EMERGENCY POWER SUPPLY
POWER SUPPLY FRAME
POWER SUPPLY UNIT
Power supply equipment for fire detection and fire alarm systems for buildings
(Does not apply to VX-2000DS SA and VX-200PS SA)
Thank you for purchasing TOA's Emergency Power Supply, Power Supply Frame, and Power Supply
Unit.
Please carefully follow the instructions in this manual to ensure long, trouble-free use of your equipment.
All manuals and user guides at all-guides.com
1134
TOA Electronics Europe GmbH
Suederstrasse 282, 20537 Hamburg, Germany
1134-CPR-083
14
DoP 1134-CPD-083
EN 54-4: 1997/A1: 2002 + A2: 2006
VX-2000DS ER/UK, VX-200PS ER/UK
INSTRUCTION MANUAL
VX-2000DS ER
VX-2000DS UK
VX-2000DS SA
VX-2000PF
VX-200PS ER
VX-200PS UK
VX-200PS SA

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VX-2000DS ER and is the answer not in the manual?

Questions and answers

Summary of Contents for Toa VX-2000DS ER

  • Page 1 VX-2000DS ER/UK, VX-200PS ER/UK (Does not apply to VX-2000DS SA and VX-200PS SA) Thank you for purchasing TOA's Emergency Power Supply, Power Supply Frame, and Power Supply Unit. Please carefully follow the instructions in this manual to ensure long, trouble-free use of your equipment.
  • Page 1 VX-2000DS ER/UK, VX-200PS ER/UK (Does not apply to VX-2000DS SA and VX-200PS SA) Thank you for purchasing TOA's Emergency Power Supply, Power Supply Frame, and Power Supply Unit. Please carefully follow the instructions in this manual to ensure long, trouble-free use of your equipment.
  • Page 2: Table Of Contents

    All manuals and user guides at all-guides.com TABLE OF CONTENTS 1. SAFETY PRECAUTIONS ................. 3 2. NOMENCLATURE AND FUNCTIONS 2.1. VX-2000DS Emergency Power Supply .............. 5 2.2. VX-200PS Power Supply Unit ................7 2.3. VX-2000PF Power Supply Frame ..............8 3.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS 1. SAFETY PRECAUTIONS ................. 3 2. NOMENCLATURE AND FUNCTIONS 2.1. VX-2000DS Emergency Power Supply .............. 5 2.2. VX-200PS Power Supply Unit ................7 2.3. VX-2000PF Power Supply Frame ..............8 3. INSTALLATION 3.1. Assembling the VX-2000PF Power Supply Frame ..........9 3.2.
  • Page 3: Safety Precautions

    • Should the following irregularity be found during use, immediately switch off the main power (or circuit breaker), and contact your nearest TOA dealer. Make no further attempt to operate the unit in this condition as this may cause fire or electric shock.
  • Page 3: Safety Precautions

    • Should the following irregularity be found during use, immediately switch off the main power (or circuit breaker), and contact your nearest TOA dealer. Make no further attempt to operate the unit in this condition as this may cause fire or electric shock.
  • Page 4 · Avoid locations exposed to the direct sunlight, high temperature and high humidity when storing batteries. • (Applicable to VX-200PS only) Contact your TOA dealer as to the cleaning. If dust is allowed to accumulate in the unit over a long period of time, a fire or damage to the unit may result.
  • Page 4 · Avoid locations exposed to the direct sunlight, high temperature and high humidity when storing batteries. • (Applicable to VX-200PS only) Contact your TOA dealer as to the cleaning. If dust is allowed to accumulate in the unit over a long period of time, a fire or damage to the unit may result.
  • Page 5: Nomenclature And Functions

    • Automatically switches to the backup power supply when the DC power supply from the VX-200PS is interrupted. • Detects charging circuitry or battery failures, and transmits failure signals to the DS LINK of the TOA Voice Evacuation Systems (VX-2000, SX-2000, and VM-3000).
  • Page 5: Nomenclature And Functions

