Page 1
Cat. No. I130E-EN-02 Customised to your machine Model: 3G3RX 200 V Class Three-Phase Input 0.4 to 55 kW 400 V Class Three-Phase Input 0.4 to 132 kW QUick StARt gUidE...
Page 2
OMRON. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is con- stantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice.
Refer to the User’s Manual for detailed information about the product and functions. Basic specifications and EMC filter Type HD (150% overload for 60s) ND (120% overload for 60s) Voltage EMC filter 3G3RX- Max Motor (KW) Rated current (A) Max Motor (KW) Rated current (A) A2004 0.75 A2007 0.75...
-10°C to 50°C Indoor (no corrosive gas, dust, etc.) Installation Installation height Max. 1000 m 3G3RX-A004 to A220, 5.9 m/s (0.6G), 10 to 55 Hz Vibration 3G3RX-A300 to B13K, 2.94 m/s (0.3G), 10 to 55 Hz RX Quick Start Guide...
INSTALLATION 2.4 Installation environment clearance Save enough space to prevent the upper Airflow and lower wiring ducts from blocking cooling airflow. Inverter *1 10 cm min. 5 cm min. 5 cm min. *2 10 cm min. Note that replacing the smoothing capacitor Wall requires 22 cm or more.
RX Quick Start Guide 2.5 Wiring overview Braking resistor DC reactor (optional) (optional) PD/+1 R/L1 U/T1 V/T2 S/L2 T/L3 W/T3 3-phase 200 V AC 3-phase 400 V AC Short-circuit wire To wire the control circuit power supply and main circuit power supply separately, be sure to Relay output *1 remove the J51 connector...
Page 13
INSTALLATION Terminals arrangement Applicable models 3G3RX-A2004 to A2037 3G3RX-A4004 to A4037 R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 Ro, To: M4 Ground terminal: M4 Others: M4 PD/+1 CHARGE LED indicator When not using the DC reactor, keep the PD/+1 - P/+ short-circuit bar PD/+1 - P/+ short-circuit bar attached.
RX Quick Start Guide 3G3RX-A2450 3G3RX-A4450 to A4550 CHARGE LED indicator Ro, To: M4 Ground terminal: M8 Others: M8 R/L1 S/L2 T/L3 PD/+1 U/T1 V/T2 W/T3 PD/+1-P/+ short-circuit bar Ground terminal with short-circuit bar (shaded area) When not using the DC...
Page 15
INSTALLATION Internal 24 VDC Power supply for contact input signal 100 mA max Input common Common terminal for P24, TH and FM digital monitor Forward rotation command terminal Motor runs in forwards direction when FW is ON 27 VDC max Input imped 4.7 k...
RX Quick Start Guide 2.8 Digital inputs SINK/SOURCE (NPN/PNP) settings Sinking internal supply (for NPN outputs) Sinking external supply (for NPN outputs) Short-circuit 24 V DC 24 V DC DC24V Output unit etc. Output unit etc. Inverter Inverter Sourcing internal supply (for PNP outputs) Sourcing external supply (for PNP outputs) 24 V DC Short-circuit...
PROGRAMMING RX 3.2 Navigation LCD digital operator has four display modes which can be changed from one to another by pressing the key at Navi- gation level. Moreover, there are 3 other models called Read mode, Write mode and Option mode. In any display mode, it moves to Read mode or Write mode via key or key, and moves to Option mode after pressing...
RX Quick Start Guide 3.4 Initialization Initialize the parameters use the following procedure. Set parameter b084 to "2" and parameter b180 to "1". Display example Description FUNCTION M1-STOP ALL FUNCTION M1-STOP ALL Press the Prev. Page or Next Page key With the Prev.
PROGRAMMING RX Func. Name code Carrier frequency b083 0.5 to 15.0(kHz) 0.4-55kW 5.0(kHz) 0.4-55kW 0.5 to 10.0(kHz) 0.4-55kW 3.0(kHz) 0.5 to 10.0(kHz) 75-132kW 0.5 to 8.0(kHz) 75 - 132kW Motor capacity selection H003 0.2 to 160(kW) Depends on type 0.4 to 160(kW) 1 size up than HD 3.6 Basic settings After selecting the inverter mode follow next steps for a basic operation of the inverter...
RX Quick Start Guide 3.7 Auto tuning (vector control modes) The RX inverter has auto-tuning function to get suitable motor control performance by measuring the motor constants automat- ically. Auto-tuning is effective only for vector control types (sensorless, 0-Hz or sensor type). Basically two modes are available the static and the rotative: •...
Page 21
PROGRAMMING RX Next diagram shows the auto-tuning procedure with motor rotation Step 1: Set motor size and Step 2:Set base freq. and Step 3: Enable auto-tuning motor poles AVR voltage H001 A003 H003 Base freq. Motor size H004 A082 Motor poles AVR voltage Result is displayed Auto-tuning starts...
