoor air for all combustion appliances
and exhaust equipment
Ensure furnace and air conditioning return vents are not
located in the immediate vicinity of the appliance
Avoid installing the appliance near doors, walkways or
small isolated spaces
Recessed lighting should be a "sealed can" design
Attic hatches weather stripped or sealed
Attic mounted duct work and air handler joints and seams
taped or sealed
D. Draft
Draft is the pressure difference needed to vent an appli-
ance successfully. When an appliance is drafting suc-
cessfully, all combustion byproducts are exiting the home
through the chimney.
Install through the warm airspace enclosed by the build-
ing envelope. This helps to produce more draft, especially
during lighting and die-down of the fire.
Considerations for successful draft include:
Preventing negative pressure
Location of appliance and chimney
October 12, 2017
NOTICE: Hearth & Home Technologies assumes no
responsibility for the improper performance of the chimney
system caused by:
Inadequate draft due to environmental conditions
Down drafts
Tight sealing construction of the structure
Mechanical exhausting devices
E. Chimney and Exhaust Connection
1. Chimney & Connector: Use 3 or 4 inch (76-102mm)
diameter type "L" or "PL" venting system. It can be vented
vertically or horizontally.
NOTE: The appliance exhaust outlet is designed to ac-
commodate 3 inch venting. Use of 4 inch venting requires
the use of a 3-to-4 inch exhaust vent increaser in addition
to any other venting components needed, sold separate-
ly.
2. Mobile Home: Approved for all Listed pellet vent. If using
the 3 inch (76mm) vertical Top Vent Adapter Kit or the 3
to 6 inch (76-152mm) Top Vent Offset Adapter, use Listed
double wall flue connector. A Quadra-Fire Outside Air Kit
(OAK-3) must be used with manufactured home installa-
tions.
3. Residential: The 3 inch (76mm) vertical Top Vent Adapter
Kit and the 3 to 6 inch (76-152mm) Top Vent Offset Adapter
are tested to use 24 gauge single wall flue connector or
Listed double wall flue connector to Class A Listed metal
chimneys, or masonry chimneys meeting International
Residential Code standards for solid fuel appliances.
4. INSTALL VENT AT CLEARANCES SPECIFIED BY THE
VENT MANUFACTURER.
5. Secure exhaust venting system to the appliance with at
least 3 screws. Also secure all connector pipe joints with
at least 3 screws through each joint.
6. DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST
VENTING SYSTEM OF THIS Appliance.
7. DO NOT CONNECT THIS Appliance TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
NOTE: All pipe must be welded seam pipe whenever
possible. Seal pipe joints with high temperature silicone
(500°F [260°C] minimum rated only).
USE ONLY RECOMMENDED VENTING COMPONENTS;
OTHERWISE MAKESHIFT PARTS MAY RESULT IN PROP-
ERTY DAMAGE, PERSONAL INJURY, OR DEATH.
7080-162B
MT VERNON E2-C
WARNING
15

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MT VERNON E2-C and is the answer not in the manual?

Questions and answers

Table of Contents