Advertisement

5 SETTINGS
To select a data item to be part of an exchange, it is only necessary to choose the starting Modbus address of the item.
That is, for items occupying more than one Modbus register (e.g. 32 bit integers and floating point values), only the first
Modbus address is required. The EGD exchange configured with these settings contains the data items up to the first
setting that contains a Modbus address with no data, or 0. That is, if the first three settings contain valid Modbus
addresses and the fourth is 0, the produced EGD exchange will contain three data items.
!
PATH: SETTINGS
PRODUCT SETUP

# MODBUS USER MAP

#
MESSAGE
The Modbus User Map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
line (this value must be converted from hex to decimal format). The corresponding value is dis-
ADDRESS
played in the
line. A value of "0" in subsequent register
VALUE
lines incremented by "1". An address value of "0" in the initial register means "none" and values of "0" will be dis-
ADDRESS
played for all registers. Different
These settings can also be used with the DNP protocol. See the DNP Analog Input Points section in Appen-
dix E for details.
NOTE
!
PATH: SETTINGS
PRODUCT SETUP
# REAL TIME
# CLOCK
MESSAGE
The date and time for the relay clock can be synchronized to other relays using an IRIG-B signal. It has the same accuracy
as an electronic watch, approximately ±1 minute per month. An IRIG-B signal may be connected to the relay to synchronize
the clock to a known time base and to other relays. If an IRIG-B signal is used, only the current year needs to be entered.
See also the
!"
COMMANDS
The
REAL TIME CLOCK EVENTS
GE Multilin
!"
MODBUS USER MAP
ADDRESS
1:
VALUE:
0
ADDRESS 256:
VALUE:
0
values can be entered as required in any of the register positions.
ADDRESS
!"

REAL TIME CLOCK

IRIG-B SIGNAL TYPE:
None
REAL TIME CLOCK
EVENTS: Disabled
menu for manually setting the relay clock.
SET DATE AND TIME
setting allows changes to the date and/or time to be captured in the event record.
G60 Generator Management Relay
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
lines automatically returns values for the previous
ADDRESS
Range: None, DC Shift, Amplitude Modulated
Range: Disabled, Enabled
5.2 PRODUCT SETUP
5.2.5 MODBUS USER MAP
5.2.6 REAL TIME CLOCK
5-21