HID-DynaVision Control SON
Electrical installation notes
Mains operation
Rated mains voltage
With tolerances for performance
With tolerances for operation
Mains frequency
Operation frequency (typical)
Power factor* (nominal power)
Power factor* (35% power)
* With rated PF capacitor value
Earth leakage current (per gear)
Overvoltage protection
Cable length to normal gear
Notes:
1. With three-phase mains supply, neutral should never be
disconnected; otherwise circuitry could be damaged.
2. Gear must be earthed.
3. Power factor correction capacitor should be connected directly
on the mains; when installing this device in front of existing gear, the
original capacitor has to be removed.
HID-DVC
3.124
OEM Catalogue 2009/2010
220 - 240 V
203 - 254 V
180 - 264 V
50/60 Hz
50 Hz
> 0.92
> 0.7
< 0.5 mA
48 hrs at 325 Vac
2 hrs at 366 Vac
5 min at 400 Vac
No limit.
Control characteristics
Control input
Control voltage input
Protected against mains voltage
connection
Control resistance (to be
connected on 1-10V input)
Regulating light level SON
250/400 W
After ignition or lamp restrike allways 100% level for 5 min
Gear dimming fading rates are:
SON 250/400 W
Fade up (35-100%)
Fade down (100-35%)
Mechanical installation notes
Wire cross-section:
On the mains side
On the lamp side
Strip length
1-10 V
Yes
0 - 100 kΩ
20 - 100%
< 1.0 min
< 1.5 min
0.75...2.5 mm
2
0.75...2.5 mm
2
6 mm