    • Automatically switches to the backup power supply when the DC power supply from the VX-200PS is interrupted. • Detects charging circuitry or battery failures, and transmits failure signals to the DS LINK of the TOA Voice Evacuation Systems (VX-2000, SX-2000, and VM-3000).
  • Page 6 All manuals and user guides at all-guides.com 1. Power indicator [MAIN POWER] 8. PS detect switches Lights green when both DC power from the VX- Always connect a power supply to the terminals 200PS and AC power are supplied. 1 + 2 of the DC INPUT. When connecting a power supply to the terminals 3 + 4 of the DC 2.
  • Page 6 1. Power indicator [MAIN POWER] 8. PS detect switches Lights green when both DC power from the VX- Always connect a power supply to the terminals 200PS and AC power are supplied. 1 + 2 of the DC INPUT. When connecting a power supply to the terminals 3 + 4 of the DC 2.
  • Page 7: Vx-200Ps Power Supply Unit

    All manuals and user guides at all-guides.com [Fault indication] If any of the Power indicator [MAIN POWER], Battery connect indicator [BATTERY CONNECT], Charging indicator [CHARGING], or Battery check indicator [BATTERY CHECK] on the front panel remains unlit, the unit is judged failed. In such cases, remove the cause of the failure, and restore the unit to normal operation. Note Even if any of these indicators flashes, this does not indicate malfunction.
  • Page 7: Vx-200Ps Power Supply Unit

    [Fault indication] If any of the Power indicator [MAIN POWER], Battery connect indicator [BATTERY CONNECT], Charging indicator [CHARGING], or Battery check indicator [BATTERY CHECK] on the front panel remains unlit, the unit is judged failed. In such cases, remove the cause of the failure, and restore the unit to normal operation. Note Even if any of these indicators flashes, this does not indicate malfunction.
  • Page 8: Vx-2000Pf Power Supply Frame

    All manuals and user guides at all-guides.com 2.3. VX-2000PF Power Supply Frame The VX-2000PF permits the VX-200PS Power Supply to be mounted in an equipment rack. Up to 3 VX-200PS units can be installed in the VX-2000PF. Refer to p. 10 for the VX-200PS mounting procedure.
  • Page 8: Vx-2000Pf Power Supply Frame

    2.3. VX-2000PF Power Supply Frame The VX-2000PF permits the VX-200PS Power Supply to be mounted in an equipment rack. Up to 3 VX-200PS units can be installed in the VX-2000PF. Refer to p. 10 for the VX-200PS mounting procedure. [VX-2000PF Components] This unit is comprised of the following components.
  • Page 9: Installation

    All manuals and user guides at all-guides.com 3. INSTALLATION 3.1. Assembling the VX-2000PF Power Supply Frame Self-tapping screw 4 x 10 (supplied with the VX-2000PF) Chassis Side panel Side panel Fixing bracket Front panel Note: Mount the front panel and fixing bracket after installing the VX-200PS units on the chassis. [Installation Precautions] The VX-2000PF and VX-200PS units are slightly different in specifications between the previous and current production lots.
  • Page 9: Installation

    3. INSTALLATION 3.1. Assembling the VX-2000PF Power Supply Frame Self-tapping screw 4 x 10 (supplied with the VX-2000PF) Chassis Side panel Side panel Fixing bracket Front panel Note: Mount the front panel and fixing bracket after installing the VX-200PS units on the chassis. [Installation Precautions] The VX-2000PF and VX-200PS units are slightly different in specifications between the previous and current production lots.
  • Page 10: Installing The Vx-200Ps Power Supply Unit In The Vx-2000Pf

    All manuals and user guides at all-guides.com 3.2. Installing the VX-200PS Power Supply Unit in the VX-2000PF To be compliant with EN 54-4, install the VX-2000DS and VX-2000PF in the CR cabinet rack series CR-15, CR-22, CR-27, CR-35, CR-40, and CR-44. Step 1.
  • Page 10: Installing The Vx-200Ps Power Supply Unit In The Vx-2000Pf

    3.2. Installing the VX-200PS Power Supply Unit in the VX-2000PF To be compliant with EN 54-4, install the VX-2000DS and VX-2000PF in the CR cabinet rack series CR-15, CR-22, CR-27, CR-35, CR-40, and CR-44. Step 1. Mount the VX-2000PF in an equipment rack. Step 2.
  • Page 11: Battery Installation

