GROUPED ELEMENTS
5.7.2 Setting group 1
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6)
SETTING GROUP 1
5
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.
5.7.3 Transformer
5.7.3.1 Menu
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) TRANSFORMER
TRANSFORMER
This menu contains the settings for the transformer differential elements and the transformer thermal elements.
5-200
TRANSFORMER
PHASE CURRENT
NEUTRAL CURRENT
GROUND CURRENT
NEGATIVE SEQUENCE
CURRENT
GENERATOR
UNBALANCE
SPLIT PHASE
VOLTAGE ELEMENTS
LOSS OF EXCITATION
ACCIDENTAL ENERGIZATION
POWER
STATOR
GROUND
PERCENT
DIFFERENTIAL
HOTTEST-SPOT
TEMPERATURE
AGING FACTOR
LOSS OF LIFE
See below
See page 5-208
See page 5-220
See page 5-228
See page 5-235
See page 5-239
See page 5-241
See page 5-245
See page 5-257
See page 5-259
See page 5-261
See page 5-264
See below
See page 5-206
See page 5-206
See page 5-207
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS