Isn-sm-xx series seismic detectors and accessories
Table of Contents

Advertisement

Quick Links

ISN-SM-xx
Seismic Detectors and Accessories
Application Guide

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ISN-SM-30 and is the answer not in the manual?

Questions and answers

Summary of Contents for Bosch ISN-SM-30

  • Page 1 ISN-SM-xx Seismic Detectors and Accessories Application Guide...
  • Page 2 Copyright Technical specifications and availability subject to change without notice. © Copyright Bosch Security Systems 2016 We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the sub- ject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.
  • Page 3: Table Of Contents

    Calculating the number of detectors required - Example 1 ....33 6.1.2 Calculating the number of detectors required - Example 2 ....34 6.1.3 Calculating the number of detectors required – Example 3 ....36 Modular vaults ....................37 Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 4 10.5 Graphic Index ..................... 63 10.6 Table Index ......................64 Appendix 1: Drill template ISN-SM-xx ............65 Appendix 2: Drill Template GMXP3/Z ............. 66 Appendix 3: Drill Template GMXS5 ..............67 Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 5: General Information

    General information General information The Bosch Security Systems ISN-SM-xx range of seismic detectors has been the market leader in seismic detection for more than 20 years. Bosch Security Systems detectors are designed to detect and report any attempt to compromise the integrity of any type of high value storage unit.
  • Page 6: Detector And Accessory Overview

    General information Detector and accessory overview Additional information relating to the Bosch Security Systems Seismic range of detectors and acces- sories is available on www.spiap.com. Figure 1-2: Detector and accessory overview Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 7: Applications

    Applications Applications The Bosch Security Systems ISN-SM-xx range of seismic detectors offers detection solutions with a wide range of applications. Detector applications and attack profiles The following table shows some of the more common applications for the detectors: Applications Attack Types grouped by amplitude profile Financial –...
  • Page 8: Detector Selection

    Table 2-2: Applications and recommended detectors LWS Light Weight Safes can be constructed from a range of different composite materials. Bosch Security Systems recommend that on-site tests are performed to ascertain the correct number of detectors required for each LWS application.
  • Page 9: Steel Applications And Accessory Options

    Additional Protection Anti-drill foil GMXD7 Cable Access Plastic/Metal Conduit GMXC2 Table 2-4: Concrete applications and accessories The GMXP0 Mounting plate is a mandatory accessory when surface mounting a detector on con- crete. Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 10: Installation - Detectors

    There is a 1:1 scale copy of the drill template located in Appendix 1: Drill template ISN-SM-xx. The drill templates are also available as a download from the Bosch Security Systems Seismic micro- site on SPIAP.
  • Page 11: Detector Installation On Steel Using The Gmxp0 Mounting Plate

    3.4.1 Weld fixing Bosch Security Systems recommend weld fixing the GMXP0 mounting plate directly on to the clean, paint-free area of the protected surface. This option provides the best acoustic coupling for the detec- tion of vibration signals.
  • Page 12: Screw Fixing

    Before fixing the mounting plate to the protected surface, it is important to consider cable access to the detector. If necessary, rotate the mounting plate to the correct orientation to give cable access to the detector. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 13: Glue Fixing

    The recommended option for installation is to drill or weld the GMXP0 to the protected surface and to follow the installa- tion guides throughout this document and the associated installation sheets. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 14: Indirect Installation On Concrete

    Use the ISN-SM-xx drill template (supplied with the detector) to correctly locate the cable access for the detector and to locate the drill holes for the GMXP0 mounting plate detector and for the GMXS1 test transmitter (if required). Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 15 It is essential that the GMXS1 test transmitter is secured directly to the concrete and that it does not make contact with the GMXP0 or the detector. This is to ensure that the correct test signal is applied to the protected surface when the GMXS1 is activated. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 16 3. Use the M6 x 47mm screw to secure the GMXP0 to the steel expansion plug. 4. Use the M4 x 21mm screw to secure the GMXS1 to the brass expansion plug. 5. Mount the ISN-SM-xx detector on to the GMXP0. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 17: Installation - Accessories

    GMXS1 is determined by the drill template or the mounting plate. In both cases, the GMXS1 is located under the cover of the ISN-SM-xx detector. The GMXS1 may be used for both steel and concrete applications. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 18 When selecting the Active high option, it is essential to connect a permanent 0v to avoid unwanted alarms. To activate, remove the 0v. The input selection is only available through SensTool. GMXS1 internal test transmitter Figure 4-4: ISN-SM-xx detector with GMXS1 Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 19: Gmxs5 - External Test Transmitter