    All manuals and user guides at all-guides.com 3.3. Battery Installation WARNING • Take special care to prevent the battery from being shorted by misconnection of the battery cable. If the short occurs, the unit may fail. Follow the instructions in this section for safe and secure connection. •...
  • Page 11: Battery Installation

    3.3. Battery Installation WARNING • Take special care to prevent the battery from being shorted by misconnection of the battery cable. If the short occurs, the unit may fail. Follow the instructions in this section for safe and secure connection. •...
  • Page 12 All manuals and user guides at all-guides.com Correct Incorrect • Strip the cable end long enough (30 mm ± 5 mm) to be fully clamped. Otherwise, its outer jacket prevents the cable conductor from being tightly secured, causing poor contact. [Attaching the insulating sheet] To prevent the battery cable from being shorted to the rear panel due to misconnection, attach the supplied insulating sheet in place following the procedures below.
  • Page 12 Correct Incorrect • Strip the cable end long enough (30 mm ± 5 mm) to be fully clamped. Otherwise, its outer jacket prevents the cable conductor from being tightly secured, causing poor contact. [Attaching the insulating sheet] To prevent the battery cable from being shorted to the rear panel due to misconnection, attach the supplied insulating sheet in place following the procedures below.
  • Page 13 All manuals and user guides at all-guides.com • Use the battery connection cables as short in length and as large in diameter as possible. VX-2000DS BATTERY POWER IN DC POWER OUT (+) MAX 25A (DC 20V-40V) PS IN ( ) MAX 25A (DC20V-40V) DETECT(VX-200PS) MAX150A PS IN...
  • Page 13 • Use the battery connection cables as short in length and as large in diameter as possible. VX-2000DS BATTERY POWER IN DC POWER OUT (+) MAX 25A (DC 20V-40V) PS IN ( ) MAX 25A (DC20V-40V) DETECT(VX-200PS) MAX150A PS IN 1,2:PS1 3,4:PS2 ON OFF...
  • Page 14 All manuals and user guides at all-guides.com [Disconnecting the Battery] Step 1. Confirm that battery power is not in use by means of the VX-2000DS' front-mounted BATTERY POWER LED, which is unlit in this case. Step 2. Loosen the VX-2000DS' BATTERY POWER IN negative terminal screw, then pull out the negative battery cable.
  • Page 14 [Disconnecting the Battery] Step 1. Confirm that battery power is not in use by means of the VX-2000DS' front-mounted BATTERY POWER LED, which is unlit in this case. Step 2. Loosen the VX-2000DS' BATTERY POWER IN negative terminal screw, then pull out the negative battery cable.
  • Page 15: Affixing Declaration Of Compliance (En 54-4 Standard)

    (supplied with the VX-2000DS) When replacing the batteries, 4 each of fastener hooks and loops, and a thermal insulating sheet listed below are also required. Consult your nearest TOA dealer on how you can obtain them. Part code Part name...
  • Page 15: Affixing Declaration Of Compliance (En 54-4 Standard)

    (supplied with the VX-2000DS) When replacing the batteries, 4 each of fastener hooks and loops, and a thermal insulating sheet listed below are also required. Consult your nearest TOA dealer on how you can obtain them. Part code Part name...
  • Page 16: Connections When Using With The Vx-2000 System

    All manuals and user guides at all-guides.com 4. CONNECTIONS WHEN USING WITH THE VX-2000 SYSTEM 4.1. Connections between VX-2000DS and VX-200PS (–) VX-200PS VX-200PS VX-200PS – – – – – – PS OUT PS OUT PS OUT 230 V AC 230 V AC 230 V AC 220 V AC...
  • Page 16: Connections When Using With The Vx-2000 System

    4. CONNECTIONS WHEN USING WITH THE VX-2000 SYSTEM 4.1. Connections between VX-2000DS and VX-200PS (–) VX-200PS VX-200PS VX-200PS – – – – – – PS OUT PS OUT PS OUT 230 V AC 230 V AC 230 V AC 220 V AC 220 V AC 220 V AC 50/60 Hz...
  • Page 17: Connecting The Vx-2000Ds To Vx-2000 System

