Summary

1.1

Brief description

The ALBATROS controllers described in this documentation are designed for
integration in mass-produced heat generating equipment and offer the following control
choices:
• Single- or 2-stage burner, 1 BMU
• D.h.w. charging pump or diverting valve
• 3-position mixing valve and circulating pump
The range of products comprises several units that are complementary in terms of
application and scope of functions. The controllers have communication capability and
can be combined to form extensive heating systems.
For more detailed information about the generation of LPB systems, refer to "Local
Process Bus (LPB), Basic Documentation, System Engineering", document no.
CE1P2370E.
1.2

Features

• Heating controller for mixing and / or pump heating circuits with:
weather-compensated flow temperature control
weather-compensated flow temperature control with room influence
• 2 separately controlled heating circuits (mixing or pump heating circuits)
• Quick setback and boost heating
• Automatic 24-hour heating limit
• Automatic summer / winter changeover
• Remote operation via digital room unit
• The building's thermal dynamics are taken into consideration
• Automatic adjustment of heating curve to the type of building construction and the
heat demand (provided a room unit is connected)
• Adjustable flow temperature boost with mixing heating circuit
• Floor curing function
1)
• Single- or 2-stage burner
• BMU
(Boiler Management Unit)
• Heat generation lock with contact H
• Protective boiler start-up
• Protection against boiler overtemperatures (pump overrun)
• Adjustable minimum and maximum limitation of boiler temperature (boiler flow
temperature)
• Burner cycling protection by observing a minimum burner running time
• Frost protection for the house or building, the plant, d.h.w., the heating circuit, and the
boiler
• Protection for the pump and the mixing valve through periodic control (pump and
valve kick)
• Adjustable minimum and maximum limitation of flow temperature
• Protection against overtemperatures in the pump heating circuit
Basic Dokumentation RVA63.280, RVA53.280