Diagnostic Error Messages - Mercoid Series MPC Installation And Operating Manual

Pump controller
Table of Contents

Advertisement

DIAGNOSTIC ERROR MESSAGES

Display
Meaning
UFL
Underflow or
or
Overflow: Process
0FL
value has
exceeded input
range ends.
CHEC
CAL
Check calibration
appears as an
alternating
message if the
instrument
calibration nears
tolerance edges.
Check calibration
appears as a
flashing message if
the instrument
calibration exceeds
specification.
ArEA
This message
(Alternates
appears if the
with PV)
ambient
temperature of the
control approaches
the ends of
ArEA
tolerance. This
message appears
if the ambient
temperature of the
control is out of
range or RJC
sensor is broken.
SP Outputs
Action Required
Set point
Input signals may normally
outputs active
go above or below range
Alarms active
ends. If not, check input and
correct.
Set point
Remove the instrument for
outputs active
service and / or recalibration.
Alarms active
To reset use the INDEX &
ENTER keys.
Remove the instrument for
Set point
outputs
service and / or recalibration.
inactive
To reset use the INDEX &
Alarms active
ENTER keys.
Set point
Correct the ambient
outputs active
temperature conditions.
Alarm active
Ventilate the area of the
cabinet or check for clogged
filters. If RJC broken, return
to factory for service.
Set point
Correct the ambient
outputs active
temperature conditions.
Alarms active
Ventilate the area of the
cabinet or check for clogged
filters. If RJC broken, return
to factory for service.
25