EFC x610 Series

14.2.6 Communication Disruption and Response

Code
Communication error
E8.01
detection time
Communication error
E8.02
protection mode
When [E8.01] = 0.0 s, the disruption detection function is inactive.
If the interval between the current and next communication commands ex-
ceeds the time defined in [E8.01] 'Communication error detection time', the
frequency converter will reports a communication error code and act as de-
fined in [E8.02] 'Communication error protection mode':
– [E8.02] = 0: Freewheeling stop
The motor freewheels to stop after the communication timeout no matter
the settings of parameter E0.50 'Stop mode'.
– [E8.02] = 1: Keep running
The motor continues running at the setting frequency, and warning code
'C-dr' will be displayed on the operating panel.
DOK-RCON03-EFC-X610***-IT03-EN-P
Name
0.0...60.0 s (0.0: Inactive)
0, 1
Setting range
Default
Bosch Rexroth AG
Communication
Min.
Attri.
0.0
0.1
Stop
1
Stop
231/337