Cu-3Z68Tbe - Panasonic CU-3Z52TBE Service Manual

Outdoor unit
Hide thumbs Also See for CU-3Z52TBE:
Table of Contents

Advertisement

10.2 CU-3Z68TBE

10.2.1
Check Points
Outdoor unit power supply:
Single-phase 230V, 50Hz
16A switch
(circuit breaker)
(Not included in the unit)
2
2.5 mm
or more x 3 core
(Not included in the unit)
Outdoor
wiring work
AMP Air Conditioning
Indoor/outdoor unit
connection cables
(Not included in the unit)
2
1.5 mm
Unit C
(polychloroprene sheathed)
(Not included in the unit)
Unit B
2
1.5 mm
flexible cord x 4 core
(polychloroprene sheathed)
(Not included in the unit)
Unit A
Applicable connecting tube kit:
CZ-3F type
Unit A Maximum pipe length: 25 m
Unit B Maximum pipe length: 25 m
Unit C Maximum pipe length: 25 m
Total maximum pipe length: 60m
Grounding work
101
flexible cord x 4 core
www.ampair.co.uk | sales@ampair.co.uk
elevation:
15m max
.
elevation between
each of the indoo
units and between
the indoor and
outdoor units.

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CU-3Z52TBE and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Cu-4z68tbeCu-3z68tbe

Table of Contents

Save PDF