    All manuals and user guides at all-guides.com 4.2. Connecting the VX-2000DS to VX-2000 System VX-2000 AUDIO LINK DATA LINK From VX-2000DS (–) DC POWER IN VX-2000SF DS-SF LINK From VX-2000DS (–) DC POWER IN VP-2064, VP-2122, VP-2241, or VP-2421 DC POWER IN 28 V 4.8 A PA OUT (SP LINE)
  • Page 17: Connecting The Vx-2000Ds To Vx-2000 System

    4.2. Connecting the VX-2000DS to VX-2000 System VX-2000 AUDIO LINK DATA LINK From VX-2000DS (–) DC POWER IN VX-2000SF DS-SF LINK From VX-2000DS (–) DC POWER IN VP-2064, VP-2122, VP-2241, or VP-2421 DC POWER IN 28 V 4.8 A PA OUT (SP LINE) From VX-2000DS (–) VP-2064, VP-2122, VP-2241, or VP-2421...
  • Page 18: Connections When Using With The Sx-2000 System

    All manuals and user guides at all-guides.com 5. CONNECTIONS WHEN USING WITH THE SX-2000 SYSTEM 5.1. Connections between VX-2000DS and VX-200PS (–) VX-200PS VX-200PS VX-200PS – – – – – – PS OUT PS OUT PS OUT 230 V AC 230 V AC 230 V AC 220 V AC...
  • Page 18: Connections When Using With The Sx-2000 System

    5. CONNECTIONS WHEN USING WITH THE SX-2000 SYSTEM 5.1. Connections between VX-2000DS and VX-200PS (–) VX-200PS VX-200PS VX-200PS – – – – – – PS OUT PS OUT PS OUT 230 V AC 230 V AC 230 V AC 220 V AC 220 V AC 220 V AC 50/60 Hz...
  • Page 19: Connecting The Vx-2000Ds To Sx-2000 System

    All manuals and user guides at all-guides.com 5.2. Connecting the VX-2000DS to SX-2000 System [When using a redundant power system*] In this connection example, 2 power supply units are used. Even if one of the 2 units fails or its power supply line is broken, power is still supplied from the other unit, preventing the system from going down.
  • Page 19: Connecting The Vx-2000Ds To Sx-2000 System

    5.2. Connecting the VX-2000DS to SX-2000 System [When using a redundant power system*] In this connection example, 2 power supply units are used. Even if one of the 2 units fails or its power supply line is broken, power is still supplied from the other unit, preventing the system from going down. * A method of connecting separate power sources to each power input or connecting the commercial power supply and backup power supply separately to each power input to prevent the system from going down when a cable is broken or power fails.
  • Page 20 All manuals and user guides at all-guides.com [When not using a redundant power system] Required power is supplied to the system from a single power supply unit. Connect the [+] terminal of Input A to the [+] terminal of Input B, and the [–] terminal of Input A to the [–] terminal of Input B. SX-2100AO or SX-2000AO 4P removable terminal plug (The figure below shows the SX-2100AO.)
  • Page 20 [When not using a redundant power system] Required power is supplied to the system from a single power supply unit. Connect the [+] terminal of Input A to the [+] terminal of Input B, and the [–] terminal of Input A to the [–] terminal of Input B. SX-2100AO or SX-2000AO 4P removable terminal plug (The figure below shows the SX-2100AO.)
  • Page 21: Ds Link Terminal Connections

    All manuals and user guides at all-guides.com 5.3. DS Link Terminal Connections Connect the DS-SF LINK terminal of the VX-2000DS to the DS Link terminal of the SX-2000SM or SX- 2100AO. The figure below shows a connection example when the VX-2000DS units are connected to the SX- 2100AO.
  • Page 21: Ds Link Terminal Connections

    5.3. DS Link Terminal Connections Connect the DS-SF LINK terminal of the VX-2000DS to the DS Link terminal of the SX-2000SM or SX- 2100AO. The figure below shows a connection example when the VX-2000DS units are connected to the SX- 2100AO.
  • Page 22: Connections When Using With The Vm-3000 System

