AGC 100 Designer's Reference Handbook
Additional functions
4189340766 UK
M-Logic:
6.34.2 Input for fan control
The fan control requires a temperature input in order to start and stop the fans based on a temperature meas-
urement.
Fan temperature input is set up in parameter 6561, and this input can be selected between the multi-configu-
rable inputs: Multi-input 6, 7, 8.
The multi-inputs can be configured to measure an engine- or ambient temperature.
Based on the measurement of the selected input, the fan(s) is (are) started and stopped.
6.34.3 Fan start/stop
The start and stop settings of the fan(s) are set up in parameters 6563 to 6574. With the settings in the table
below, the illustrative curve can be observed.
A hysteresis (abbreviation: hyst.) ensures that there is a range between the start and stop.