APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 25 of 51)
ADDR
REGISTER NAME
72A7
Neg Sequence Directional Overcurrent 1 Reverse Pickup
72A8
Negative Sequence Directional Overcurrent 1 Target
72A9
Negative Sequence Directional Overcurrent 1 Block
72AA
Negative Sequence Directional Overcurrent 1 Events
72AB
Negative Sequence Directional Overcurrent 1 Offset
72AC
Neg Seq Directional Overcurrent 1 Pos Seq Restraint
72AD
Reserved (3 items)
72B0
...Repeated for Neg Seq Directional Overcurrent 2
Breaker Arcing Current Settings (Read/Write Setting)
72C0
Breaker 1 Arcing Current Function
72C1
Breaker 1 Arcing Current Source
72C2
Breaker 1 Arcing Current Initiate A
72C3
Breaker 1 Arcing Current Initiate B
72C4
Breaker 1 Arcing Current Initiate C
72C5
Breaker 1 Arcing Current Delay
72C6
Breaker 1 Arcing Current Limit
72C7
Breaker 1 Arcing Current Block
72C8
Breaker 1 Arcing Current Target
72C9
Breaker 1 Arcing Current Events
72CA
...Repeated for Breaker 2 Arcing Current
dcmA Inputs (Read/Write Setting) (24 modules)
7300
dcmA Inputs 1 Function
7301
dcmA Inputs 1 ID
7307
Reserved 1 (4 items)
730B
dcmA Inputs 1 Units
730E
dcmA Inputs 1 Range
730F
dcmA Inputs 1 Minimum Value
7311
dcmA Inputs 1 Maximum Value
7313
Reserved (5 items)
7318
...Repeated for dcmA Inputs 2
7330
...Repeated for dcmA Inputs 3
7348
...Repeated for dcmA Inputs 4
7360
...Repeated for dcmA Inputs 5
7378
...Repeated for dcmA Inputs 6
7390
...Repeated for dcmA Inputs 7
73A8
...Repeated for dcmA Inputs 8
73C0
...Repeated for dcmA Inputs 9
73D8
...Repeated for dcmA Inputs 10
73F0
...Repeated for dcmA Inputs 11
7408
...Repeated for dcmA Inputs 12
7420
...Repeated for dcmA Inputs 13
7438
...Repeated for dcmA Inputs 14
7450
...Repeated for dcmA Inputs 15
7468
...Repeated for dcmA Inputs 16
7480
...Repeated for dcmA Inputs 17
7498
...Repeated for dcmA Inputs 18
74B0
...Repeated for dcmA Inputs 19
74C8
...Repeated for dcmA Inputs 20
74E0
...Repeated for dcmA Inputs 21
74F8
...Repeated for dcmA Inputs 22
7510
...Repeated for dcmA Inputs 23
7528
...Repeated for dcmA Inputs 24
Disconnect switches (read/write settings)
7540
Disconnect switch 1 function
GE Multilin
RANGE
0.015 to 30
0 to 2
0 to 65535
0 to 1
0 to 250
0 to 0.5
0 to 1
0 to 1
0 to 5
0 to 65535
0 to 65535
0 to 65535
0 to 65.535
0 to 50000
0 to 65535
0 to 2
0 to 1
0 to 1
---
0 to 65535
---
0 to 6
-9999.999 to 9999.999
-9999.999 to 9999.999
0 to 65535
0 to 1
D30 Line Distance Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
pu
0.05
F001
---
1
F109
---
1
F300
---
1
F102
ohms
0.01
F001
---
0.001
F001
---
1
F001
---
1
F102
---
1
F167
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
2
kA
-cyc
1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
---
F205
---
1
F001
---
---
F206
---
1
F173
---
0.001
F004
---
0.001
F004
---
1
F001
---
1
F102
DEFAULT
5
0 (Self-reset)
0
0 (Disabled)
0
B
63
0
0 (Disabled)
0 (SRC 1)
0
0
0
0
1000
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
"DCMA I 1"
0
"mA"
6 (4 to 20 mA)
4000
20000
0
0 (Disabled)
B-33