DTR.PYRP.PYRD.PYRL-28.
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
PRESSURE TRANSMITTERS
PYRP-28, PYRP-28IS
DIFFERENTIAL PRESSURE TRANSMITTERS
PYRD-28, PYRD-28IS
HYDROSTATIC LEVEL TRANSMITTER PROBES
PYRL-28, PYRL-28IS
JULY 2012
Rev. C
The Pyropress Engineering Company Limited.
Bell Close, Newnham Industrial Estate, Plympton,
Plymouth, Devon, United Kingdom PL7 4JH
Tel: +44 (0) 1752 333933 Fax: +44 (0) 1752 336681
Email: sales@pyropress.com Website: www.pyropress.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PYRP-28 and is the answer not in the manual?

Questions and answers

Summary of Contents for Pyropress PYRP-28

  • Page 1 HYDROSTATIC LEVEL TRANSMITTER PROBES PYRL-28, PYRL-28IS JULY 2012 Rev. C The Pyropress Engineering Company Limited. Bell Close, Newnham Industrial Estate, Plympton, Plymouth, Devon, United Kingdom PL7 4JH Tel: +44 (0) 1752 333933 Fax: +44 (0) 1752 336681 Email: sales@pyropress.com Website: www.pyropress.com...
  • Page 2 DTR.PYRP.PYRD.PYRL-28 Symbols used Symbol Description Warning – Installer to proceed strictly in accordance with the information contained within the manual in order to ensure the safety and full functionality of the product. Denotes information applicable during installation and operation of all listed products. Denotes information essential to Exia certified products.
  • Page 3: Table Of Contents

    ........................5 ECHNICAL 5.2.1. PYRD–28. M .......................... 5 EASUREMENT ANGES 5.2.2. PYRD–28. O ........................5 PERATING ARAMETERS 5.3. PYRP-28, PYRD-28.- C ....................5 OMMON PARAMETERS 5.3.1. PYRP–28, PYRD–28 . E ....................5 LECTRICAL ARAMETERS 5.3.2. PYRP–28, PYRD–28. P ................5 ERMITTED...
  • Page 4: Introduction

    3.5. The PYRP-28 or PYRD-28 transmitters and the PYRL-28 probes provide a 2 wire, 4 - 20mA output signal. Alternatively, the PYRP-28 and PYRD-28 can as an supplied with either a 3 wire, 0 - 20mA or 0 - 10V output...
  • Page 5: Identifying Marks. Ordering Procedure

    5. TECHNICAL DATA 5.1. PYRP–28 Pressure Transmitter Technical Data 5.1.1. PYRP–28 Measurement Ranges The PYRP-28 pressure transmitter can be supplied specifically calibrated with any desired range contained within the below spans: Gauge pressure : 0 - 10 mbar to 0 - 1000 Bar Absolute pressure : 400mbar to 80bar.
  • Page 6: Pyrd-28. Technical Data

    0.05% Hysteresis and repeatability *- This error can be eliminated by zeroing the transmitter in static pressure conditions with zero differential pressure. 5.3. PYRP-28 Pressure and PYRD-28 Differential Pressure Transmitters - Common Parameters 5.3.1. Electrical Parameters Power supply 10.5 - 36V DC, nominally 24V DC (2 wire, 4 - 20mA version) 15 - 30V DC (3 wire, 0 - 10V or 0 - 20mA version) Note: For power supply for Intrinsically Safe versions see Appendix 01 of this manual.
  • Page 7: Pyrp-28, Pyrd-28. Construction Materials

    C type connection for direct mounting with a 3 or 5 valve manifold see Fig. 8. 5.5. PYRP–28 and PYRD–28 Electrical Connectors and IP Ratings. PYRP-28, PYRD-28 with PD-type connector, DIN 43650, PG-11 gland. IP65 rated (EN 60529:1991/A1:2000) PYRP-28, PYRD-28 with PZ-type terminal box, M20x1,5 packing gland. IP66 rated (EN 60529:1991/A1:2000) PYRP-28, PYRD-28, PYRL-28 with PK-type cable connector.
  • Page 8: Casing , Electrical Connections

    6.3. Casing and Electrical Connections 6.3.1. The casing of the PYRP-28 and PYRD-28 transmitters is manufactured from ø27 tube (304 st steel or 316 st. steel), fixed to the the sensing module as shown in figure 1b and 7. At the electrical connection end is the PD type electrical connector with PG-11 packing gland.
  • Page 9: Installation Location Of Transmitters