RX Quick Start Guide 3.8 Ramps adjustment The basic frequency (speed) profile is defined by parameters con- Output tained in the "F" Group as shown to the right. The set running fre- frequency F002 F003 quency is in Hz, but acceleration and deceleration are specified in the time duration of the ramp (from zero to maximum frequency, A004 or from maximum frequency to zero).
PROGRAMMING RX This table shows the different acceleration shapes Setting Curve Line S-curve U-curve Inverse U-curve EL S-curve A097 F re q . F re q . F re q . F re q . F re q . (Accel. pattern) A098 (Decel.
Page 24
RX Quick Start Guide • DC braking by frequency detection can be selected setting A051 to “02” (Frequency detection). In this case DC braking oper- ates when the output frequency comes down to the one you specified in A052 while the RUN command is still active. Exter- nal DB and internal DC braking are invalid during the frequency detection mode.
PROGRAMMING RX 3.10 V/F curve The inverter generates the motor output according to the V/f algorithm selected Constant torque on parameter A044. The factory default is Constant torque (“00”). Review fol- A044=00 100% lowing description to help you choose the best torque control algorithm for your application:.
RX Quick Start Guide Automatic torque boost- Use the voltage compensation (A046) and slip compensation (A047) to obtain a better performance under automatic torque boost mode (A041=01) adjusting the output frequency and output voltage automatically depending on the load. The output voltage due automatic boost is added to the manual torque boost voltage so both should be adjusted. Parameter Parameter Name Description...
PROGRAMMING RX Parameter Parameter name Description A016 O, O2, OI sampling 1 to 30 31 (with 500ms filter ±0.1 Hz hysteresis) A111 O2 start frequency -400.00 to 400.00 Hz A112 O2 end frequency -400.00 to 400.00 Hz A113 O2 start ratio -100% to O2 end ratio A114 O2 end ratio...
Page 28
RX Quick Start Guide Input Function Summary Table Option Terminal Function Name Description Code Symbol Multi-step speed setting bit 1 Bit encoded speed select, Bit 1 to Bit 7 Multi-step speed setting bit 2 Multi-step speed setting bit 3 Multi-step speed setting bit 4 Multi-step speed setting bit 5 Multi-step speed setting bit 6 Multi-step speed setting bit 7...
PROGRAMMING RX All this functions could be assigned to any of the multi-function inputs on parameters C001 to C008, select if the input will be normally open or normally close and the response time of the input. Parameter Parameter name Description C001 Multi-function input 1 selection...
Page 30
RX Quick Start Guide Output Function Summary Table Option Terminal Function Name Description Code Symbol Brake error Brake error has occurred 0 Hz signal Output frequency falls below the threshold specified in C063 Excessive speed deviation Deviation of speed command and actual speed exceeds the specified value P027. Position ready Positioning is completed Set frequency exceeded 2...
PROGRAMMING RX Parameter Parameter name Description C130 Output 11 ON delay 0.0 to 100.0 s C131 Output 11 OFF delay C132 Output 12 ON delay 0.0 to 100.0 s C133 Output 12 OFF delay C134 Output 13 ON delay 0.0 to 100.0 s C135 Output 13 OFF delay C136...
RX Quick Start Guide 3.16 Torque limit Torque limit function allows you to limit the motor output when sensorless vector control “03”, 0-Hz sensorless vector control “04” or sensor vector control “05” is selected in A044. In open loop vector function has limited accuracy and repeatability, per- formance is much better when encoder feedback is used.
PROGRAMMING RX 3.17 Torque control Torque control is only available in sensor vector control A044=”05” and it requires to setup following parameters. 100% torque is referred to inverter rated current but absolute torque value depends on the motor connected. Parameter Parameter name Description P033...
RX Quick Start Guide b013 could be used to match the torque characteristic with the load. Output current on the winding is used for this calculation as is proportional to the torque generated by the motor. That’s why the current level has to be set in parameter b012 with a range that goes from 20 to 100% of the inverter rated current.
PROGRAMMING RX In standard operation, inverter uses a reference source selected by A001 for the output frequency which may be a fixed or vari- able value. To enable PID operation is necessary to set A071 to “01” and this will cause the inverter to calculate the target fre- quency or set point.
RX Quick Start Guide Parameter Parameter name Description b021 Overload limit selection 00: OFF (Disabled) 01: ON-Acc/Cnst (Enabled in acceleration/constant speed operation) 02: ON-Cnst (Enabled in constant speed operation) 03: ON-A/C(R) (Enabled in acceleration/constant speed operation (Accelerates during regeneration)) b022 Overload limit level 0.20 x Rated current to 2.00 x Rated current (0.4 to 55 kW) 0.20 x Rated current to 1.80 x Rated current (75 to 132 kW)
PARAMETER LIST b052 > Main circuit DC voltage at recovery b052 < Main circuit DC voltage at recovery Main circuit DC voltage Main circuit P-N voltage Main circuit P-N voltage at power recovery Vpn (V) Vpn (V) b052 b052 Power recovery b051 b051 Main circuit DC voltage...
