Rectify faults ........................23 Exchanging the electronics module ................24 How to proceed if a repair is needed ................25 Dismount Dismounting steps......................26 Disposal ......................... 26 Supplement Technical data ........................ 27 Dimensions ........................30 VEGAWAVE 61 • - NAMUR...
Instructions manuals for accessories and replacement parts Tip: To ensure reliable setup and operation of your VEGAWAVE 61, we of- fer accessories and replacement parts. The corresponding documen- tations are: • 32357 - External housing - VEGAWAVE •...
Action This arrow indicates a single action. Sequence of actions Numbers set in front indicate successive steps in a procedure. Battery disposal This symbol indicates special information about the disposal of bat- teries and accumulators. VEGAWAVE 61 • - NAMUR...
During work on and with the device the required personal protective equipment must always be worn. Appropriate use The VEGAWAVE 61 is a sensor for point level detection. You can find detailed information about the area of application in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
This device fulfills the legal requirements of the applicable EC guide- lines. By attaching the CE mark, VEGA provides a confirmation of successful testing. You can find the CE conformity declaration in the download area of "www.vega.com". SIL conformity VEGAWAVE 61 meets the requirements to the functional safety ac- cording to IEC 61508. Further information is available in the Safety Manual "VEGAWAVE series 60". Safety instructions for Ex areas Please note the Ex-specific safety information for installation and op- eration in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.
With the serial number, you can access the delivery data of the instru- ment via www.vega.com, "VEGA Tools" and "serial number search". You can find the serial number on the inside of the instrument as well as on the type label on the outside. Principle of operation Application area VEGAWAVE 61 is a point level sensor with tuning fork for point level detection. VEGAWAVE 61 • - NAMUR...
It also works when subjected to strong external vibrations or changing products. Solid detection in water If VEGAWAVE 61 was ordered for solids detection in water, the tuning fork is set to the density of water. In air or when immersed in water (density: 1 g/cm³/0.036 lbs/in), VEGAWAVE 61 signals "uncovered".
Not exposed to corrosive media • Protected against solar radiation • Avoiding mechanical shock and vibration • Storage and transport Storage and transport temperature see chapter "Supplement - temperature Technical data - Ambient conditions" • Relative humidity 20 … 85 % VEGAWAVE 61 • - NAMUR...
You can find the specifications in chapter "Technical data" and on the nameplate. In general, VEGAWAVE 61 can be installed in any position. The instru- Switching point ment only has to be mounted in such a way that the vibrating element is at the height of the desired switching point.
A spout forms in the concave protective sheet preventing wear of the protective sheet. To achieve a very precise switching point, you can install VEGAWAVE Horizontal installation 61 horizontally. However, if the switching point can have a tolerance of a few centimeters, we recommend mounting VEGAWAVE 61 approx. 20° inclined to the vessel bottom to avoid buildup. VEGAWAVE 61 • - NAMUR...
Page 12
Fig. 4: Horizontal installation Inflowing medium If VEGAWAVE 61 is mounted in the filling stream, unwanted false measurement signals can be generated. For this reason, mount VEGAWAVE 61 at a position in the vessel where no disturbances, e.g. from filling openings, agitators, etc., can occur. Product flow To make sure the tuning fork of VEGAWAVE 61 generates as little resistance as possible to product flow, mount the sensor so that the surfaces are parallel to the product movement.
Page 13
Marking on top with screwed version Baffle protection against In applications such as grit chambers or settling basins for coarse falling rocks sediments, the vibrating element must be protected against damage with a suitable baffle. This baffle must be manufactured by you. > 125 mm (> 5") Fig. 7: Baffle for protection against mechanical damage VEGAWAVE 61 • - NAMUR...
Proceed as follows: 1. Unscrew the housing cover 2. Loosen compression nut of the cable entry gland 3. Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 1 cm (0.4 in) of insulation from the ends of the individual wires 4. Insert the cable into the sensor through the cable entry 5. Lift the opening levers of the terminals with a screwdriver (see following illustration) VEGAWAVE 61 • - NAMUR...
10. If necessary, carry out a fresh adjustment 11. Screw the housing cover back on The electrical connection is finished. Wiring plan, single chamber housing The following illustrations apply to the non-Ex as well as to the Ex-d version. VEGAWAVE 61 • - NAMUR...
Page 16
In addition to the test key on the electronics module, you can connect an external key to start the test procedure. Connect the key according to the following wiring plan. In shipping condition, terminals 3 and 4 are bridged. For additional information see "Recurring function test". VEGAWAVE 61 • - NAMUR...
External simulation key Wiring plan - version IP 66/IP 68, 1 bar Wire assignment, con- nection cable Fig. 12: Wire assignment, connection cable brown (+) and blue (-) to power supply or to the processing system Shielding VEGAWAVE 61 • - NAMUR...