    (less than -25°C), the transmitter and impulse lines should be heated. 7.3. High Process Temperatures. The PYRP-28 and PYRD-28 transmitters may be used to measure media with temperatures of up to 120°C. To protect the sensing module from temperatures in excess of 120ºC, suitably long impulse lines should be incorporated to disperse the heat and to reduce the process temperature at the transmitter inlet.
  • Page 10: Installation And Mechanical Connections

    (if possible) to the side of the equipment and not directly in the flow of a continuous rising heat source. The PYRP-28 can be fitted to a Pyropress syphon loop to protect against high temperature vapour applications, see Fig. 14.
  • Page 11: Connections For Transmitters With Pd- Type Connector

    9.4. Connections for transmitters incorporating terminal housing (PZ Type) The PYRP-28 and PYRD-28 transmitters with PZ terminal housing should be wired to the terminal block as shown in figure 2 (page 15). Tighten the packing gland ensuring there is a water tight seal on the cable, and refit the screwed terminal cover and gasket.
  • Page 12: Earthing

    DTR.PYRP.PYRD.PYRL-28 9.6. Earthing The transmitter earthing methods are detailed in figures 1a and 2. If the transmitter is directly mounted or connected to an fully earthed electrically conductive structure or pipework system via a metal bodied fitting then additional earthing would not be necessary 10.
  • Page 13: Spare Parts

    DTR.PYRP.PYRD.PYRL-28 11.4. Spare parts. The following transmitter parts may need replacing due to damage or normal wear: PD connector – DIN plug and gasket, connector base screwed clamping ring, information/rating label. PK connector – the entire connector. PZ/PS housing – cover seal/gasket and electrical packing gland. In the Exia version, the user may replace only the terminal block with angled cover and the seal in the PD connector, or the seal and packing gland in the PZ/PS housing version Replacement or repair of any other parts should not be carried out by anyone other than the...
  • Page 14: Electrical Connection. Settings

    Storage and transport as above. 14. GUARANTEE 14.1 The manufacturer guarantees the correction functioning of the PYRP-28 pressure and PYRD-28 differential pressure transmitters for a period of 24 months from the date of purchase and servicing, the specific details being as stated in the product warranty supplied with the goods.
  • Page 15: Figures (Diagrams)