Page 38
RX Quick Start Guide Function code Function name Monitoring and setting items Units Modbus Register No. d005 Multi-function input monitor 1007h Example MONITOR-A M1-STOP ALL FW, Multi-function input terminals 7, 2, 1: ON d005 Input Multi-function input terminals 8, 6, 5, 4, 3: OFF HLHLLLLHH H001 00:OFF...
PARAMETER LIST 4.2 Parameter group A Function code Function name Monitoring and setting items Units Modbus Default mode Register edit Nº A001 Frequency reference selection 00: VR (Digital operator (FREQ adjuster)) – 1201h 01: Terminal 02: Digital operator (F001) 03: RS485 (Modbus communication) 04: Option 1 05: Option 2...
Page 40
RX Quick Start Guide Function code Function name Monitoring and setting items Units Modbus Default mode Register edit Nº A032 Multi-step speed reference 12 0.00/starting frequency to max frequency 122Eh 0.00 122Fh A033 Multi-step speed reference 13 0.00/starting frequency to max frequency 1230h 0.00 1231h...
Page 41
PARAMETER LIST Function code Function name Monitoring and setting items Units Modbus Default mode Register edit Nº A067 Jump frequency 3 0.0 to 400.00 1259h 0.00 125Ah A068 Jump frequency width 3 0.0 to 10.00 125Bh 0.50 A069 Acceleration stop frequency 0.0 to 400.00...
RX Quick Start Guide Function code Function name Monitoring and setting items Units Modbus Default mode Register edit Nº A105 OI start selection 00: Start FQ (Use OI start frequency [A101]) – 1287h 01: 0 Hz A111 O2 start frequency -400.00 to 400.00 128Dh 0.00...
Page 43
PARAMETER LIST Function code Function name Monitoring and setting items Units Modbus Default mode Register edit b213 2nd electronic thermal characteristics selection 00: Reduced TRQ (Reduced torque characteristics) – 230Dh 01: Const TRQ (Constant torque characteristics) 02: Free set (Free setting) ...
Page 44
RX Quick Start Guide Function code Function name Monitoring and setting items Units Modbus Default mode Register edit b046 Reverse rotation prevention selection 00: OFF (Disabled) – 1330h 01: ON (Enabled) b049 Dual rate selection 00: CT (Constant torque) –...
PARAMETER LIST Function code Function name Monitoring and setting items Units Modbus Default mode Register edit b110 Free V/F frequency 6 0 to free V/F frequency 7 1371h b111 Free V/F voltage 6 0.0 to 800.0 1372h b112 Free V/F frequency 7 0 to 400...
Page 46
RX Quick Start Guide Function code Function name Monitoring and setting items Units Modbus Default mode Register edit C035 Multi-function output terminal 15 contact selection 00: NO – 1423h 01: NC C036 Relay output (AL2, AL1) contact selection 00: NO contact at AL2;...
Page 47
PARAMETER LIST Function code Function name Monitoring and setting items Units Modbus Default mode Register edit C103 Reset frequency matching selection 00: 0 Hz start – 146Bh 01: f-match (Frequency matching start) 02: Actv. f-match (Active frequency matching restart) ...
PARAMETER LIST Function code Function name Monitoring and setting items Units Modbus Default mode Register edit H033 Motor parameter Io (auto-tuning data) 0.01 to 655.35 152Ah 152Bh H233 2nd motor parameter Io (auto-tuning data) 0.01 to 655.35 252Ah 252Bh ...
Page 50
RX Quick Start Guide Function code Function name Monitoring and setting items Units Modbus Default mode Register edit P034 Torque reference setting 0 to 200 (0.4 to 55 kW) 1622h 0 to 180 (75 to 132 kW) P035 Polarity selection at torque reference via O2 00: Sign (Signed) –...
Page 51
PARAMETER LIST Function code Function name Monitoring and setting items Units Modbus Default mode Register edit P102 Drive program parameter U(02) 0 to 65535 1668h P103 Drive program parameter U(03) 0 to 65535 1669h P104 Drive program parameter U(04) 0 to 65535 166Ah ...
RX Quick Start Guide 4.7 Parameter group F Function code Function name Monitoring and setting items Units Modbus Default mode Register edit 0001h 0.0/Starting frequency to 1st/2nd/3rd max. frequency 0.00 F001 Output frequency setting/monitor 0.00 to 400.00 0002h 1103h ...