    All manuals and user guides at all-guides.com 6. CONNECTIONS WHEN USING WITH THE VM-3000 SYSTEM Cable: AWG 10 – AWG 8 (–)(–)(+)(+) From VX-2000DS Note VM-3240VA/3360VA Remove the short bar attached at the factory. 230 V AC 220 V AC 50/60 Hz VP-2241 DC POWER IN...
  • Page 22: Connections When Using With The Vm-3000 System

    6. CONNECTIONS WHEN USING WITH THE VM-3000 SYSTEM Cable: AWG 10 – AWG 8 (–)(–)(+)(+) From VX-2000DS Note VM-3240VA/3360VA Remove the short bar attached at the factory. 230 V AC 220 V AC 50/60 Hz VP-2241 DC POWER IN 28 V 4.8 A PA OUT (SP LINE) PA LINK...
  • Page 23 All manuals and user guides at all-guides.com [Required number of VX-200PS and VX-2000DS units] The required number of the VX-2000DS Emergency Power Supply units and VX-200PS Power Supply Units are determined depending on the application of the system configured with the VM-3240VA, VM-3360VA, VM- 3240E, and VM-3360E (hereinafter called "VM amplifier"), and/or the VP-2241 and VP-2421 (hereinafter called "VP amplifier").
  • Page 23 [Required number of VX-200PS and VX-2000DS units] The required number of the VX-2000DS Emergency Power Supply units and VX-200PS Power Supply Units are determined depending on the application of the system configured with the VM-3240VA, VM-3360VA, VM- 3240E, and VM-3360E (hereinafter called "VM amplifier"), and/or the VP-2241 and VP-2421 (hereinafter called "VP amplifier").
  • Page 24 All manuals and user guides at all-guides.com System including one VP amplifier connected as a standby amplifier One VX-2000DS is required every 3 VM amplifiers. Number of VM amplifiers Number of VX-2000DS units Number of VX-200PS units Below is an example showing that 2 VX-2000DSs and 1 VX-200PS are used in a system including 4 VM amplifiers.
  • Page 24 System including one VP amplifier connected as a standby amplifier One VX-2000DS is required every 3 VM amplifiers. Number of VM amplifiers Number of VX-2000DS units Number of VX-200PS units Below is an example showing that 2 VX-2000DSs and 1 VX-200PS are used in a system including 4 VM amplifiers.
  • Page 25 All manuals and user guides at all-guides.com • Required number of VX-2000DS and VX-200PS units in a BGM/Paging system One each of the VX-2000DS and VX-200PS is required every 2 VM amplifiers. Number of VM amplifiers Number of VX-2000DS units Number of VX-200PS units Below is an example showing that 2 each of VX-2000DSs and VX-200PSs are used in a system including 3 VM amplifiers.
  • Page 25 • Required number of VX-2000DS and VX-200PS units in a BGM/Paging system One each of the VX-2000DS and VX-200PS is required every 2 VM amplifiers. Number of VM amplifiers Number of VX-2000DS units Number of VX-200PS units Below is an example showing that 2 each of VX-2000DSs and VX-200PSs are used in a system including 3 VM amplifiers.
  • Page 26: Cable Usage Table

    All manuals and user guides at all-guides.com 7. CABLE USAGE TABLE [VX-2000DS] Terminal to Connect Cable Type Equipment to be Connected to Terminal Equipment Terminal Equipment Plug Cable Type Plug Equipment Name Receptacle Name Receptacle AC IN 3P inlet – Supplied cable –...
  • Page 26: Cable Usage Table

    7. CABLE USAGE TABLE [VX-2000DS] Terminal to Connect Cable Type Equipment to be Connected to Terminal Equipment Terminal Equipment Plug Cable Type Plug Equipment Name Receptacle Name Receptacle AC IN 3P inlet – Supplied cable – – – 230 V AC, 50/60 Hz 220 V AC, 50/60 Hz DS-SF LINK RJ45 (female) RJ45 (male)
  • Page 27: Using The Vx-2000Ds Exclusively As A Backup Power Supply

