GE 869 Instruction Manual page 398

Motor protection system
Hide thumbs Also See for 869:
Table of Contents

Advertisement

MONITORING
4–266
TRIP CIRCUIT MONITORING
Path:
Setpoints > Monitoring > Breaker 1 > Trip Circuit Monitoring
FUNCTION:
Range: Disabled, Latched Alarm, Alarm, Configurable
Default: Disabled
PICKUP DELAY:
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 10.000 s
DROPOUT DELAY:
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
This setting provides selection for reset time delay used to delay the dropout of the
detection of the overcurrent condition.
BYPASS BREAKER STATE:
Range: Enabled, Disabled
Default: Disabled
Set the Bypass Breaker State to Enabled when a by-pass resistor is connected across
the breaker auxiliary contact for continuous Trip circuit monitoring. The circuits are
monitored regardless of breaker position.
BREAKER STATE CLOSED:
Range: Off, Any FlexLogic operand Contact inputs, Virtual inputs, Remote inputs.
Default: Off
This setpoint selects the FlexLogic operand, digital input, virtual input or remote input to
indicate that circuit breaker is closed. When the Bypass Breaker State is set to Disabled,
monitoring of the trip coil is blocked when the breaker is (not closed) open.
BLOCK:
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
For details see
Common
EVENTS:
Range: Disabled, Enabled
Default: Enabled
TARGETS:
Default: Self-reset
Range: Disabled, Self-reset, Latched
Setpoints.
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS