6.2.2 Installation in the active zone

Between the maximum level (b2) and the mounting element the minimum
distance (a2) must be adhered to (fig. 6.3 and table 6-4).
► Fix mounting elements in the mounting
zone (M) (fig. 6-1). Adhere to the
maximum permitted outside length (c)
(table 6-1 ).
► Ensure that the maximum level (b2)
is not exceeded after completed
installation:
(b2) = (L) - (c) - (a2) (without offset)
► Observe further minimum distances
according to table 6-4.
c:
Maximum permitted outside length
(observe footnote table 6-1)
a2:
Minimum distance between mounting
element and maximum level (b2).
b2:
Max. level from the lower edge of
the sensor
x
u
a2 (LK3122)
a2 (LK3123)
a2 (LK3124)
v *
)
w *
)
*) → Fig. 6-1.
MEdI = CLW.1
[cm]
[inch]
2.0
0.8
1.0
0.4
2.0
0.8
4.0
1.6
6.0
2.4
4.5
1.8
4.0
1.6
Table 6-4
MEdI = CLW.2, OIL.1
[cm]
[inch]
3.0
1.2
1.0
0.4
2.5
1.0
4.5
1.8
7.0
2.8
4.5
1.8
5.0
2.0
Fig. 6-3
x
MEdI = OIL.2 / Auto
[cm]
[inch]
4.0
1.6
1.0
0.4
3.0
1.2
5.0
2.0
8.0
3.2
4.5
1.8
6.0
2.4
UK
19