    See Figure 4-8: Activate 4 detectors from a single GMXS5 for more information. Figure 4-6: GMXS5 Electrical connections Figure 4-6 shows the electrical connection for the device, 12 VDC, tamper (Sabo) contacts and a selectable switched input are the available connections. Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 20 Figure 4-8: Activate 4 detectors from a single GMXS5 Figure 4-8: Activate 4 detectors from a single GMXS5 is a typical example of how to activate multi- ple detectors from a single GMXS5. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 21 Figure 4-10 is an example of how to activate multiple detectors from a single GMXS5. Material Detector Effective Transmission Diameter of the GMXS5 Concrete ISN-SM-90 Steel ISN-SM-90 Concrete ISN-SM-80 Steel ISN-SM-80 Concrete ISN-SM-50 Steel ISN-SM-50 Steel ISN-SM-30 Table 4-1: GMXS5 transmission diameters Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 22: Gmxw0 Wall Mounting Kit

    The mould must be fully removed to reveal the mounting plate and the conduit access points to the left and right hand sides. The mounting plate contains pre-drilled and tapped M4 mounting holes for the detector and for the GMXS1 test transmitter. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 23: Gmxb0 Floor Box

    There are pre-drilled and tapped M4 mounting holes for the detector and the GMXS1 test transmit- ter. The GMXB0 has pre-formed conduit access holes to enable the cables to be securely offered to the device through the concrete. Figure 4-13: GMXB0 installed Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 24: Gmxp3 & Gmxp3Z Lock Protection System

    Refer to installation sheet for the GMXP3 for details of the accessories required for the swivel arm clearance distance. GMAS6 movable mounting kit The GMAS6 movable mounting kit is used in conjunction with seismic detectors on safe and strong room doors with flush-fitting keyholes. Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 25 When the system is armed, the seismic detector also detects unauthorized opening, thermal at- tacks, and mechanical attacks. As the cable for the detector is exposed and will be subject to constant movement, then a form of mechanical cable protection should be considered. Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 26: Gmxd7

    SensTool is supplied as a CD and a serial port to special USB connection lead. The software can also be used as a fault-finding guide. See Section 8 SensTool for more infor- mation. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 27: Gmxc2 Conduit Connection Cover

    Adjacent = within 25mm of the detector, placed upon a clean surface (no paint, grease or other for- eign bodies to impair the signal). If the surface is painted, then the tool must be placed upon the GMXP0, if installed. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 28: Planning

    In the sections below, are guides in what conditions to avoid. In addition to this, it is essential that the correct installation practices are followed and only Bosch Se- curity Systems accessories, detailed in section 3 are used to compliment the system.
  • Page 29: Installation Guidelines

    Bosch Security Systems recommend that planners create their own version of these tables and insert the relevant information under the headings in these tables to assist with planning and as a means of recording all of the salient information.
  • Page 30 Electrical cupboard board ground (default) ground floor floor Expander # 3 (Zones 25 Electrical riser, Dual 4K7 PSU # 3 Electrical riser, base- – 32) basement (default) ment Table 5-2: System requirements Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 31: Design

    The formula to determine the spacing distance for seismic detectors to provide a comprehensive detection coverage of the protected surface is: Spacing distance (sd) = operating radius(r) x 2 x 0.75 Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 32 Detection radius (r) set at 2.5m, assuming the centre of the wall height is the mounting location for the seismic detectors. d1 & d2 = 2m Sum of d1 & d2 = 4m sd = 2.5 x 2 x 0.75 =3.75m Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 33: Calculating The Number Of Detectors Required - Example 1

    For the example detailed in Table 6-1 using two detectors at the calculated locations provides the minimum detection that is sufficient to provide coverage for the wall. For maximum performance and efficient coverage Bosch Security Systems recommend a more balanced layout using 3 detec- tors.
  • Page 34: Calculating The Number Of Detectors Required - Example 2

    In this example, the distance d1 plus the sd distance does not provide the required detection cov- erage. If a second sd spacing is used, coverage would be adequate but not balanced. Figure 6-6: Example 2 - unbalanced coverage Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 35 To balance a system design, the distances d1, d2 & sd may be reduced but never in- creased. Figure 6-7: Example 2 - balanced coverage Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 36: Calculating The Number Of Detectors Required - Example 3

    To balance a system design, the distances d1, d2 & sd may be reduced but never in- creased. Figure 6-9: Example 3 - detector spacing with balanced coverage Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 37: Modular Vaults

    For more information on installation method and on the mandatory and optional accessories, see Section 2 Applications. 6.2.1 Interlocking panels Figure 6-11: Modular vault - interlocking panel construction Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 38: Panels With Steel Surrounds

