Function
Name
code
Restart after
P01.21
power off
The waiting
P01.22
time of restart
after power off
P01.23
Start delay time
Delay of the
P01.24
stopping speed
P01.25
0Hz output

P02 Group Motor 1

Detailed instruction of parameters
When the set frequency is above the lower limit one again
and it lasts for the time set by P01.20, the inverter will run
automatically.
Setting range: 0.0~3600.0s (valid when P01.19=2)
This function can enable the inverter start or not after the
power off and then power on.
0: Disabled
1: Enabled, if the starting need is met, the inverter will run
automatically after waiting for the time defined by P01.22.
The function determines the waiting time before the
automatic running of the inverter when powering off and
then powering on.
Setting range: 0.0~3600.0s (valid when P01.21=1)
The function determines the brake release after the running
command is given, and the inverter is in a stand-by state
and wait for the delay time set by P01.23
Setting range: 0.0~60.0s
Setting range: 0.0~100.0s
Select the 0Hz output of the inverter.
0: Output without voltage
1: Output with voltage
2: Output at the DC braking current
38
Function Parameters
Default
Modify
value
0
1.0s
0.0s
0.0s
0