The L60 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as
the characteristics of the line or feeder, are entered in this menu.
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in
the FaultReport.txt file includes:
•
Fault report number
•
Name of the relay, programmed by the user
•
Firmware revision of the relay
•
Date and time of trigger
•
Name of trigger (specific operand)
•
Line/feeder ID via the name of a configured signal source
•
Active setting group at the time of trigger
•
Pre-fault current and voltage phasors (two cycles before either a 50DD disturbance associated with fault report source
or the trigger operate)
•
Fault current and voltage phasors (one cycle after the trigger)
•
Elements operated at the time of triggering
•
Events: 9 before trigger and 7 after trigger (only available via the relay webpage)
•
Fault duration times for each breaker (created by the breaker arcing current feature)
GE Multilin
FAULT REPORTS
FAULT REPORT 1
FAULT REPORT 1
SOURCE: SRC 1
FAULT REPORT 1 TRIG:
Off
FAULT REPORT 1 Z1
MAG: 3.00 Ω
FAULT REPORT 1 Z1
ANGLE: 75°
FAULT REPORT 1 Z0
MAG: 9.00 Ω
FAULT REPORT 1 Z0
ANGLE: 75°
FAULT REPORT 1 LINE
LENGTH UNITS: km
FAULT REP 1 LENGTH
(km
): 100.0
FAULT REPORT 1 VT
SUBSTITUTION: None
FAULT REP 1 SYSTEM
Z0 MAG: 2.00 Ω
FAULT REP 1 SYSTEM
Z0 ANGLE: 75°
L60 Line Phase Comparison Relay
5.2 PRODUCT SETUP
5.2.7 FAULT REPORTS
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: FlexLogic™ operand
Ω
Range: 0.01 to 250.00
in steps of 0.01
Range: 25 to 90° in steps of 1
Ω
Range: 0.01 to 650.00
in steps of 0.01
Range: 25 to 90° in steps of 1
Range: km, miles
Range: 0.0 to 2000.0 in steps of 0.1
Range: None, I0, V0
Ω
Range: 0.01 to 650.00
in steps of 0.01
Range: 25 to 90° in steps of 1