General Technical Specifications

6.3 Transport and storage conditions

6.3
Transport and storage conditions
Requirements for Fail-Safe Modules
Fail-safe modules surpass the requirements for transport and storage conditions defined in
IEC 61131, Part 2. The following specifications apply to fail-safe modules that are
transported and stored in the original packaging.
Type of condition
Free fall
Temperature
Temperature change
Air pressure
Relative humidity
6.4

Mechanical and Climatic Environmental Conditions

Climatic environmental conditions
The following climatic environmental conditions are applicable:
Environmental Conditions
Temperature
Temperature change
Relative humidity
Air pressure
Pollutant concentration
Mechanical Environmental Conditions
The requirements for mechanical environmental conditions are presented in the following
table in the form of sinusoidal vibrations.
Frequency range
5 ≤ f ≤ 8 Hz
8 ≤ f ≤ 150 Hz
46
Areas of Application
From -25 °C to 55 °C
10 K/h
From 5% to a maximum of 100%
From 1080 hPa to 795 hPa
SO
: < 0.5 ppm;
2
Relative humidity < 60%, no
condensation
H
S: < 0.1 ppm;
2
Relative humidity < 60%, no
condensation
Constant
0.35 mm amplitude
5 g constant acceleration
Permissible range
≤ 1 m
From -25°C to +70°C
20 K/h
From 1080 hPa to 660 hPa
(corresponds to an altitude of -1000 m to 3500 m)
From 5% to 95%, without condensation
Comments
All mounting positions
With condensation
Corresponds to an altitude of -1000 m
to 2000 m
Test:
10 ppm; 4 days
1 ppm; 4 days
Intermittent
0.75 mm amplitude
10 g constant acceleration
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02