    5.4.1. PM12 cable connector IP67 rated cable as in connector PK diag. 1c or 1d Fig.1f. PCE-28 transmitter with PM12 connector Figure 1. PYRP-28 transmitter with PD, PK and PM12 connectors: dimensions and methods of connection.
  • Page 16 Terminals designation to: 0 ... 20mA and 0 ... 10V output signals: Terminal 1 - Supply "+" (plus) Terminal 2 - Output signal Terminal 3 - Supply "-" (minus) Figure 2. PYRP-28 transmitter with PZ connector: dimensions and connection method.
  • Page 17 DTR.PYRP.PYRD.PYRL-28 Fig.3a. M connection Fig.3b. Socket for M connection. with M20x1.5 thread min.15 diaphragm seal Fig.4a. P connection Fig.4b. Socket for P connection with M20x1.5 thread min.15 diaphragm seal Fig.5a. T connection Fig.5b. Socket for Fig.5c. Weldable fitting ring for with flush diaphragm T connection T connection...
  • Page 18 DTR.PYRP.PYRD.PYRL-28 24,5 -0.5 14,5 min. Fig.6a. GB connection Fig.6b. Socket for GB connection. with G1/2" thread 21,5 -0,2 min.10,5 Sealing: teflon 21,2 x 24,4 x 1,7 O-ring 15x2 20,5 -0,1 27-6kt. Fig.6c. GF connection Fig.6d. Weldable fitting ring for with flush diaphragm GF connection with G1/2"...
  • Page 19 DTR.PYRP.PYRD.PYRL-28 Figure 7. PYRD-28 differential pressure transmitter with PD, PK connectors.  PRE-28 transmitter PRE-28 transmitter PYRD-28 transmitter PYRD-28 transmitter with PK connector for with PK connector with PK connector with PK connector output signal 4…20mA. (three-wire transmission for output signal 4...20mA (three-wire transmission 0…10V or 0…20mA).
  • Page 20 DTR.PYRP.PYRD.PYRL-28  M20x1,5 packing gland   PZ connector IP66 M10 or 7/16" UNF 4 holes Figure 8. PYRD-28 differential pressure transmitter with C process connection to be mounted together with valve manifold.
  • Page 21 DTR.PYRP.PYRD.PYRL-28 PD connector as in fig. 1b or PK connector as in fig. 1c or 1d connection as in fig. 1a. vent (in Ex version)  Optional steel clasp for mounting in hermetic tanks.     Optional movable clasp for mounting ...
  • Page 22 DTR.PYRP.PYRD.PYRL-28  L= 50, 100, 150, 200 Figure 10. PYRD-28 differential pressure transmitter with a single direct diaphragm seal...
  • Page 23 DTR.PYRP.PYRD.PYRL-28 34.5 Pipe 25 Bracket assembly code BC for fitting differential pressure transmitters. with P-type connector on a Ø25 pipe Figure 11. Example: how to install the PYRD-28.
  • Page 24 DTR.PYRP.PYRD.PYRL-28 Fastener BCZ or BCS for fitting differential pressure transmitters with C-type connection to a 2” pipe or to a wall. See valves and fitting assemblies literature. Figure 12. Example: how to install the PYRD-28 transmitter on a vertical or horizontal pipe.
  • Page 25 DTR.PYRP.PYRD.PYRL-28 BU Mounting bracket made from 3 mm metal sheet, for mounting the valve manifold.   Figure 13. Example: how to install the PYRD-28 transmitter with a valve manifold to a wall...
  • Page 26 DTR.PYRP.PYRD.PYRL-28 Looped siphon tube (available from Pyropress). Recommended when measuring vapour pressure. Fitted vertically. Threaded pipe stub (available from Pyropress) recommended when measuring liquid pressure. Fitted vertically (medium temp. to 140°C) or horizontally (medium temp. to 180°C). Figure 14. Possible methods of isolating the transmitter from high temperatures...
  • Page 27 DTR.PYRP.PYRD.PYRL-28 M20x1,5 or G1/2" Moving M20x1,5 or G1/2" Moving Weldable pipe stub 100 Bar max. Marerial:ST3S galvanised steel Ordering code: PS-M 2 0 o r PS-G1 /2 " M20x1,5 G1/2" Siphon tube  100 Bar  max. 300°C Weld connector Temp.
  • Page 28: Appendix 01 (For Intrinsically Safe Atex Certified Versions)

    APPENDIX 01 DTR.PYRP.PYRD.PYRL-28 0359 PYRP–28IS, PYRL–28IS AND PYRD–28IS PRESSURE/LEVEL/DIFFERENTIAL PRESSURE TRANSMITTERS - ATEX INTRINSICALLY SAFE CERTIFIED VERSIONS. 1. Introduction 1.1. This appendix applies to ATEX certified Intrinsically Safe Transmitters Type PYRP-28IS/XX/YY, PYRL-28IS/XX/YY and PYRD-28IS/XX/YY. 1.2. The appendix contains supplementary information relating to the Exia version transmitters. During installation and use of the Exia transmitters, reference should be made to DTR.PYRP.PYRD.PYRL-28 in conjunction with “Appendix 01”.
  • Page 29 - for power supply with a linear characteristic Ui = 28V DC; Ii = 0,1A; Pi=0,7W - for power supply with a “trapezial” and “rectangular” characteristic Ui = 24V DC; Ii = 0,1A; Pi=1,2W Input inductance and capacity: Ci = 25nF*, Li = 0,4mH* Ta =-40°C to …see Table Z1 *It should take into account the capacity and inductance of the cable which in permanently connected cables are: Ck= 0.2nF/m i Lk=1µH/m.
  • Page 30 Appendix 01 6. Supply examples 6.1.- For power supply with a linear characteristic Power supply with a “linear” characteristic may be e.g. a typical barrier with parameters Uo=28V Io=0.093A Rw=300Ω Fig.1. Power supply from a source with “linear” characteristic 6.2. - For power supply with a trapezial characteristic Supply parameters in accordance with the Exia certification: a) Uo=24V Io=0,08A Po=1,2W b) Uo=24V Io=0.05A Po=0,6W...
  • Page 31 Appendix 01 7. Connection of Exia transmitters: PYRP–28IS, PYRL–28IS and PYRD–28IS The transmitter and other devices in the measuring loop must be installed and electrically connected in accordance with the relevant applicable hazardous area installation requirements and standards. To measure the current in the transmitter without Hazardous area Safe area...