GE C70 Instruction Manual page 358

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

GROUPED ELEMENTS
CHAPTER 5: SETTINGS
Figure 5-96: Neutral current unbalance connections
5
The following settings are available. They are for the neutral current unbalance 1 element. The same descriptions apply to
the neutral current unbalance 2 and 3 elements.
— This setting indicates the signal source that signifies the split-phase neutral current in
NTRL CUR UNBALCE 1 BANK SOURCE
its ground current channel. At minimum the ground channel of this source must be set. If the factor compensating for
inherent bank unbalance is set above zero signalling the intent of using the compensation, the phase currents of this
source must be configured as well. Without the phase currents configured under this source, the function would run only if
the magnitude of the inherent unbalance factor is set to zero.
To improve accuracy, a relatively low-ratio window CT can be used for instrumentation of the split-phase neutral current,
and be wired to a 1 A or even sensitive ground relay input for extra sensitivity. CT primary and secondary ratings are
entered under a separate menu. Directionality of wiring of the split-phase current is not important for proper functioning of
the feature as long as the angle of the factor compensating for the inherent unbalance is set appropriately.
— This setting defines magnitude of the factor compensating for the inherent unbalance of the
NTRL CUR UNBALCE 1 K MAG
bank. Under balanced conditions, the amount of the spill current measured in the neutral connection between the banks is
proportional to the positive-sequence component of the total current of the two banks. This setting defines the magnitude
of the proportionality factor. Quality of balancing the bank with a given value of this setting can be viewed under
ACTUAL
menu. An automatic setting procedure is available via the
menu to calculate the compensating factor
VALUES
COMMANDS
automatically. Setting the compensating factor to zero effectively disables the compensation. If further the slope is set to
zero as well, this feature becomes a plain overcurrent element responding to the neutral split-phase current.
5-192
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL