QUICK START GUIDE*

Pump Down Cycle
CellarCool's split systems operate on a pump down cycle different from traditional air conditioners. As such, there is no wiring
between the condensing unit and evaporator unit. (However, if the system is equipped with a Cold Weather Start Kit, it will require
two 24-volt wires running from the evaporator unit to the condensing unit.)
CellarCool units utilize a solenoid valve on the liquid line and a low-pressure switch on the suction line. When the thermostat calls
for cooling, the solenoid valve opens, permitting the flow of refrigerant. The low-pressure switch then signals the compressor to
cycle on.
When the cellar reaches the desired temperature and the thermostat is satisfied, the solenoid will close, stopping the liquid
refrigerant flow to the TXV valve. The compressor will continue to operate until most of the refrigerant on the low side boils off
and is pumped through the compressor into the condenser coil and receiver. As the suction pressure falls below the pressure
control setting, the low-pressure switch will signal the compressor to cycle off. Most of the refrigerant is now stored between the
condensing unit and receiver.
Cold Weather Start Kit
If you are installing a unit equipped with the optional cold weather start kit, run two low-voltage wires from the evaporator unit to
the condensing unit.
...............................................................................................................
WARNING: Do not utilize a ground fault interrupter, as it will prevent
the unit from drawing the necessary amperage to start the unit.
TXV Adjustments
A. A TXV adjustment may be necessary based on ambient temperatures in the cellar and at the condensing unit.
B. Adjust the TXV until the superheat is between 8-12°F degrees (measured at the outlet of the evaporator coil).
C. Under normal operation, with the wine cellar at 55°F and the ambient temperature at 85°F, the low side pressure should be
between 28-32 PSI and the high side should be between 170-180 PSI.
The TXV is preadjusted at the factory. If the superheat is not
within 8-12°F, the TXV will need to be adjusted.
Use a ⁄ " hex key to remove the cap from the TXV superheat
adjustment port. With the cap removed, insert the hex key into
the superheat adjustment port. Increase superheat by turning
the hex key clockwise. Decrease superheat by turning the hex
temperature) and the temperature of the liquid line. The temperature
*Further system operation information is available on page 38.
Page 4 | 1-855-235-5271
TXV
ADJUSTING THE TXV
key counterclockwise.
Liquid Line King Valve
This location is used to charge the system with liquid refrigerant
and identify the high side pressure of the system.
Calculating Subcooling
To determine the subcooling of the system, calculate the difference
between the high side pressure of the system (converted to
of the liquid line will be taken at the outlet of the receiver.
*Saturation temp — liquid line temp
5-9°F SUBCOOLING REQUIRED FOR WARRANTY APPROVAL
070517