Connecting EnerVista 750/760 Setup to the Relay
Using the Quick
Connect Feature
GE Multilin
8.
Click the Read Order Code button to connect to the 750/760 device and
upload the order code. If an communications error occurs, ensure that the 750/
760 serial communications values entered in the previous step correspond to
the relay setting values.
9.
Click OK when the relay order code has been received. The new device will be
added to the Site List window (or Online window) located in the top left corner
of the main EnerVista 750/760 Setup window.
The 750/760 Site Device has now been configured for serial communications.
Proceed to Connecting to the Relay on page 4–17 to begin communications.
The Quick Connect button can be used to establish a fast connection through the
front panel RS232 port of a 750/760 relay. The following window will appear when
the Quick Connect button is pressed:
As indicated by the window, the Quick Connect feature quickly connects the
EnerVista 750/760 Setup software to a 750/760 front port with the following
settings: 9600 baud, no parity, 8 bits, 1 stop bit. Select the PC communications port
connected to the relay and press the Connect button.
The EnerVista 750/760 Setup software will display a window indicating the status of
communications with the relay. When connected, a new Site called "Quick Connect"
will appear in the Site List window. The properties of this new site cannot be
changed.
The 750/760 Site Device has now been configured via the Quick Connect feature for
serial communications. Proceed to Connecting to the Relay on page 4–17 to begin
communications.