Step Component
Reactor
⑩
replacement
AMP Air Conditioning
Procedure
WARNING
Do not detach the inverter for 5 minutes after
turning off the breaker as doing so may cause
electric shocks.
1) Perform Step 1 of ①, Step 1 of ④.
2) Remove the screws on the reactor.
(M4×8, 4)
3) Mount a new reactor.
CAUTION
When mounting, connect lead wires of the
same color to each reactor. Faulty wiring will
result if the lead wire colors are connected in
alternation.
161