    Setting switch Lead-acid Lead-acid Battery Battery Caution The charging current from VX-2000DS is 5 A maximum. Applicable Batteries: Panasonic LC-X1265PG/APG Note: Internal setting change is required. Leave this work to service personnel. Contact your TOA dealer.
  • Page 27: Using The Vx-2000Ds Exclusively As A Backup Power Supply

    Setting switch Lead-acid Lead-acid Battery Battery Caution The charging current from VX-2000DS is 5 A maximum. Applicable Batteries: Panasonic LC-X1265PG/APG Note: Internal setting change is required. Leave this work to service personnel. Contact your TOA dealer.
  • Page 28: Switching Off System Power (Dc)

    All manuals and user guides at all-guides.com 9. SWITCHING OFF SYSTEM POWER (DC) When the system power (DC) needs to be switched off in such cases as maintenance or unit configuration change, shift the Setting switch on the VX-2000DS to the "AC" position following the procedure below. [To switch off the system power] Step 1.
  • Page 28: Switching Off System Power (Dc)

    9. SWITCHING OFF SYSTEM POWER (DC) When the system power (DC) needs to be switched off in such cases as maintenance or unit configuration change, shift the Setting switch on the VX-2000DS to the "AC" position following the procedure below. [To switch off the system power] Step 1.
  • Page 29: Block Diagram

    All manuals and user guides at all-guides.com 10. BLOCK DIAGRAM Control Connector [DS-SF LINK] BATTERY DC Detect CONNECT Indicator DC Input [PS IN] (150 A max.) DC Input 1 Control Circuit DC Input 2 DC Input 3 DC Input 4 DC Input 5 DC Input 6 Battery Connection...
  • Page 29: Block Diagram

    10. BLOCK DIAGRAM Control Connector [DS-SF LINK] BATTERY DC Detect CONNECT Indicator DC Input [PS IN] (150 A max.) DC Input 1 DC Input 2 Control Circuit DC Input 3 DC Input 4 DC Input 5 DC Input 6 Battery Connection Terminal [BATTERY POWER IN] Fuse...
  • Page 30: Specifications

    All manuals and user guides at all-guides.com 11. SPECIFICATIONS 11.1. VX-2000DS Emergency Power Supply Power Source 230 V AC (ER/UK), 220 – 230 V AC (SA), 50/60 Hz Power Consumption 240 W max. Applicable Battery Panasonic LC-X1265PG/APG (65 Ah) Charging Method Trickle charging Charging Current 5 A max.
  • Page 30: Specifications

    11. SPECIFICATIONS 11.1. VX-2000DS Emergency Power Supply Power Source 230 V AC (ER/UK), 220 – 230 V AC (SA), 50/60 Hz Power Consumption 240 W max. Applicable Battery Panasonic LC-X1265PG/APG (65 Ah) Charging Method Trickle charging Charging Current 5 A max. Charging Output Voltage 27.3 V ±0.3 V (at 25°C) Temperature correction coefficient: –40 mV/°C...
  • Page 31: Vx-200Ps Power Supply Unit

    All manuals and user guides at all-guides.com 11.2. VX-200PS Power Supply Unit Power Source 230 V AC (ER/UK), 220 – 230 V AC (SA), 50/60 Hz Power Consumption 580 W DC Power Output Rated output: 210 W (29 V, 7.25 A) x 2 Peak output: 400 W x 2 M4 screw terminal, distance between barriers: 11 mm Applicable cable diameter: AWG 14 –...
  • Page 31: Vx-200Ps Power Supply Unit

    11.2. VX-200PS Power Supply Unit Power Source 230 V AC (ER/UK), 220 – 230 V AC (SA), 50/60 Hz Power Consumption 580 W DC Power Output Rated output: 210 W (29 V, 7.25 A) x 2 Peak output: 400 W x 2 M4 screw terminal, distance between barriers: 11 mm Applicable cable diameter: AWG 14 –...
  • Page 32 All manuals and user guides at all-guides.com Traceability Information for Europe Manufacturer: Authorized representative: TOA Corporation TOA Electronics Europe GmbH 7-2-1, Minatojima-Nakamachi, Chuo-ku, Kobe, Hyogo, Suederstrasse 282, 20537 Hamburg, Japan Germany URL: http://www.toa.jp/ 133-02-00147-00...