    Always equip modules which have a pay-in/withdrawal slot with a detector; this will also be able to monitor the adjacent modules. As construction methods of vaults may vary, the transfer of detection radius from one surface to an adjacent surface should not form part of any calculation. Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 39: Vault Protection Guidelines

    Figure 6-14 shows the the detectors that are mounted inside the vault in white (for example B1, B2, A2). The test transmitters, detector, and lock protection system that are mounted externally to the vault are shown in grey (for example A1, E3). Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 40 Figure 6-16: Example 2 - detector layout and external devices Figure 6-17 shows the detector location and the detection radius for each detector. This is an ex- ample to demonstrate that each surface of the vault has comprehensive detection coverage. The Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 41 Ceiling (B) ISN-SM-90 - 3 5m concrete GMXP0 GMXS1 ISN-SM-90 - 4 5m concrete GMXP0 GMXS1 Right hand wall ISN-SM-90 - 5 5m concrete GMXW0 GMXS5 ISN-SM-90 - 6 5m concrete GMXW0 Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 42: Night Deposit Box And Atm Applications

    Door wall (A) ISN-SM-90 – 10 5m concrete GMXW0 GMXS1 Door in wall (A) ISN-SM-30 - 11 2m steel GMXP3 GMXS1 Table 6-4: Overview of complete vault installation Not all of the detection radius options are available via the DIP switches. SensTool must be used to access of a full set of options.
  • Page 43: Atm's

    Externally on the door Secure or public area? of the unit If installed in a public area, Bosch Security Systems recommend the use of the GMXD7 anti-drill foil for increased protection. Consider the mounting height. Ideally, mount the detector above the nor- mal hazards such as shopping trolleys, baby buggies, cleaning equip- ment, and any other hazard that may be site/location specific.
  • Page 44: Detector Sensitivity

    The construction of ATM’s and night safes can involve layers of different materials, which could be steel/concrete/steel. This adds additional protection from drill attacks but provides challenges to the installation of the seismic detectors & ancillary devices to the enclosure. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 45: Cabinet Protection

    A single ISN-SM-xx detector mounted internally provides adequate coverage for most document cabinets. Figure 6-21: Document cabinet shows a suggested installation of a detector mounted in- ternally to the top of the document cabinet. Figure 6-21: Document cabinet Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 46: Filing Cabinet

    Consider the accessories GMXP3, GMXP3Z & GMAS-6 for lock protec- tion and additional security. Figure 6-23: Gun cabinet shows a suggested installation of a detector mounted internally to the top of the gun cabinet. Figure 6-23: Gun cabinet Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 47: Commissioning

    After about 30 seconds the detector signals an alarm condition. The ISN-SM-50, ISN-SM-80 & ISN-SM-90 confirm an alarm by opening the alarm contact and illuminating the internal LED. The ISN-SM-30 will only open alarm contacts. Using a small metal plate to protect the surface, repeatedly hit the Integration metal plate, leaving 2 second intervals, with a small hammer.
  • Page 48: Staged Commissioning

    The internal LED will pulse for 10 seconds to confirm that the correct power is applied. The LED is not available on the ISN-SM-30 version. 2. Verify that the correct detection radius and material type are selected via the DIP switches or use the SensTool, if available to select.
  • Page 49 2.7v DC level as confirmation. The recommended method of recording and verifying the tests is to use the GMXD7 SensTool. See Section 8 SensTool for additional information. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 50: Senstool

    Senstool is an essential part of the successful configuration of the ISN-SM-xx seismic detectors. Note that the ISN-SM-30 does not have Senstool connectivity. It is strongly recommended that SensTool is used for the configuration and commissioning of the ISN-SM-xx seismic detectors. Certain configura- tion options are only available from SensTool, such as digital filters, temperature adjustment &...
  • Page 51: Recording Ambient Noise Levels

    12.5% of the original setting. Local regulations will determine if this is a permissible option. Figure 8-2: SensTool detector signal Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 52: Trouble Shooting

    Identify the source and take appropri- ate action to prevent Temperature Check the high and low settings of the de- Use SensTool and adjust if required. Alarm present tectors. Check ambient temperature of the local area. Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 53: Using Senstool As A Record Of Commissioning

    Note that this event memory is only available in the ISN-SM-80 and ISN-SM-90 detectors. Figure 8-3: SensTool event memory In addition to the record of testing and the configuration of the actual detector settings complete with any associated guidance notes. Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 54: Interface To Spc Panel/System

    There are a number of different connection options for the monitoring of the seismic detectors available from the SPC system. Bosch Security Systems recommend that the dual end of line op- tions are selected, as they provide the most comprehensive coverage and reporting.
  • Page 55: Testing The Detectors