Control lamp Switching point adapta- With the potentiometer you can adapt the switching point to the solid. tion (1) It is already preset and must only be modified in special cases. By default, the potentiometer of VEGAWAVE 61 is set to the right stop (> 0.02 g/cm³ or 0.0008 lbs/in³). In case of very light-weight solids, turn the potentiometer to the left stop (> 0.008 g/cm³ or 0.0003 lbs/ in³). VEGAWAVE 61 will thus be more sensitive and can detect light- weight solids more reliably.
The following chart provides an overview of the switching conditions depending on the set mode and the level. Note: The mode setting on the NAMUR amplifier must be selected in such a way that the switching output takes on safe state in case of failure (I ≤ 1 mA). Level Signal current - Control lamp Sensor Falling character- ≥ 2.4 mA istics max. Falling character- ≤ 1 mA istics max. VEGAWAVE 61 • - NAMUR...
NAMUR electronics module WE60N. For this purpose, the switching delay must be set to 0.5 s. VEGAWAVE 61 has an inte- grated simulation key. The simulation key is lowered on the electronics module. Push the simulation key for > 2 seconds.
Page 21
When used in measuring chains according to IEC 61508, mode B (dry run protection) is not permitted. You can carry out the function test with the stated current values also directly with a safety PLC or a process control system. VEGAWAVE 61 • - NAMUR...
Page 22
6 Setup Test assessment (SPLC) Test passed • Low Current ≥ 2 s • High Current ≥ 1 s Test not passed • Low Current < 2 s / > 4 s • High Current < 1 s / > 2 s VEGAWAVE 61 • - NAMUR...
24 hour service hotline Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550. The hotline is manned 7 days a week round-the-clock. Since we offer this service worldwide, the support is only available in the English language. The service is free, only standard call charges are incurred.
6. Pull out the old electronics module 7. Compare the new electronics module with the old one. The type label of the electronics module must correspond to that of the old electronics module. This applies particularly to instruments used in hazardous areas. VEGAWAVE 61 • - NAMUR...
Clean the instrument and pack it damage-proof • Attach the completed form and, if need be, also a safety data sheet outside on the packaging • Please contact the agency serving you to get the address for the return shipment. You can find the agency on our home page www.vega.com. VEGAWAVE 61 • - NAMUR...
These may be used only for privately used products according to the WEEE directive. Correct disposal avoids negative effects on humans and the environ- ment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal. VEGAWAVE 61 • - NAMUR...
Ʋ Pipe thread, cylindrical (DIN 3852-A) G1½ A Ʋ American pipe thread, conical 1½ NPT (ASME B1.20.1) Instrument weight (depending on pro- 0.8 … 4 kg (0.18 … 8.82 lbs) cess fitting) Max. lateral load 600 N (135 lbf) Fig. 31: Max. lateral load alongside fork side (narrow fork side) Output variable Output Two-wire NAMUR output VEGAWAVE 61 • - NAMUR...
Page 28
250°C (-58°F) (122°F) (212°F) (302°F) (392°F) (482°F) -40°C (-40°F) Fig. 32: Ambient temperature - Process temperature Process temperature Ambient temperature Temperature range with temperature adapter Product density Ʋ Standard > 0.02 g/cm³ (0.0007 lbs/in³) Ʋ adjustable > 0.008 g/cm³ (0.0003 lbs/in³) Granular size max. 10 mm (0.4 in) VEGAWAVE 61 • - NAMUR...
Page 29
Voltage supply Operating voltage (characteristics ac- for connection to an amplifier according to NAMUR cording to standard) IEC 60947-5-6, approx. 8.2 V Off-load voltage approx. 8.2 V Shortcircuit current approx. 8.2 mA Depending on the version M12 x 1, according to ISO 4400, Harting, 7/8" FF. VEGAWAVE 61 • - NAMUR...
Approvals Instruments with approvals can have different technical specifications depending on the version. For that reason the associated approval documents of these instruments have to be carefully noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools" and "Instrument search" as well as via "Downloads" and "Approvals". Dimensions Housing in protection IP 66/IP 67 and IP 66/IP 68; 0.2 bar...
Page 31
Fig. 34: Housing versions with protection rating IP 66/IP 68 (1 bar) Stainless steel housing, precision casting Aluminium housing G1½ ø 43 mm (1.69") Fig. 35: VEGAWAVE 61, threaded version G1½ A (DIN ISO 228/1) VEGAWAVE 61 • - NAMUR...
Page 32
9 Supplement ø 34 mm (1.34") Fig. 36: Temperature adapter VEGAWAVE 61 • - NAMUR...
Page 33
Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec- tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus- trial. Para mayor información revise la pagina web www.vega.com.