APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 23 of 52)
ADDR
REGISTER NAME
6008
87L Current Differential Ground Function
6009
87L Current Differential Ground Pickup
600A
87L Current Differential Ground Restraint
600B
87L Current Differential Ground Delay
600C
87L Current Differential Key DTT
600D
87L Current Differential External Key DTT
600E
87L Current Differential Target
600F
87L Current Differential Event
6010
87L Current Differential Tap 2 Setting
CT Failure Detector (Read/Write Setting)
6124
CT Fail Function
6125
CT Fail Block
6126
CT Fail Current Source 1
6127
CT Fail Current Pickup 1
6128
CT Fail Current Source 2
6129
CT Fail Current Pickup 2
612A
CT Fail Voltage Source
612B
CT Fail Voltage Pickup
612C
CT Fail Pickup Delay
612D
CT Fail Target
612E
CT Fail Events
Autoreclose (Read/Write Setting) (6 modules)
6240
Autoreclose 1 Function
6241
Autoreclose 1 Initiate
6242
Autoreclose 1 Block
6243
Autoreclose 1 Max Number of Shots
6244
Autoreclose 1 Manual Close
6245
Autoreclose 1 Manual Reset from LO
6246
Autoreclose 1 Reset Lockout if Breaker Closed
6247
Autoreclose 1 Reset Lockout On Manual Close
6248
Autoreclose 1 Breaker Closed
6249
Autoreclose 1 Breaker Open
624A
Autoreclose 1 Block Time Upon Manual Close
624B
Autoreclose 1 Dead Time Shot 1
624C
Autoreclose 1 Dead Time Shot 2
624D
Autoreclose 1 Dead Time Shot 3
624E
Autoreclose 1 Dead Time Shot 4
624F
Autoreclose 1 Reset Lockout Delay
6250
Autoreclose 1 Reset Time
6251
Autoreclose 1 Incomplete Sequence Time
6252
Autoreclose 1 Events
6253
Autoreclose 1 Reduce Max 1
6254
Autoreclose 1 Reduce Max 2
6255
Autoreclose 1 Reduce Max 3
6256
Autoreclose 1 Add Delay 1
6257
Autoreclose 1 Delay 1
6258
Autoreclose 1 Add Delay 2
6259
Autoreclose 1 Delay 2
625A
Reserved (4 items)
625E
...Repeated for Autoreclose 2
627C
...Repeated for Autoreclose 3
629A
...Repeated for Autoreclose 4
62B8
...Repeated for Autoreclose 5
62D6
...Repeated for Autoreclose 6
GE Multilin
RANGE
0 to 1
0.05 to 1
1 to 50
0 to 5
0 to 1
0 to 65535
0 to 2
0 to 1
0.2 to 5
0 to 1
0 to 65535
0 to 5
0 to 2
0 to 5
0 to 2
0 to 5
0 to 2
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
1 to 4
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 655.35
0 to 655.35
0 to 655.35
0 to 655.35
0 to 655.35
0 to 655.35
0 to 655.35
0 to 655.35
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 655.35
0 to 65535
0 to 655.35
0 to 0.001
L30 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
pu
0.01
F001
%
1
F001
seconds
0.01
F001
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
0.01
F001
---
1
F102
---
1
F300
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.01
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F001
---
1
F300
---
1
F300
---
1
F108
---
1
F108
---
1
F300
---
1
F300
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.01
F001
---
1
F300
s
0.01
F001
---
0.001
F001
DEFAULT
0 (Disabled)
10
25
10
1 (Enabled)
B
0
0 (Self-reset)
0 (Disabled)
100
0 (Disabled)
0
0 (SRC 1)
2
1 (SRC 2)
2
0 (SRC 1)
20
1000
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
1
0
0
0 (Off)
0 (Off)
0
0
1000
100
200
300
400
6000
6000
500
0 (Disabled)
0
0
0
0
0
0
0
0
B-31