Settings; Information List; General Protection Data (Power System Data 2); Setting Notes - Siemens siprotec 7SD610 User Manual

Differential protection
Hide thumbs Also See for siprotec 7SD610:
Table of Contents

Advertisement

2 Functions
2.1.3.3

Settings

Addr.
Parameter
301
ACTIVE GROUP
302
CHANGE
2.1.3.4

Information List

No.
Information
-
Group A
-
Group B
-
Group C
-
Group D
7
>Set Group Bit0
8
>Set Group Bit1
2.1.4

General Protection Data (Power System Data 2)

The general protection data (P.System Data 2) include settings associated with all
functions rather than a specific protection, monitoring or control function. In contrast
to the P.System Data 1 as discussed before, these can be changed over with the
setting groups and can be configured via the operator panel of the device.
To ensure uniform conversion factors of measured values for WEB-Monitor and
control centres, the setting of all operational rated values of the parameter groups
under P.System Data 2 should be identical.
2.1.4.1

Setting Notes

Rated values of
The information under this margin heading refers to protected lines (cables or over-
protected lines
head lines) if no power transformer is located within the protected zone, i.e. to models
without transformer option or if address 143 TRANSFORMER = NO has been set to,
Section 2.1.1.2).
With address 1103 FullScaleVolt. you inform the device on the primary rated
voltage (phase-to-phase) of the equipment to be protected (if voltages are applied).
This setting influences the displays of the operational measured values in %.
The primary rated current (address 1104 FullScaleCurr.) is that of the protected
object. For cables the thermal continuous current-loading capacity can be selected.
For overhead lines the nominal current is usually not defined; set the rated current of
the current transformers (as set in address 205 CT PRIMARY, Section 2.1.2.1). If the
40
Setting Options
Group A
Group B
Group C
Group D
Group A
Group B
Group C
Group D
Binary Input
Protocol
Type of In-
formation
IntSP
Group A
IntSP
Group B
IntSP
Group C
IntSP
Group D
SP
>Setting Group Select Bit 0
SP
>Setting Group Select Bit 1
Default Setting
Group A
Active Setting Group is
Group A
Change to Another Setting Group
Comments
Comments
7SD610 Manual
C53000-G1176-C145-4