    The time required for the actual test for 50 detectors would be 1-2 seconds and the lower time lim- its should be used in preference to the upper limits. The automatic seismic test is not dependent upon the set condition of the system but operates differently for either option. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 56: Automatic Test When Setting

    With the unrestricted mode selected in the SPC panel, system testing can be a combina- tion of automatic test and automatic test when setting. In this case, all seismic detectors are tested each time the system is set. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 57: Test And Indication Flow

     If the test fails, the message ‘SEISMIC FAIL’ is displayed. If the “i” or VIEW key is pressed, a scrollable list of the failed zones is displayed.  If the test succeeds, ‘SEISMIC OK’ is displayed. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 58: Useful Information

    Useful information 10.1 Cross-reference chart for country-specific approvals Product Comment ISN-SM-30 Seismic detector CCC, UL, RCM, PD6662, CE, EAC ISN-SM-50 Seismic detector CE, CCC, UL, RCM, PD6662, CNPP, IMQ, IN- CERT, MABISZ, NBU, PIE, SBSC, VdS, VSÖ, F&P, REQ, EAC...
  • Page 59: Cross Reference Chart For All Related Internal Documentation

    Data sheet V54534-F114-A100_ISN-SM- 90LSNi_023_01_en GM780LSN Install sheet 022-GM780LSN_A6V10314908_d Data sheet V54534-F116-A100_GM780LSN_023_01_en GMXP0 Install sheet Data sheet Bosch Security Systems - Seis- mic_Range_of_Accessories GMXS1 Install sheet 020_GMXS1_686_g Data sheet Bosch Security Systems - Seis- mic_Range_of_Accessories GMXS5 Install sheet 020_GMXS5_004707_e Data sheet...
  • Page 60 Useful information Doc Ref Product Reference Description Data sheet Bosch Security Systems - Seis- mic_Range_of_Accessories GMXC2 Install sheet Data sheet Bosch Security Systems - Seis- mic_Range_of_Accessories GMXS2 Install sheet Data sheet Bosch Security Systems - Seis- mic_Range_of_Accessories GMXS4 Install sheet...
  • Page 61: Cross Reference Chart For Applicable, External Related Documents

    GMAS6 Movable mounting kit – ISN-SM-xx VBPZ:4886060001 GMXD7 Anti-drill foil (10x) – ISN-SM- VA5Q00006245 50/760/775 GMSW7 SensTool-SW – ISN-SM-50/760/775 VA5Q00006245 GMYA7-AS Remote testing system V54534-F101-A100 GMYA7-A Alarm for indicator module V54534-F102-A100 Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 62 Useful information Product code Description Article number GMXC2 Connection sleeve (16mm) – ISN-SM- VBPZ:5021840001 GMXS2 2mm spacer VBPZ:3506110001 GMXS4 4mm spacer VBPZ:3506240001 GMXC4 Test tool Table 10-4: Part numbers Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 63: Graphic Index

    Figure 6-12: Modular vault - panels with steel surrounds ..................38 Figure 6-13: Vault protection system - example 1 ....................39 Figure 6-14: Vault protection system - example 2 ....................39 Figure 6-15: Example 2 - detectors inside vault ....................40 Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 64: Table Index

    Table 9-2: Automatic seismic test .......................... 56 Table 10-1: Country Specific Approvals ........................ 58 Table 10-2: Related documentation – internal ...................... 61 Table 10-3: Related documentation - external ...................... 61 Table 10-4: Part numbers ............................62 Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 65: Appendix 1: Drill Template Isn-Sm-Xx

    Printer settings must be optimized to reproduce at actual size. While every effort has been made to ensure accurate sizing, the templates in this docu- ment must be checked before use to ensure that the dimensions are correct. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 66: Appendix 2: Drill Template Gmxp3/Z

    Printer settings must be optimized to reproduce at actual size. While every effort has been made to ensure accurate sizing, the templates in this docu- ment must be checked before use to ensure that the dimensions are correct. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 67: Appendix 3: Drill Template Gmxs5

    Printer settings must be optimized to reproduce at actual size. While every effort has been made to ensure accurate sizing, the templates in this docu- ment must be checked before use to ensure that the dimensions are correct. Bosch Security Systems Seismic Detectors Application Guide I-200153-1...
  • Page 68 Appendix 3: Drill Template GMXS5 Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...
  • Page 69 Issued by © Bosch Security Systems, 2016 Bosch Security Systems Technical specifications and availability subject to change without notice. 130 Perinton Parkway Fairport, NY 14450 www.boschsecurity.com Bosch Security Systems Seismic Detectors Application Guide I-200153-1 04.2016...